Foreword Dealers purchase Telguard alarm communicators for the quality, features and total value they represent. The Telguard TG-7FM meets UL standards for Commercial Fire, Commercial Burglary, and combination fire/burglary systems. The TG-7FM has a cellular pathway for signal transmission, suitable as the sole communication path when applicable features are enabled.
NOTE: RMA number must be on the outside of box or product will not be accepted. Future Testing and Limitations on Use The Telguard TG-7FM is part of an advanced design alarm communication system. It does not offer guaranteed protection against burglary and fire. Any alarm communication system is subject to compromise or failure.
THE EXCLUSIVE WARRANTY, IN LIEU OF ALL OTHER WARRANTIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE, DELIVERY, INFRINGEMENT OR FITNESS FOR A PARTICULAR PURPOSE AND NO OTHER WARRANTIES WILL BE HONORED, WHETHER EXPRESSED OR IMPLIED. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Decide on a STC Trip Output Strategy Optional Trip Input Swinger Function Step 2: Physically Install the TG-7FM in Desired Location Identify Location for Placing the TG-7FM Device and Mount Connect Antenna Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Page 6
Appendix 5 Compliance with UL Standards Appendix 6 Detailed Specifications Dialer to Interface Electronics Power Field Wiring Electrical Ratings System Faults Impedance Digital Cellular Radio and Other Specifications Appendix 7 Accessories Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Can be used as either a Primary or Secondary Path device when an alternate communications path is connected to another alarm panel DACT interface. In such cases, the panel determines the alarm reporting path. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Tamper Protection. Tamper wires and all other wires connecting the communicator to the panel shall be in rigid or flexible metal conduit. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Features This section summarizes the key features of the Telguard TG-7FM. Operating Mode The TG-7FM communicator is a sole path cellular Data/SMS transmission device that is installed at the protected premises to provide alarm transmission for fire and/or burglary alarm systems over the applicable cellular network.
Catastrophic Failure (CF) is any condition that causes the communicator to stop functioning at all levels. The most common CF is a power failure event. The STC1 and STC2 trip outputs are activated and the visible indication is loss of all LED activity. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Communicator not activated at TCC: communicator requires activation for use • Catastrophic Failure (CF): all power is lost • Transmit Disable command received from TCC: used when a runaway dialer situation is detected or by Customer Service Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
• Release the button. After the factory reset concludes, the LEDs will again operate the way they did prior to installation. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
16 to 22 gauge in size. • A standard telephone or lineman's butt-set is recommended for verifying communication between the panel and the communicator. • An unbent paperclip to activate side buttons. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Decide on a STC Trip Output Strategy The communicator provides the host alarm panel with two supervisory trip outputs for reporting a Telguard system trouble code to the central station. The supervisory trip outputs are Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
If moving the communicator to a different location is not practical, you may need to purchase an extension cable to remote the antenna in order to Telguard TG-7FM Installation & Operating Guide 56055101...
10 ft 20 ga 20 ft 18 ga 60 ft (20 ft max. for fire systems) UL Compliance Note: All wiring shall be in accordance with NFPA 72 and NFPA 70. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
(DACT) into the RJ-45 jack of the communicator. UL Compliance Note: For Commercial Fire installations, all connections from the alarm panel and the Telguard communicator must be mechanically protected and no greater than 20 feet in distance. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
If both a local signaling device and an alarm panel are required, then external relays are needed to provide additional uncommitted contacts. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Burglary Applications. Its use is optional in Fire-only applications. To use the tamper switch, wire the Tamper connector to a zone on the panel that is designated for Tamper Protection. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 TG-7FM SEE NOTE ABOVE Tamper Switch TRIP INPUT STC2 NOT PERMITTED IN UL FIRE SYSTEMS Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
INCOMING TELCO ANTENNA RJ-31X FACP LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 TG-7FM TRIP INPUT STC2 NOT PERMITTED IN UL FIRE SYSTEMS Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
ANTENNA ALARM PANEL LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 TG-7FM Tamper Switch TRIP INPUT STC2 NOT PERMITTED IN UL FIRE SYSTEMS Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
UL 864. Contact ID and SIA2 are the only formats identified as complying beginning with UL 864 10 Edition. If in doubt, check with your AHJ. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
TG-7FM can still receive (Initiated by TCC) (Status data) radio signals from the TCC. The STC LED will flash all applicable indications in sequence and then repeat the sequence. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Trip Input Trip Input not activated or is restored LED 8 DC power connected to unit Power The STC LED will flash all applicable indications in sequence and then repeat the sequence. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
LEDs 5-3 = on, LED 2 = slow flash -60 LEDs 5-2 = on NOTE: When LED 1 is on in RSSI mode, it indicates more than one cellular tower within range. Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
TG-7FM Signal Strength Installation instructions for the Telguard TG-7FM indicate that a signal strength of -90dBm (LEDs 4 and 5 on, with LED 3 flashing) is sufficient. , an additional level of signal integrity will minimize false alarm supervision failures caused by interference and atmospheric fading.
# All conductors of a fire alarm system shall be installed in metal raceway of the totally enclosed type or incorporated in a cable having a metal armor or sheath; these metal elements must be grounded Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...
Digital Cellular Radio and Other Specifications The Telguard TG-7FM radio provides data connectivity on LTE-M networks. The TG-7FM transceiver is FCC compliant, meeting all requirements of Part 15 and 27 testing. It is also certified as compliant to PTCRB requirements.
50 feet of low loss high performance antenna cable and mounting bracket ACD-100 100 feet of low loss high performance antenna cable and mounting bracket HGDL-0 High Gain Directional Antenna EXDL-0 External Omni-Directional Antenna Telguard TG-7FM Installation & Operating Guide 56055101 Rev A.1...