Information in this User’s Manual is subject to change without notice and does not represent a commitment on the part of PLANET. PLANET assumes no responsibility for any inaccuracies that may be contained in this User’s Manual. PLANET makes no commitment to update or keep current the information in this User’s Manual, and reserves the right to make improvements and/or changes to this User’s Manual at...
WEEE as unsorted municipal waste and have to collect such WEEE separately. Trademarks The PLANET logo is a trademark of PLANET Technology. This documentation may refer to numerous hardware and software products by their trade names. In most, if not all cases, these designations are claimed as trademarks or registered trademarks by their respective companies.
1. Product Introduction Thank you for purchasing PLANET LoRaWAN Sensor, LS series. The descriptions of these models are as follows: EU868 LS100-WL-EU868 IP65 LoRaWAN Water Leak Sensor (EU868 Sub 1G) IP30 LoRaWAN Indoor Occupancy Sensor (Occupancy/Light/ LS100-PIR-EU868 Temperature -20~55 degrees C, EU868 Sub 1G)
Page 6
US915 LS100-WL-US915 IP65 LoRaWAN Water Leak Sensor (US915 Sub 1G) IP30 LoRaWAN Indoor Occupancy Sensor (Occupancy/Light/ LS100-PIR-US915 Temperature -20~55 degrees C, US915 Sub 1G) LS100-DW-US915 IP30 LoRaWAN Door and Window Sensor (US915 Sub 1G) IP20 LoRaWAN CO Detector (High-Temperature Alarm, US915 Sub LS100-CO-US915 IP20 LoRaWAN Smoke Detector (High-Temperature Alarm, US915 LS100-SMK-US915...
If any of the above items are missing, please contact your dealer imme- diately. 1.2 Overview Build a Smart IoT Environment with Fabulous LoRaWAN Sensors PLANET LS100 and LS 200 LoRaWAN sensors are intended for environmental monitoring and data collection. Data such as temperature, humidity, illumination,...
Page 8
and ingress/egress all impact the status of a facility or a device, whether it is a motor, a refrigeration unit, or even the networking gear itself. Sensors in the LS series mostly have IP65 and IP67 ratings, allowing them to be deployed in outdoor and industrial indoor environments.
Page 9
Expanding Capabilities with PLANET Industrial LoRa Node Controllers The integration of PLANET LS100/LS200 Sensor series into the NMS-AIoT platform enhances the system’s capabilities by enabling seamless connectivity via LoRa, HaLow, and wireless, or wired options. This allows the LS100/LS200 Sensor series to...
Environmental Sensors: z Temperature and Humidity LS200-TH IP65 LoRaWAN Indoor Temperature and Humidity Sensor z Water Leakage LS100-WL IP65 LoRaWAN Water Leak Sensor z Light Detection LS200-LG IP65 LoRaWAN Light Level Sensor z Gas LS200-VOC IP65 LoRaWAN TVOC Sensor LS200-PM25 IP30 LoRaWAN PM2.5 Sensor LS100-CO IP20 LoRaWAN CO Detector z Smoke...
1.3 Features Key Features LS100-WL z Water Leak Sensor z IP65 rating z LoRaWAN™ Class A compatible LS100-PIR z Indoor Occupancy Sensor (Occupancy/Light/Temperature) z IP30 rating z LoRaWAN™ Class A compatible LS100-DW z Door and Window contact Sensor z IP30 rating z LoRaWAN™...
Page 12
LS200-TC z Machine Temperature Sensor with Thermocouple (-40 °C to 125 °C) z IP65 rating z LoRaWAN™ Class A compatible LS200-RF z Refrigerator Temperature and Humidity Sensor (-40 °C to 55 °C) z IP65 rating z LoRaWAN™ Class A compatible ...
Glass Break Sensor (Detection Mode: Piezoelectric buzzer) z LoRaWAN™ Class A compatible LS250-PLUG z Power Plug with Power Meter z Maximum 16 A current measurement z IP20 rating z LoRaWAN™ Class C compatible 1.4 Product Specifications LS100 series (WL/PIR/DW) Product LS100-WL LS100-PIR LS100-DW Wireless Transmission Technology LoRaWAN...
Page 14
5 years 3 years (25 °C, 15-minute reports, TxPower=20 dBm, (25 °C, 15-minute Battery Life Time SF10) reports, TxPower=20 dBm, SF10) Standby Current 22 μA 110 μA 12 μA Wake-up Current 7.12 mA 9.78 mA 120 mA/11 mA (Typical value) Low Battery 3.2 V 3.2 V 2.4 V Threshold...
