Copeland HLR13 Series Application Manuallines

Scroll digital receiver
Table of Contents

Advertisement

Quick Links

Copeland scroll digital receiver
HLR units
HLR13
*
HLR31
*
APPLICATION GUIDELINES

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HLR13 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Copeland HLR13 Series

  • Page 1 APPLICATION GUIDELINES Copeland scroll digital receiver HLR units HLR13 HLR31...
  • Page 2: Table Of Contents

    Icon explanation....................1 Safety statements ....................1 General instructions ..................... 2 Product description....................3 General information about Copeland scroll digital receiver HLR units ....3 Product range ...................... 3 Nomenclature ...................... 3 Product nameplate....................3 Dimensions in mm ....................3 Application range ....................
  • Page 3 3.2.2 Access door to electrical cabinet..............12 Refrigeration piping connections ................ 13 3.3.1 Brazing recommendations ................13 3.3.2 Brazing procedure ..................13 Electrical connections ..................14 3.4.1 Power supply connections ................14 3.4.2 Pre-wired electrical components ..............14 3.4.3 Discharge temperature protection............... 15 3.4.4 Electrical protection standard (protection class) ..........
  • Page 4: About These Guidelines

    About these guidelines The purpose of these application guidelines is to provide guidance in the application of Copeland scroll digital receiver HLR units (or HLR units). They are intended to answer the questions raised while designing, assembling and operating a system with these products.
  • Page 5: General Instructions

    1.3 General instructions WARNING Pressurized system! Serious personal injuries and/or system breakdown! Accidental system start before complete set-up must be avoided. Never install a system in the field and leave it unattended when it has no charge, when it has a holding charge, or with the service valves closed, without locking out the system electrically.
  • Page 6: Product Description

    Product description 2.1 General information about Copeland scroll digital receiver HLR units Copeland has developed the Copeland scroll digital receiver HLR units to meet the refrigeration market demands for compact solutions at highest efficiency levels. These units allow continuous capacity modulation from 10 to 100 % and can be combined with various condenser concepts.
  • Page 7: Figure 2: Hlr13-Zbd58Kce & Hlr13-Zbd76Kce

    Figure 2: HLR13-ZBD58KCE & HLR13-ZBD76KCE Figure 3: HLR31-ZBDT60KCE, HLR31-ZBDT90KCE & HLR31-ZBDT114KCE Figure 4: HLR31-ZBDT152K5E AGL_Unit_HLR_EN_Rev01...
  • Page 8: Application Range

    It is essential that the glide of refrigerant blends be carefully considered when adjusting pressure and superheat controls. Oil recharge values can be taken from Copeland scroll compressors brochures or Copeland Select software available at www.copeland.com/en-gb. Units HLR13* & HLR31*...
  • Page 9: Main Components Description

    Single-compressor units are equipped with: ▪ dual pressure switch with automatic reset Copeland Flow Controls PS2-W7A; ▪ electronic unit controller Copeland EC2-552 with HP and LP pressure transmitters. Tandem-compressor units are equipped with: ▪ single low-pressure switch with automatic reset Copeland Flow Controls PS1-W3A;...
  • Page 10: Discharge Line Thermistor

    Cut-in point: 22 bar PT5 Pressure transmitter from Copeland Flow Controls HLR units are equipped with HP and LP pressure transmitters, connected to the Copeland EC2-552 electronic unit controller – see section 2.8 "Electronic controller – Copeland EC2-552". A PT5-30M pressure transmitter from Copeland Flow Controls is used at the high-pressure part of the system.
  • Page 11: Discharge Line Thermostat

    2.7.9 Oil separator OSH from Copeland Flow Controls The OSH-407 oil separator from Copeland Flow Controls is fitted as standard on the two smaller tandem- compressor HLR units. The two larger tandem-compressor HLR units are equipped with the OSH-411 oil separator.
  • Page 12: Select Parameter Configuration

    Compressor 2: On Fan: On Compressor 1: On Figure 9: Electronic controller Copeland EC2-552 The controller has been pre-programmed with a number of parameter values that are most likely correct. Individual installation requirements however may make it necessary to alter parameter settings.
  • Page 13: Main Parameters On Ec2-552

