It removes the need to wire each unit's AC input and output terminals. • Reduce equipment costs: Combining MultiPlus-II 8, 10, or 15kVA units with an external transfer switch lifts their "no parallel" restriction. Otherwise, the more expensive Quattro 8, 10, or 15kVA units would have been required.
Page 4
MultiPlus-II External Transfer Switch application Country Certificate* Ziehl relay UFR1001E required Austria TOR Type A ver 1.3 Belgium C10/11 ed 2.3 Denmark TR3.3.1 Rev 5 Europe EN50549-1:2019 Germany VDE-AR-N 4105:2018:11 Northern Ireland G99 Issue 1 Amd 1 (Dec 2023) Poland PTPiREE Rev 1.2:2021...
MultiPlus-II External Transfer Switch application 2. Functionality The external transfer switch replaces the internal AC transfer switch of each individual MultiPlus-II unit in the system. The system operates almost identically to one using the internal AC transfer switches. Features such as UPS functionality, AC input current limit, PowerControl, and PowerAssist remain active.
Before the system's initial power-up, double-check all wiring. Wiring mistakes can damage the MultiPlus-II units. 3.1. AC voltage measurement The MultiPlus-II's AC input functions as a measuring input. Since the internal back-feed relay is not used, the wires can be relatively thin, 1.5mm² wires are sufficient. Connection procedure: Connect the AC-IN terminals of MultiPlus-II to the AC supply.
For more information, see: https://www.victronenergy.com/meters-and-sensors/current-transformer-for-multiplus-ii. 3.3. Ground relay The ground relay drive signal is supplied by the MultiPlus-II “Ext GND Relay” terminals of the L1 phase master unit via a help relay. Since the “Ext GND Relay” output signal is limited to 24V / 200mA, a help relay with a 24V coil must be used to switch the actual ground relay.
MultiPlus-II External Transfer Switch application 3.5. Ziehl relay A Ziehl UFR1001E relay might be required for certain grid-connected countries or applications. The Grid code certification country list [1] section lists the requirements per country. Grid or generator K1, K2 transfer switch position feedback signals...
Repeat the process for all MultiPlus-II units. CAUTION: Never use MultiPlus-II unit with standard firmware in an "External transfer switch" application. This will cause the system to connect to the AC input and likely trigger the current protection on that measurement- only circuit.
MultiPlus-II External Transfer Switch application 4.3. MultiPlus-II configuration Use "VEConfigure" to configure each MultiPlus-II unit. Configuration procedure: Ensure the “S99” firmware version is installed Navigate to the “General” tab. For all phase master units, set the "Current sensor rating" to 100 or 400A, matching the current sensor's current rating.
MultiPlus-II External Transfer Switch application 4.4. Venus OS version If a GX device is used, it should be updated to Venus OS version 3.33 or later. 4.5. GX device generator start/stop feature. If the system includes a generator, we recommend using the generator start/stop feature in our GX devices, including the cool-down function, to ensure a seamless transfer.
• This indicates a configuration fault. Verify that the current transformer (CT) rating matches the system capacity. For example, in a three-phase 12 x 48/15000 MultiPlus-II setup, this fault occurs if the configured CT rating is set to 100A. For such a system, a 400A CT rating is required.