Duct Humidity and Temperature Sensor
Important: Retain these instructions
These instructions shall be used by trained service
personnel only.
If the equipment is used in a manner not
specifi ed by these instructions, the protection provided by the
equipment may be impaired.
CONTENTS
1
Box Contents .................................................................1
2
Installation .....................................................................1
3
Fault Finding ..................................................................3
4
Maintenance ..................................................................4
5
Humidity Calibration ......................................................4
6
Disposal .........................................................................4
2
INSTALLATION
Dimensions
1
33 mm (1.3")
Requirements
2
measurement ranges
0°C
+40°C
(32°F)
(104°F)
+50°C
-5°C
-20°C
(23°F)
(122°F)
(-4°F)
V > 10 m/s, 33'/s
Or: using optional mounting fl ange (ACC/FLANGE/12MM/5)
45 mm (1.77")
Ø circle
4 holes
Ø 23 mm
Ø 4 mm (0.16")
(0.91")
HT/D/2% Duct Humidity and Temperature Sensor Installation Instructions TG200988 Issue 5, 19-Feb-2021
12 mm diam
(0.47")
263 mm (10.35")
M20x1.5
gland
0 %RH
100 %RH
non-condensing
Protection :IP65
H O
2
+60°C
(140°F)
Installation Instructions
https://partners.trendcontrols.com
1
BOX CONTENTS
97 mm (3.82")
57 mm (2.74")
85 mm (3.35")
centres
3
Ø 15 mm (0.59")
foam washer
4 pilot holes
HT/D/2%
HT/D/2%
Installation Instructions
(TG200988)
Prepare Duct
Either: screw directly to duct
2 pilot holes
42.5 mm
42.5 mm
(1.67")
(1.67")
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the HT/D and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TREND HT/D

  • Page 1 (1.67”) Or: using optional mounting fl ange (ACC/FLANGE/12MM/5) 45 mm (1.77”) Ø circle foam washer 4 holes Ø 23 mm 4 pilot holes Ø 4 mm (0.16”) (0.91”) HT/D/2% Duct Humidity and Temperature Sensor Installation Instructions TG200988 Issue 5, 19-Feb-2021...
  • Page 2 Refi t Connector & Lid Caution: IP67 (NEMA6) rating is only achieved if the sensor is correctly installed and has both the lid and cable gland (or conduit connection) securely tightened. HT/D/2% Duct Humidity and Temperature Sensor Installation Instructions TG200988 Issue 5, 19-Feb-2021 .
  • Page 3 Clean fi lter (see section 4) Complete failure No power supply Check power supply and cable Humidity reading too high Condensation on sensor probe Remove fi lter and carefully dry the probe HT/D/2% Duct Humidity and Temperature Sensor Installation Instructions TG200988 Issue 5, 19-Feb-2021...
  • Page 4 Building Division of Honeywell Products and Solutions SARL, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.