Page 15
LS100 series (CO/SMK) Product LS100-CO LS100-SMK Wireless Transmission Technology LoRaWAN EU868: 863 to 870 MHz Frequency US915: 902 to 928 MHz US915: 20 dBm EU868: 16 dBm TX Power AS923: 16 dBm (optional) KR920: 14 dBm (optional) AU915: 20 dBm (optional)
Page 17
Temperature Sensor Temperature Sensor Temperature Sensor - Measurement Range: - Measurement Range: - Measurement Range: -20 °C to 55 °C -40° to 125 °C -40° to 125 °C - Measurement Sensor Accuracy: ±1 °C Humidity Sensor Measurement Info - Measurement Range: 0 % to 100 % RH - Measurement Accuracy: ±4 % RH...
Page 18
Wake-up Current 7.11 mA 7.5 mA 127 mA (Typical value) Low Battery 3.2 V 3.2 V 3.2 V Threshold Physical Characteristics Dimensions 112 mm x 65 mm x 112 mm x 65 mm x 112 mm x 88.19 mm (L x W x H) 32 mm 32 mm x 32 mm...
Page 19
US915 20 dBm EU868 16 dBm TX Power AS923 16 dBm (optional) KR920 14 dBm (optional) AU915 20 dBm (optional) IN865 20 dBm (optional) -136 dBm (LoRa, Spreading Factor = 12, Bitrate = 293 bps) Rx Sensitivity -121 dBm (FSK, Frequency Deviation = 5 kHz, Bitrate = 1.2 kbps) Work Mode OTAA/ABP Class A Data Interfaces...
Page 20
Current TVOC Sensor PM2.5 Particle Concentration - Measurement Range: - Measurement Range: 1 A to 150 A 0 ppb to 60000 ppb Sensor - Measurement Temperature Sensor - Particle Mass Accuracy: < ±1 % - Measurement Range: Concentration - Current Resolution: -20 °C to 55 °C Effective Range: 1 mA...
Page 22
Tilt Sensor - Conversion Angle: 45° ± 5° - Contact Resistance: Less than 10 Ω - The Insulation Resistance: Greater than 100 MΩ - Operating Temperature: -40 °C to 85 °C - Installation Type: Suitable for PCB at vertical state Vibration Sensor - Model: Ball type omnidirectional signal trigger switch - Voltage: < 6 V - Current: 2 μA to 10 mA - Insulation Resistance: >...
2. Hardware Introduction 2.1 Physical Descriptions LS100-DW LED Indicator Function Button Appearance Water Leak Sensor LS100-DW Indicator External Antenna Appearance Function Button Magnet LS100-CO Indicator Appearance Test Button Function Button LS100-SMK Indicator Appearance Test Button Function Button...
Page 25
LS100-PIR LED Indicator Function Button Infrared Sensor Infrared Sensitivity Adjustment Kob Appearance Snap-fit Joint LS200-TH Indicator Function Button Appearance Built-in Temperature and Humidity LS200-PT PT1000 Needle Probe Appearance LED Indicator Function Button...
Page 26
LS200-TC LED Indicator Function Button Appearance Thermocouple Sensor LS200-RF Indicator Function Button Appearance Built-in Temperature and Humidity LS200-LG Light Sensor Indicator Appearance Function Button LS200-CM3 Indicator Function Button Appearance Clamp-on Current Transformer...
Page 27
LS200-CM LED Indicator Function Button Appearance Clamp-on Current Transformer LS200-PM25 Built-in Temperature and Humidity PM2.5 sensor Appearance LED Indicator Function Button Batteries Box DC In LS200-VOC Indicator Function Button Appearance...
Page 28
LS200-MF8 Indicator PIR Sensor Function Button Light Sensor Appearance Reed Switch Glass Break Sensor LS200-PLUG Network LED Switch LED Indicator Indicator Switch Button Appearance Factory Reset Button...
LED Definition: Color Function Indicating the network is successfully connected after Lights 1 time turning on LoRaWAN sensor. Indicating it is triggered to send a report after pressing the Flashes 1 time Function Button Once. LED Green Indicating the LoRaWAN sensor is not in the network after Flashes 3 times pressing the Function Button Once.
● Product uses two ER14505 batteries: Modules: LS100-PIR, LS100-WL, LS200-TH, LS200-PT, LS200-TC, LS200-RF, LS200-LG, and LS200-CM Unscrew the four screws on the device's cover to remove the front cover. Insert the battery and put back the device's cover and tighten the screws. 2.2.2 Magnetic Mounting or Wall Mounting ●...
● Wall mounting by the double-sided stickers Model: LS100-PIR 1. Clean the surface of the objects before sticking with the sticker. 2. Tear off the 3M300LSE side of the sticker, place it on the bottom of the product as shown in the picture, and press it. 3. Tear off the other side of the sticker and put the sticker to a clean surface of the wall and press the sticker firmly for around 20 seconds.
