Adp ModuleFlex MX Series Installation Instructions Manual

Indoor modular blowers

Advertisement

Available languages

Available languages

Quick Links

TABLE OF CONTENTS
Air Handler Safety ............................................................... 1
Wiring Diagrams .................................................................. 2
Thermostat Connections ..................................................... 4
Blower Performance Data ................................................... 5
Inspect Shipment ................................................................ 6
Installation Requirements .................................................... 6
Tools and Parts................................................................... 6
Location Requirements ....................................................... 7
Installation Clearances ........................................................ 7
Installation Configurations ................................................... 7
Electrical Requirements ...................................................... 9
To install the MX Series Air Handler in the horizontal position a (2") clearance must be maintained between the apex of the
evaporator coil and the top of the coil's cabinet. Therefore, the ADP multi-position evaporator coils listed below cannot be
used in the horizontal position with the MX Series Air Handler. The HD Series and V Series dedicated horizontal coils are
recommended for these applications.
Slab numbers: A07, A15, E27, E37, E48, E50, E55, E57, E87, and E88.
Slab numbers E25 and E35 in 21.5"h cabinet.
Slab number E54 in 29.5"h cabinet.
AIR HANDLER SAFETY
Your safety and the safety of others are very
important.
We have provided many important safety messages in this manual and
on your appliance. Always read and obey all safety messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or
hurt you and others.
All safety messages will follow the safety alert symbol and
either the word "DANGER" or "WARNING." These words mean:
Product improvement is a continuous process at Advanced Distributor Products. Therefore, product specifications are subject to change without notice and
without obligation on our part. Please contact your ADP representative or distributor to verify details.
MX Series
Indoor Modular Blowers─ModuleFlex
Electric or Hot Water Heat
© 2025 by Advanced Distributor Products. All rights reserved.
2140 Lake Park Blvd, Richardson, TX 75080
Installation Instructions
PAGE
Ductwork Requirements ...................................................... 9
Blower and Coil Assembly ................................................ 10
Install Ductwork ................................................................. 11
Make Electrical Connections ............................................. 11
Hot Water Coil Flushing .................................................... 12
Hot Water Coil Installation ................................................. 13
Complete Installation ......................................................... 14
Sequence of Operation ..................................................... 15
MX Series Air Handler Maintenance ................................. 18
Assistance or Service ........................................................ 18
Warranty ............................................................................ 19
WARNING
DANGER: You can be killed or seriously injured if you don't
immediately follow instructions.
WARNING: You can be killed or seriously injured if you don't follow
instructions.
All safety messages will tell you what the potential hazard is, tell you how
to reduce the chance of injury, and tell you what can happen if the
instructions are not followed.
www.adpnow.com
IM-MAH-US-0662403-14
November 2024
®
PAGE

Advertisement

loading
Need help?

Need help?

Do you have a question about the ModuleFlex MX Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Adp ModuleFlex MX Series

  • Page 1 To install the MX Series Air Handler in the horizontal position a (2”) clearance must be maintained between the apex of the evaporator coil and the top of the coil’s cabinet. Therefore, the ADP multi-position evaporator coils listed below cannot be used in the horizontal position with the MX Series Air Handler.
  • Page 2: Wiring Diagrams

    CAUTION This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  • Page 3 PART NO. 67844700 WIRING DIAGRAM - MX, PSC, 120 V, HW PART NO. 67876800 WIRING DIAGRAM - MX, VSM, 120 V, HW...
  • Page 4: Thermostat Connections

    THERMOSTAT CONNECTIONS 5-Speed Motor (Electric Heat) Maximum allowable current draw from power-stealing thermostats or other accessories is 18 mA. Exceeding this value may cause the Air Handler control board to operate abnormally. For 2 stage outdoor units: Identify desired tap/CFM for 1st stage from airflow chart and move motor lead on terminal board to Y1. Identify desired tap/CFM for 2nd stage from airflow chart and move motor lead on terminal board to Y2.
  • Page 5: Blower Performance

