Fast EGEA - RWP Use, Installation And Maintenance Manual

Water cooled chillers, heat pumps and motoevaporating units

Advertisement

Quick Links

EGEA - RWP
Water cooled chillers, heat pumps
and motoevaporating units
Capacities from 21 kW to 280 kW
USE, INSTALLATION AND
MAINTENANCE MANUAL
GB

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EGEA - RWP and is the answer not in the manual?

Questions and answers

Summary of Contents for Fast EGEA - RWP

  • Page 1 EGEA - RWP Water cooled chillers, heat pumps and motoevaporating units Capacities from 21 kW to 280 kW USE, INSTALLATION AND MAINTENANCE MANUAL...
  • Page 3: Table Of Contents

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series Summary GENERALITIES pg. 4 STANDARD VERSIONS AND ACCESSORIES pg. 4 COMPONENTS DESCRIPTION pg. 5 NOMINAL TECHNICAL DATA pg. 6 PERFORMANCE TABLES pg. 10 APPLICATION LIMITS pg. 12 SOUND PRESSURE LEVELS pg.
  • Page 4: Generalities

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series EGEA-RWP F-H-ME-HW GENERALITIES The EGEA-RWP series is made of 16 sizes of water cooled chillers with scroll compressors covering a range of capacities from 20 to 280 kW. A single circuit version is available for the fi rst 12 sizes (from 20 to 140 KW), double circuit version for the remaining models.
  • Page 5: Components Description

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series EGEA RWP (F-H-ME-HW) 21 - 280 COMPONENTS DESCRIPTION COMPRESSORS Hermetic scroll compressors provided with internal thermal protection. Direct starting. The cooling capacity control is made through capacity steps depending on the installed compressors number. The compressors are located in a soundproof technical room.
  • Page 6: Nominal Technical Data

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series EGEA RWP F-H-ME-HW 21 - 40 Size Cooling capacity (1) F/ME [kW] 21,4 28,4 37,1 42,5 Input power (1) F/ME [kW] 10,3 Heating capacity (2) HW-H [kW] 27,8...
  • Page 7 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series EGEA RWP F-H-ME-HW 45 - 80 Size Cooling capacity (1) F/ME [kW] 42,8 56,8 74,2 85,6 Input power (1) F/ME [kW] 10,4 13,4 17,8 20,6 Heating capacity (2) HW-H...
  • Page 8 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series EGEA RWP F-ME-HW 110 - 170 Size Cooling capacity (1) F/ME [kW] 110,4 148,4 171,2 Input power (1) F/ME [kW] 34,3 35,6 41,2 Heating capacity (2) HW [kW]...
  • Page 9 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series EGEA RWP F-ME-HW 200 - 280 Size Cooling capacity (1) F/ME [kW] 220,8 247,4 273,9 Input power (1) F/ME [kW] 48,6 62,4 68,7 Heating capacity (2) HW [kW]...
  • Page 10: Performance Tables

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series twc: cond. in/out temp. [°C] Pf: Cooling capacity [kW] EGEA RWP F-H-ME-HW 21 - 70 twe: evap. in/out temp. [°C] Pt: Heating capacity [kW] *: condensing temp. [°C]...
  • Page 11 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series twc: cond. in/out temp. [°C] Pf: Cooling capacity [kW] EGEA RWP F-H-ME-HW 80 - 220 twe: evap. in/out temp. [°C] Pt: Heating capacity [kW] *: condensing temp. [°C]...
  • Page 12: Application Limits

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series twc: cond. in/out temp. [°C] Pf: Cooling capacity [kW] EGEA RWP F-H-ME-HW 250 - 280 twe: temp. evap. in/out temp. [°C] Pt: Heating capacity [kW] *: condensing temp. [°C]...
  • Page 13: Dimensions

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series EGEA RWP F-H-ME-HW 21-40 evap. water inlet temp. 1” GAS evap. water outlet temp. 1” GAS condenser water inlet temp. 1” GAS condenser water outlet temp. 1” GAS...
  • Page 14 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series EGEA RWP F-ME-HW 110-140 1400 1050 1190 A: water inlet temp. 2” GAS B: water outlet temp. 2” GAS C: condenser water inlet temp. 2” GAS D: condenser water outlet temp. 2” GAS...
  • Page 15: Safety

    Egea - RWP Series SAFETY The FAST chiller IDRA-RWS series have been designed in order to minimize all the possible risks for the operators safety. Please, read carefully the following instruction in order to be aware of the possible dangerous situations while operating with the unit.
  • Page 16: Receipt And Storage

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series RECEIPT AND STORAGE On receipt of the goods, verify they have not been damaged and they conform to what indicated in the transport documen- ts. Damages or incomplete supplies must be immediately notifi ed.
  • Page 17: Positioning

