INSTALLATION AND OPERATING MANUAL I n s ta l l a t i o n te c h n i c i a n SYSTEM V 3 . 1 4 - 1 Controller KSM System ADAPT, VERSI, WPLV, ETERA, ADAPT...
Page 2
Installation and operating manual_BMS_17-20-28-4023-04 This work is protected by copyright. Any use of this document outside of the Copyright and Related Rights Act and without the express consent of KRONOTERM d.o.o. (hereinafter: KRONOTERM) is illegal and punishable by fine. Despite taking extensive care to ensure the accuracy of all figures and descriptions, KRONOTERM d.o.o.
IMPORTANT INFORMATION ......4 Symbols ................4 Introduction ..............4 Limitation of liability ..........4 Conditions for changing parameters ..4 CONNECTING THE BMS TO THE KSM CONTROLLER ............... 5 MODBUS TABLE ............6 DESCRIPTONS OF VARIABLES ....... 10 Status ................10 4.2 Domestic hot water ..........
CONDITIONS FOR CHANGING PARAMETERS The instructions describe descriptions of the variables At least one of the following requirements must be and the connection of the system to the KSM met before changing MA parameters: controller. • The device user or system designer requires a SYMBOLS change in user MA parameters.
Figure 1: Terminal for connecting the BMS system to the regulator KSM The device is connected via RS 485 communication. Connect to the TEX terminals on the KSM controller. Picture 1: Connection of the BMS system to the controller KSM via the TEX terminal...
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX 3 MODBUS TABLE Conversion and units Description 2034 x 0,1°C Current desired buffer tank * Modbus address (depending of BMS the address may /system temperature be offset by -1)
Page 7
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX Conversion Conversion and units Description and units Description 2066 Loop 3 thermostat status 2098 hours Operating hours heat source 2067 x 0,1°C Loop 3 ECO mode offset 2099...
Page 8
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX Conversion Conversion and units Description and units Description 2186 Thermostat failure 2318 Compressor status [b0 = compressor 1, b1 = 2187 x 0,1°C Desired room 1 temperature compressor 2]...
Page 9
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX Conversion and units Description 2360 Cascade status [b0 cascade 1, b1 cascade 2, b2 cascade 3, b3 cascade 4] 2361 x 1 W Electrical energy heating mode + DHW (high)
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX 4 DESCRIPTONS OF VARIABLES 2002-b0: Activation of additional source 2002-b1: Additional source 2 is active The variables below are described in more detail. The 2002-b2: Antifreeze program is active...
Page 11
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX ACTIVATION OF HOLIDAY MODE (MA_2022, RW) Activation of holiday mode. For activation you need to insert number of days on MA_2139: SYSTEM ACTIVATION (MA_2012, RW) Use this parameter to turn the system on / off (HP and...
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX HEATING SYSTEM PRESSURE (MA_2326, R) DOMESTIC HOT WATER Measured heating system pressure. DESIRED DOMESTIC HOT WATER TEMPERATURE SCREED DRYING (MA_2307, RW) (MA_2023, RW) Activation/deactivation of screed drying program.
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX THERMAL DISINFECTION START TIME (MA_2304, BUFFER TANK BUFFER TANK HEATING CURVE AT -15 °C/+20 °C Setting the start time for thermal disinfection. Insert (MA_2308, RW) the minute of day (value 240 = 4:00).
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX LOOP 2 LOOP 2 COM MODE OFFSET (MA_2058, RW) Offset in COM mode. LOOP 2 HEATING CURVE AT -15 °C/+20 °C (MA_2310, LOOP 2 ADAPTIVE CURVE (MA_2321, RW) Setting of heating curve at outdoor temperature -15 °C...
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX LOOP 3 LOOP 3 COM MODE OFFSET (MA_2068, RW) Offset in COM mode. LOOP 3 HEATING CURVE AT -15 °C/+20 °C (MA_2311, LOOP 3 ADAPTIVE CURVE (MA_2322, RW) Setting of heating curve at outdoor temperature -15 °C...
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX LOOP 4 LOOP 4 COM MODE OFFSET (MA_2078, RW) Offset in COM mode. LOOP 4 HEATING CURVE AT 15 °C/+20 °C (MA_2312, LOOP 4 ADAPTIVE CURVE (MA_2323, RW) Setting of heating curve at outdoor temperature -15 °C...
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX 4.8 POOL ALTERNATIVE SOURCE DESIRED POOL TEMPERATURE (MA_2079, RW) ALTERNATIVE SOURCE CIRCULATION PUMP STATUS Setting of desired pool temperature. (MA_2088, R) CURRENT DESIRED POOL TEMPERATURE (MA_2080, Display current desired pool temperature.
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX 4.12 ENERGY Description 2129 Current power consumption 2329 Current heating/cooling capacity 2349 Pumped ground water (high) 2350 Pumped ground water (low) 2361 Electrical energy - heating + DHW (high)*...
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX 4.13 ERRORS ERROR ACTIVE (MA_2113, RW) no error, error is active, To confirm/delete error send value 0. If the error can be deleted manually the value remains 0, otherwise the error remain active.
Page 23
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX ERROR (MA_2118, R) Label Bits Value Description 0000 0000 0000 0001 DC Peak (IPM Fault) 0000 0000 0000 0010 Max CT 0000 0000 0000 0100 DC Link Voltage is low or high...
Page 24
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX WARNING (MA_2120, R) Label Bits Value Description 0000 0000 0000 0001 DC Peak (IPM Fault) 0000 0000 0000 0010 Max CT 0000 0000 0000 0100 DC Link Voltage is low or high...
Page 26
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX ERROR (MA_2127, R) Oznaka Biti Vrednost Opis 0000 0000 0000 0001 Pressure. sensor fault - heating source (T31) 0000 0000 0000 0010 No flow - heat source 0000 0000 0000 0100...
Page 27
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX WARNING (MA_2330, R) Label Bits Value Description 0000 0000 0000 0001 Low pressure 0000 0000 0000 0010 Low superheat 0000 0000 0000 0100 High superheat 0000 0000 0000 1000...
Page 28
KRONOTERM Installation and operating manual System ADAPT, VERSI, WPLV, ETERA, ADAPT MAX ERROR (MA_2332, R) Label Bits Value Description 0000 0000 0000 0001 Main valve (EEV) 0000 0000 0000 0010 Valve 2 (EEV 2) 0000 0000 0000 0100 Stator heater feedback 0000 0000 0000 1000 Pressure.