    BLOWER PERFORMANCE Speeds marked in bold with an asterisk* are the factory speed settings for cooling. All data is given while air handler is operating with a dry coil and air filter installed. These are nominal values and blower performance can vary higher or lower from these values based on the evaporator coil that is used.
  • Page 6: Inspect Shipment

    INSPECT SHIPMENT The blower section is completely factory assembled, and all 3. If damage is found, it should be noted on the carrier’s components are performance tested. Each unit consists of a freight bill. Damage claims should be filed with carrier blower assembly and controls, in an insulated galvanized steel immediately.
  • Page 7: Location Requirements

    LOCATION REQUIREMENTS NOTE: When the unit is installed in a very humid space and • The blower and its complementing coil must be installed used in cooling applications, excessive sweating may occur on in such a way as to allow free access to the blower/ outside of unit.
  • Page 8 Conversion from Vertical to Horizontal Horizontal Configuration of Blower with an ADP Dedicated Horizontal “A” Coil. The MX Series Air Handler can be converted from operating in a vertical to a horizontal position by installing supporting brack- ets (included with all MX Series Air Handlers) between the two pieces of equipment.
  • Page 9: Electrical Requirements

    ELECTRICAL REQUIREMENTS NOTE: Use copper conductors only. WARNING • All field wiring must be done in accordance with National Electrical Shock Electrical Code, applicable requirements of UL and local codes, where applicable. Disconnect power before servicing. • Electrical wiring, disconnect means and over-current pro- Replace all parts and panels before operating.
  • Page 10 (right). 4. The MX is designed to fit perfectly with the ADP “C” depth (20.5”) coil. If “E” depth is used, modify the duct flange as follows: with the front of the MX and coil...
  • Page 11: Install Ductwork

    INSTALL DUCTWORK IMPORTANT: • • Install ductwork in accordance with NFPA 90B and any Duct connections for the MX Series Air Handler with hot local codes. water heat must allow room for water piping connections to be made in upflow and downflow configurations. •...
  • Page 12 MAKE ELECTRICAL CONNECTIONS CONT. 208-Volt Conversion Changing Circuit Breaker Orientation Handlers with Circuit Breaker Line Voltage 1. Disconnect all power supplies. Connections: 2. Remove the MX Series Air Handler access panel. If the MX Series Air Handler is positioned in a horizontal left- 3.
  • Page 13 Insulating piping or using a water-glycol solution may help prevent pipe freezing. Bleed Valve ADP MX Series Air Handlers with hot water heating coils can be used with potable water systems (Not Approved for pota- Pump/Check ble water systems in the State of MA) and are shipped with Valve Assy or without circulating pumps.
  • Page 14: Complete Installation

    COMPLETE INSTALLATION NOTE: Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging instructions. Check / Change Airflow • For proper cooling operation, the airflow through the in- PRE-Start Check door coil should be between 350 and 450 CFM per ton of cooling capacity (or 350 –...
  • Page 15: Sequence Of Operations

    COMPLETE INSTALLATION CONT. Models 08, 12, & 20 with 120 V Supply Voltage Model 16 with 120 V Supply Voltage 1. Disconnect all power supplies. 1. Disconnect all power supplies. 2. Remove the air handler access panel. 2. Remove the air handler access panel. 3.
  • Page 16 SEQUENCE OF OPERATIONS CONT. Hot Water Heat Models The Blower Door Safety Switch circuit must be complete for all Sequence of Operations to take place. Drawing of Multi-function Control Board, factory installed in all MX Series Air Handlers with hot water heat. Please take precautions while installing the Air Handler to keep Multi -function Control Board and other controls from getting wet! Cooling...
  • Page 17 Pump Timer (hot water heat) Water Heat The State of Massachusetts requires the use of a pump timer For all non-ADP external aquastats used in conjunction with on domestic water applications to periodically circulate water this air handler, please follow the installation instructions pro- during the off cycle.
  • Page 18: Assistance Or Service