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series POSITIONING Install the unit respecting the clerances indicated in the dimensional drawings. Lay the unit on an even surface, robust enough to bear its weight. Antivibrations dampers Rubber antivibration dampers are supplied as an option. Fitted to the holes in the basement, they prevent vibrations tran- smission.
  • Page 18: Start-Up

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series WIRING CONNECTIONS The inlet for the electrical feeding cables is shown in the dimensional drawings. Remove the front panel in the upper part of the unit to access the electric board; refer to the power and current values indicated in the present manual to size the electrical feeding cables.
  • Page 19: Winter Stop

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series Preliminary checks - hydraulic circuit - verify the correct connection between the unit and the plant pipes; - verify that the hydraulic shut-off valves are open; - verify that the plant is charged;...
  • Page 20: Unit Dismantling

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series Maintenance We suggest a monthly maintenance procedure to be carried out as follows: - verify the tightening of the bolts fi xing the fans to the grilles and the grilles to the unit structure;...
  • Page 21: Refrigeration Circuit Diagrams

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series REFRIGERATION CIRCUIT DIAGRAMS EGEA-RWP REFRIGERATION CIRCUIT C = compressor F = drier-fi lter VS = solenoid valve PA = high pressure switch IL = sight glass AN = antivibration pipe PB = low pressure switch PD = fl...
  • Page 22: Electrical Data

    29,4 29,4 29,4 117,6 Power[kW] 29,4 29,4 40,6 40,6 Power[kW] 40,6 40,6 40,6 40,6 162,4 * Optional ** For the electrical wirings of the models F-HW 200-220-280 and the models ME 150-170-200-220-250-280 please contact FAST Use, installation and maintenance manual...
  • Page 23: Electrical Wirings

    Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-H-HW 21-26-34-40 Use, installation and maintenance manual...
  • Page 24 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-H-HW 21-26-34-40 TERMINAL PLATE Use, installation and maintenance manual...
  • Page 25 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-H-HW 45-55-70-80 Use, installation and maintenance manual...
  • Page 26 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-H-HW 45-55-70-80 ONLY ON EGEA H ONLY ON EGEA F SOLO SU EGEA “F” SOLO SU EGEA “H” TERMINAL PLATE Use, installation and maintenance manual...
  • Page 27 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 110-140 Use, installation and maintenance manual...
  • Page 28 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 110-140 ONLY ON EGEA H ONLY ON EGEA F SOLO SU EGEA “F” SOLO SU EGEA “H” Use, installation and maintenance manual...
  • Page 29 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 110-140 TERMINAL PLATE Use, installation and maintenance manual...
  • Page 30 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 150 Use, installation and maintenance manual...
  • Page 31 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 150 Use, installation and maintenance manual...
  • Page 32 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 150 TERMINAL PLATE Use, installation and maintenance manual...
  • Page 33 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 170 Use, installation and maintenance manual...
  • Page 34 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 170 Use, installation and maintenance manual...
  • Page 35 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 170 TERMINAL PLATE Use, installation and maintenance manual...
  • Page 36 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 250 Use, installation and maintenance manual...
  • Page 37 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 250 Use, installation and maintenance manual...
  • Page 38 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP F-HW 250 TERMINAL PLATE Use, installation and maintenance manual...
  • Page 39 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP ME 21-26-34-40 Use, installation and maintenance manual...
  • Page 40 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP ME 21-26-34-40 TERMINAL PLATE Use, installation and maintenance manual...
  • Page 41 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP ME 45-55-70-80 Use, installation and maintenance manual...
  • Page 42 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP ME 45-55-70-80 ONLY ON EGEA H ONLY ON EGEA F SOLO SU EGEA “F” SOLO SU EGEA “H” TERMINAL PLATE Use, installation and maintenance manual...
  • Page 43 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP ME 110-140 Use, installation and maintenance manual...
  • Page 44 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP ME 110-140 ONLY ON EGEA H ONLY ON EGEA F SOLO SU EGEA “F” SOLO SU EGEA “H” Use, installation and maintenance manual...
  • Page 45 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series ELECTRICAL WIRINGS EGEA RWP ME 110-140 Use, installation and maintenance manual...
  • Page 46 Water cooled chillers, heat pumps and motoevaporating units Egea - RWP Series LABEL DESCRIPTION LABEL DESCRIPTION PHASE CONTROL AUTOMATIC SWITCH D100 MICROPROCESSOR QFA1 AUTOMATIC SWITCH D110 TERMINAL PANEL QFC1 AUTOMATIC SWITCH D130 REMOTE PANEL QFC2 AUTOMATIC SWITCH D200 EXPANSION QFC3...
  • Page 48 Technical data shown in this booklet are not binding. FAST S.p.A. shall have the right to introduce at any time whatever modi- fications deemed necessary to the improvement of the product.