Product’s performance for thirty-six (36) months from the ship date for such Product. Must Provide Notice of Defect: If you have a Product that you believe is defective, you must notify H2scan in writing, within the warranty period of your claim regarding any such defect.
The GSAO-1 is powered with nominal 9 to 48 VDC, which is passed through to the GRIDSCAN 5000 Hydrogen Sensor System. Only two cables are required; one to connect the GSAO-1 Module to the GRIDSCAN 5000 Hydrogen Sensor with power and communications, and one from the customer supplying DC power and taking the analog signal out to the customer’s data...
The GSAO-1 Analog Output Module has a rugged waterproof and dustproof mechanical assembly design for various transformer applications. The enclosure is easily mounted using the four mounting holes and the included #10 18-8 stainless steel screws. The GSAO-1 is rated IP68 and can be used in most environments.
2.5 Electrical Features A cable is required for connecting the GSAO-1 Analog Output Module to the GRIDSCAN 5000 Hydrogen Sensor. The required cable has a single 4-pin M12 connector for connection at the GRIDSCAN 5000 Hydrogen sensor for power and communications.
GSAO-1 module. (see wiring instructions section 8.3.2) Additionally, the customer must supply DC power to the GSAO-1 module and take the analog signal out to their data system. This cable should be a four conductor cable with wire size up to 4 mm (12 AWG) for the following: •...
GSAO-1 Operating Manual Table 2: GSAO-1 Operating Conditions Value Parameter Minimum Nominal Maximum Units Environment – Ambient Operating Temperature °C Storage Temperature °C Ingress Protection IP68 (IEC 60529) with provided cable gland fittings Humidity 0 to 100% RH, condensing Altitude...
4.1 Front View Features: Strengthened Glass Window Latch Side Hinge Side Power LED Indicator Service LED Indicator Cable Gland Fittings Figure 2: GSAO-1 Front View Features 4.2 Open View Features: Cable Shield Gasket Seal Configuration Switches Grounding Mounting Holes x4...
6 Enclosure Access When looking at the front panel of the GSAO-1 unit, the latch is located on the left side of the enclosure. From the front, the latch will release and will swing from the front to the left. This exposes the cover screws that compress the cover to the base.
GSAO-1 unit and may compromise the IP rating of the system. 7 Mounting The GSAO-1 can be easily mounted to panels and plates. Included with every unit in the Quick- Start Guide is a 1:1 template for easily locating the appropriate mounting hole locations. The included stainless-steel machine screws require that pilot holes be drilled using a 3mm (1/8”) drill...
5 mm to 12 mm (0.20” to 0.47”) Outside Diameter jacketed cables. If it is desired to utilize conduit to route cables to and from the GSAO-1, the cable gland fittings can be replaced by standard ½” conduit gland fittings without modification to the enclosure. The IP rating of the GSAO-1 is dependent upon the rating and construction of the conduit gland fittings.
The cable used to connect to the GRIDSCAN 5000 Hydrogen sensor is an orderable option available in various lengths. If the cable is not ordered from H2scan, it should be rated for the environmental conditions it will be used in. A suitably rated cable assembly is required for most field applications.
Do NOT unplug or plug wiring connectors when the system is energized. 8.3.1 Earth Grounding the GSAO-1 Module An earth ground is required to be connected to the case of the GSAO-1 Analog Output Module. It should be added in conjunction with the mounting hardware. (See Section 7) With the grounding clip securely installed with the GSAO-1 mounting, insert the bare grounding wire into the clip and tighten the set screw.
GSAO-1 Operating Manual 8.3.2 GRIDSCAN 5000 Hydrogen Sensor Wiring Connections After connecting the cable to the GRIDSCAN 5000 sensor, route the cable to the GSAO-1. Secure cable as necessary. Trim the cable to length so that there will be approximately 160 mm (6.5 inches) inside of the GSAO-1 module when assembled.
Two conductors should be used for DC power, and two for current loop analog output. After routing the cable to the GSAO-1 installation, trim any excess cable so that approximately 210 mm (8.5 inches) of cable will be inside the GSAO-1 module.