    MX SERIES AIR HANDLER MAINTENANCE At the beginning of each heating season the unit should be serviced by a qualified installer or servicing agency. ASSISTANCE OR SERVICE If you need further assistance, you may contact us at the address below with any questions or concerns. Please include a day- time phone number in your correspondence.
  • Page 19 ADP AIR HANDLER LIMITED WARRANTY Term of Warranty Equipment Information Advanced Distributor Products (ADP) warrants that products Please complete information below and retain this warranty for records and future reference. sold shall be of merchantable quality, free of defects in...
  • Page 20 WARRANTY PARTS REGISTRATION FINDER 2140 Lake Park Blvd, Richardson, TX 75080 www.adpnow.com...
  • Page 21: Table Of Contents

    L’amélioration des produits est un processus continu chez Advanced Distributor Products. Par conséquent, les spécifications du produit peuvent être modifiées sans préavis et sans obligation de notre part. Veuillez contacter votre représentant ou distributeur ADP pour vérifier les détails. © 2025 par Advanced Distributor Products. Tous droits réservés.
  • Page 22: Schéma De Câblage

    ATTENTION Cet appareil n’est pas conçu pour être utilisé par des personnes (y compris des enfants) ayant des capacités physiques, sensorielles ou mentales réduites, ou un manque d’expérience et de connaissances, sauf si elles ont été surveillées ou que des instructions ont été...
  • Page 23 PIÈCE NO. 67844700 | SCHÉMA DE CÂBLAGE - MX, PSC, 120 V, HW PIÈCE NO. 67876800 | SCHÉMA DE CÂBLAGE - MX, VSM, 120 V, HW...
  • Page 24: Connexions Du Thermostat

    CONNEXIONS DU THERMOSTAT Moteur 5-Speed (chauffage électrique) Le courant maximum autorisé des thermostats ou autres accessoires est de 18 mA. Un dépassement de cette valeur peut entraîner un fonctionnement anormal du panneau de commande du ventilo-convecteur. Pour les unités extérieures à 2 stages : Identifier le taraud/CFM désiré...
  • Page 25: Rendement Du Ventilateur

    RENDEMENT DU VENTILATEUR Les vitesses indiquées en gras avec un astérisque* sont les réglages de vitesse usine pour la climatisation. Toutes les données sont données quand le ventilo-convecteur fonctionne avec un serpentin sec et un filtre à air installés. Il s’agit de valeurs nominales et le rendement du ventilateur peut varier plus ou moins par rapport à ces valeurs en fonction du serpentin d’évaporateur utilisé.
  • Page 26: Inspecter L'expédition

    CONNEXIONS DU THERMOSTAT Moteur 5-Speed (chauffage électrique) Le courant maximum autorisé des thermostats ou autres accessoires est de 18 mA. Un dépassement de cette valeur peut entraîner un fonctionnement anormal du panneau de commande du ventilo-convecteur. Pour les unités extérieures à 2 stages : Identifier le taraud/CFM désiré...
  • Page 27: Exigences Relatives À L'emplacement

    RENDEMENT DU VENTILATEUR Les vitesses indiquées en gras avec un astérisque* sont les réglages de vitesse usine pour la climatisation. Toutes les données sont données quand le ventilo-convecteur fonctionne avec un serpentin sec et un filtre à air installés. Il s’agit de valeurs nominales et le rendement du ventilateur peut varier plus ou moins par rapport à ces valeurs en fonction du serpentin d’évaporateur utilisé.
  • Page 28: Configurations D'installation

    être installée sous le ventilo- Configuration horizontale du ventilateur avec convecteur et le serpentin de la série MX comme spécifié un serpentin « A » horizontal dédié ADP. par la plupart des codes du bâtiment locaux. Conversion de Vertical à Horizontal Le ventilo-convecteur de la série MX peut être converti en...
  • Page 29: Exigences Électriques

    EXIGENCES ÉLECTRIQUES REMARQUE : Utiliser uniquement des conducteurs en cuivre. AVERTISSEMENT • Tout le câblage sur place doit être effectué conformément Choc électrique au National Electrical Code, aux exigences applicables des codes UL et locaux, le cas échéant. Déconnecter l’alimentation électrique avant de procéder à...
  • Page 30: Ensemble Ventilateur Et Serpentin