Page 32
● LS100-PIR: IP30 LoRaWAN Indoor Occupancy Sensor The correct installation of LS100-PIR is shown below. Please place it at a height of Don’t place it near air conditioners, 2 to 2.2 meters from the ground. refrigerators, and stoves. Sensor Sensor 2.2M Bonsai, glass, or curtain should not Avoid direct sunlight.
Page 33
● LS200-TC: IP65 LoRaWAN Machine Temperature Sensor When LS200-TC is compared with the last reported values, the temperature change is expected to exceed 10 °C (by default). It will report values at the Min. Time interval. If it does not exceed 10 °C (by default), it will report values at the Max.
Page 34
1. Before using, user must check whether the appearance is deformed; otherwise, the test accuracy will be affected. 2. The operating environment should be kept away from strong magnetic fields, so as not to affect the test accuracy. It is strictly forbidden to use in humid and corrosive gas environments. 3. Before installation, please confirm the current value of the load. If the current value of the load is higher than the measurement range, select a model with a higher measurement range.
Page 35
The buzzer sounds an alarm. A CO alarm report is immediately sent. z If the CO concentration remains above 110 ppm, the device sends an alarm report every 30 seconds. z Once the CO concentration drops below 110 ppm, the alarm stops, and a restoration report is sent.
● LS200-VOC: IP65 LoRaWAN TVOC Sensor LS200-VOC measurement range is 0 ppb to 60000ppb. Default Settings Max Time: 900 s Min Time: 900 s 1. The Min Time should not be less than 4 minutes. 2. The Max Time should be greater than or equal to the Min Time. Battery Change: 0.1 V (0x01) TVOC Change: 300 ppb (0x012C) Excellent...
● LS200-PM25: IP30 LoRaWAN PM2.5 Sensor Default setting: Max Time: 8400 s Min Time: 30 s (US915, AU915, KR920, AS923, IN865) 120 s (EU868) Report Type count = 1 1. Max Time and Min Time rules, configured by formula: Max Time ≥ Report Type count * Report Min Time+10 2.
Page 38
● LS200-MF8: IP30 LoRaWAN Multi-functional Sensor Default Setting: Max Time: 3600 s (0x0e10) Min Time: 3600 s (0x0e10) Battery Change: 0.1 V (0x01) Temperature Change: 1 °C (0.0064), Signed 2 Bytes, unit: 0.01 °C Humidity Change: 10 % (0x14), 1 Byte, unit: 0.5 % Illuminance Change: 100 lux (0x64), 1 Byte, unit: 1 lux Internal Shock Sensor Sensitivity: 0x05 Internal Vibration Sensor, Sensitivity Range: 0x00-0x0A...
Before accessing the LoRaWAN Sensor controllers, user has to install utility tool for operation. 3.1 Requirements PLANET Industrial LoRaWAN Gateway, e.g., LCG-300 series Workstations running Windows 7/8/10/11, macOS 10.12 or later, Linux Kernel 2.6.18 or later, or other modern operating system are compatible with TCP/IP protocols and installed with web browser.
LCG-300 series-US LCG-300 series-EU 3.2.2 LoRaWAN Setting Click LoRaWAN label and input the related data. Object Description LoRaWAN Server Mode The service of LoRaWAN Email The registered email of LoRaWAN server The unique identity of the base station, which the server Gateway ID can distinguish a different LoRaWAN base station Server Provider...
3.2.3 Setting Up of LoRa Connection via ABP Decryption a. Click Enable. b. Click Add ABP Key Button. Then input data which has to be the same as the settings of LoRa node/sensor. Object Description Device Address* The DevAddr of device Network Session Key* The NWKSKEY of device Application Session Key*...
When sensor connects to LoRa Gateway, the RSSI and SNR would be shown on the UI of gateway as seen below. 3.3 Connecting to PLANET NMS-AIoT Set up the NMS-AIoT Controller with an Ethernet connection for the first-time configuration shown in the topology below. Non-LoRa Devices...
Page 43
The secure login with SSL (HTTPS) prefix is required. After logging on, connect the NMS-AIoT Controller to the network to centrally control PLANET managed devices. 1. In NMS-AIOT, press the “Menu” icon . Then click “Devices Management” and “Devices List” to go to devices list page. 2. Press the “plus” icon...
Page 44
3. Add a new LoRaWAN Sensor on the NMS-AIoT Enter the relevant data for the LoRaWAN Sensor. After adding sensor(s), it will be shown in the device list in Web UI of NMS-AIoT.
Thank you for purchasing PLANET products. You can browse our online FAQ resource and User’s Manual on PLANET Web site first to check if it could solve your issue. If you need more support information, please contact PLANET switch support team.
Need help?
Do you have a question about the LS100 Series and is the answer not in the manual?