Page 17
GSAO-1 Operating Manual After all wires are stripped, insert the cable through the left gland fitting on the GSAO-1 enclosure so that 10 mm (½ inch) of the cable jacket is visible inside the enclosure above the gland fitting. Securely tighten the gland fitting to the cable using an adjustable wrench. 0.28 N*m (2.5 in*lbf)
GSAO-1 Operating Manual Figure 17: GSAO-1 Cable Wire Dressing 8.4 Power Supply It is recommended that the GSAO-1 be powered by an industrial grade fixed output power supply that meets the following specifications: • DC voltage output • Output Voltage: 9, 12, 15, 24, 30, 36 or 48 VDC nominal •...
* On initial power on, the flashing rate for the Blue Green LEDs is once per second. 9.3 Analog Output The GSAO-1 analog output is expressed as a 4-20 mA signal. The following table indicates functionality: Table 5: GSAO-1 Analog Output Indications Current Condition...
Damage to the switches can affect the operation of the GSAO-1 module and may void the warrany. The GSAO-1 Analog Output Module has a configuration mode where the oil type can be changed, the scaling of the analog output can be changed, and the analog output can be tested.
Scaling Tables Figure 18: Configuration Overview If the GSAO-1 unit is not in configuration mode, the LEDs for Gas / Oil, analog output scaling, and oil type indicate the configuration that is stored within the unit. The switch positions may not indicate the current settings.
GSAO-1 Operating Manual However, if the serial number is different, the GSAO-1 will enter a service condition. This is indicated by the Blue LED blinking 3 times every 12 seconds. It is assumed that if the sensor is changed or the GSAO-1 is relocated to another installation site, that the configuration would need to be changed.
(7131). The default mode is for Mineral oil. The LED below the switches indicates which oil type is configured. When the GSAO-1 is set to configuration mode, the oil type can be changed by moving the switch above the desired oil type from the bottom to top position using the provided golf tee. The switch for the previously selected oil type should be then moved from the top to the bottom position.
The GSAO-1 Analog Output Module has the ability to report an analog output signal up to 24 mA. However, signals between 20 mA and 24 mA exceed the selected 4-20 mA scale and the GSAO-1 should be reconfigured for the appropriate scale.
LEDs, through “OIL | GAS”, and through the oil type LEDs ending with “MINERAL” being the last to illuminate. During the delay before the LED sequencing, the GSAO-1 configuration is stored in non-volatile memory and 90000180 Rev 2, 2/27/2025...
Page 27
If the GSAO-1 configuration mode is disabled by turning the “CFG” switch OFF and there are NO errors with oil type, the new configuration is stored in the GSAO-1 and is implemented in the Hydrogen sensor. The new configuration is then indicated by the oil type LED.
GSAO-1 Operating Manual 11 Re-Sealing the GSAO-1 After the GSAO-1 unit has been installed, wired, and configured, the checklist below should be followed to ensure that the module will seal properly and operate without issue. Make sure that no LEDs are flashing. Flashing indicates that there is an issue that should be resolved before leaving the installation site.
GSAO-1 Operating Manual 12 Troubleshooting The following is a guide is to be used to help resolve some of the common issues. Table 7: GSAO-1 Troubleshooting Guide Condition Possible Cause Remedy The sensor has not operated long enough to get an...
GSAO-1 Operating Manual 13 Unique LED Patterns The following is a guide is to be used to help resolve some of the common problems. Table 8: GSAO-1 Unique LED Patterns Guide Condition Possible Cause Remedy Power cycle GSAO-1 and sensor. If...
Page 31
GSAO-1 Operating Manual If you have any questions, please contact us at the address below: H2scan Corporation Headquarters: 27215 Turnberry Lane, Unit A Valencia, CA 91355 USA E-mail: hello@h2scan.com Website: www.h2scan.com 90000180 Rev 2, 2/27/2025 Page 31 of 31...
Page 32
GSAO-1 Operating Manual This Page Intentionally Left Blank 90000180 Rev 2, 2/27/2025 Page 32 of 31...
For Cutting Wires to Length and Trimming Cable Ties Marker or Pencil - To Mark Hole Locations and Wire Cut Lengths 1:1 Plot for Mounting the GSAO-1 Mounting GSAO-1 Using 4x #10 Stainless Steel Screws and star washers (Included) DO NOT OVER TIGHTEN 100mm 3.94 (3.94")