    HD (droite). 4. Le MX est conçu pour s’adapter parfaitement au serpentin ADP de profondeur « C » (20,5 po). Si la profondeur « E » est utilisée, modifier la bride du conduit comme suit : avec l’avant du MX et le serpentin alignés, couper la bride arrière du serpentin de chaque côté...
  • Page 31: Installation Des Gaines

    INSTALLATION DES GAINES IMPORTANT: • • Installer les gaines conformément à la norme NFPA 90B Les connexions des conduits pour le ventilo-convecteur et aux codes locaux. de la série MX avec chauffage à l’eau chaude doivent laisser de la place pour les connexions des conduites •...
  • Page 32: Rinçage Du Serpentin D'eau Chaude

    EFFECTUER LES CONNEXIONS ÉLECTRIQUES SUITE Conversion 208-Volt Modification de l’orientation du disjoncteur Pour les ventilo-convecteurs avec connexions de tension de 1. Déconnecter toutes les sources d'alimentation. ligne du disjoncteur : 2. Retirer le panneau d’accès au ventilo-convecteur de la Si le ventilo-convecteur de la série MX est positionné en série MX.
  • Page 33: Installation Du Serpentin D'eau Chaude

    à éviter le gel des conduites. Bleed Valve Pump/Check Les ventilo-convecteurs de la série ADP MX équipés de Valve Assy serpentins de chauffage à eau chaude peuvent être utilisés avec des systèmes d’eau potable (non approuvés pour les...
  • Page 34: Installation Complète

    INSTALLATION COMPLÈTE REMARQUE : Se reporter aux instructions d'installation de 2. Régler le thermostat de manière à ce qu’il ne demande l'unité extérieure pour les instructions de démarrage du pas de chauffage. Attendre jusqu’à 5 minutes pour que système et les instructions de chargement du réfrigérant. tous les séquenceurs s’éteignent.
  • Page 35: Séquence De Fonctionnement

    INSTALLATION COMPLÈTE SUITE Modèles 08, 12 et 20 avec tension d’alimentation de 120 V Modèle 16 avec tension d’alimentation de 120 V 1. Déconnecter toutes les sources d'alimentation. 1. Déconnecter toutes les sources d'alimentation. 2. Retirer panneau d’accès d'accès ventilo- 2.
  • Page 36 SÉQUENCE DE FONCTIONNEMENT SUITE Modèles avec chauffage à eau chaude Le circuit de l’interrupteur de sécurité de la porte du ventilateur doit être terminé pour que toutes les séquences de fonctionnement aient lieu. Dessin du contrôleur multifonction installé en usine sur tous les ventilo-convecteurs de la série MX avec chauffage à...
  • Page 37 Minuterie de la pompe (chauffage à l’eau chaude) ADP - Chauffage à eau chaude L’État du Massachusetts exige l’utilisation d’une minuterie Pour tous les aquastats externes non-ADP utilisés avec ce pour les applications avec eau domestique pour faire circuler ventilo-convecteur,...
  • Page 38: Entretien Du Ventilo-Convecteur De La Série

    ENTRETIEN DU VENTILO-CONVECTEUR DE LA SÉRIE MX Au début de chaque saison de chauffage, l’unité doit être entretenue par un installateur ou une société d’entretien qualifié. ASSISTANCE OU SERVICE Si vous avez besoin d’aide, vous pouvez nous contacter à l’adresse ci-dessous pour toute question ou préoccupation. Veuillez indiquer un numéro de téléphone de jour dans votre correspondance.
  • Page 39: Garantie

    Durée de la garantie Information sur l’équipement Veuillez écrire les renseignements demandés ci-dessous et Advanced Distributor Products (ADP) garantit que ses produits conserver la présente garantie dans vos dossiers, pour con- vendus seront de qualité marchande, exempts de défauts de sultation future.
  • Page 40 ENREGISTREMENT RECHERCHE DE DE LA GARANTIE PIÈCES 2140 Lake Park Blvd, Richardson, TX 75080 www.adpnow.com...