    100 % if the system requires less than the maximum capacity. In that case F3 > F2. NOTE: For more information about the EC2-552 controller, please contact the Application Engineering department at Copeland. AGL_Unit_HLR_EN_Rev01...
  • Page 14: Installation

    High pressure! Injury to skin and eyes possible! Be careful when opening connections on a pressurized item. Copeland scroll digital receiver HLR units are delivered with a holding charge of neutral gas. Since these units are used with remote condensers, they should be located in such a place to prevent any dirt, plastic bag, leaves or papers from covering the condenser and its fins.
  • Page 15: Connection Access

    3.2 Connection access 3.2.1 Access to refrigeration components Suction line Discharge line Liquid line Figure 11: HLR 13-ZBD30KCE, HLR13-ZBD45KCE, HLR 13-ZBD58KCE & HLR13-ZBD76KCE Suction line Discharge line Liquid line Suction line Figure 12: HLR31-ZBDT60KCE, HLR31-ZBDT90KCE, HLR31-ZBDT114KCE & HLR31-ZBDT152K5E 3.2.2 Access door to electrical cabinet Use the supplied key to open and close the electrical cabinet door.
  • Page 16: Refrigeration Piping Connections

    3.3 Refrigeration piping connections CAUTION Blockage! Compressor breakdown! Maintain a flow of oxygen-free nitrogen through the system at very low pressure during brazing. Nitrogen displaces the air and prevents the formation of copper oxides in the system. If allowed to form, the copper oxide material can later be swept through the system and block screens such as those protecting capillary tubes, thermal expansion valves, and accumulator oil return holes.
  • Page 17: Electrical Connections

    3.4 Electrical connections 3.4.1 Power supply connections The electrical connection of the scroll digital receiver HLR unit to the power supply must be made by qualified technicians in compliance with valid electrical standards, for instance DIN EN 60204-1. The electrical diagrams are located inside the electrical connection cabinet. Auxiliary relay K10 Contactor K1 Transformer T1...
  • Page 18: Discharge Temperature Protection

    ▪ Compressors ZB(D)30KCE, ZB(D)45KCE & ZBD58KCE: IP21 according to IEC 34. ▪ Compressors ZB(D)57KCE & ZB(D)76K5E: IP54 according to IEC 34. ▪ HP/LP and LP safety pressure switches (Copeland FlowControls PS2 and PS1): IP44 according to EN 60529/IEC 529. ▪ HP safety pressure switch PS3 with cable assy: IP65 according to EN 175301-803/IEC 529.
  • Page 19: Start-Up & Operation

    NOTE: The oil level should be approximately halfway up the sight glass. Copeland recommends charging the unit with one of the following oil types: ▪ Emkarate RL 32 3MAF ▪ Mobil EAL Artic 22 CC Charging is done through the Schraeder valve located on the suction Rotalock valve.
  • Page 20: Maximum Compressor Cycle

    ▪ Check that the electrical panel is closed. ▪ After starting-up and operation conditions are stabilised, Copeland recommends to check the oil level in compressor(s) and if needed to add oil to ensure a sufficient oil level (halfway up the sight glass).
  • Page 21: Maintenance & Repair

    − EN 378-2: Refrigerating systems and heat pumps - Safety and environmental requirements - Part 2: Design, construction, testing, marking and documentation. ▪ The Copeland HLR units and their associated spare parts and accessories comply with the Directive RoHS 2011/65/EU, (EU) 2015/863 on the Restriction of the use of certain Hazardous Substances in electrical and electronic equipment (recast).
  • Page 22: Appendix 1: List Of Tables And Figures

    Figure 15: Electrical connection cabinet ....................14 DISCLAIMER: The Copeland logo is a trademark and service mark of Copeland LP or one of its affiliates. Copeland Europe GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifications, assumptions, designs and technical data contained in this document are subject to modification by us without prior notice.
  • Page 23 Tel. +49 (0) 2408 929 0 - Fax: +49 (0) 2408 929 570 – Internet: copeland.com/en-gb The Copeland logo is a trademark and service mark of Copeland LP or one of its affliates. Copeland Europe GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors.

Table of Contents