Automist AP09 & AP12 DIOM version 1.1
DESIGNED BY PLUMIS
Design, Installation, Operation and Maintenance (DIOM) Manual
Automist AP09 & AP12 Version 1.1
Plumis Inc Copyright © 2024. All Rights Reserved
nd
Release date 22
October 2024
nd
Release date 22
October 2024
Page 0 of 77

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Automist AP09 and is the answer not in the manual?

Questions and answers

Summary of Contents for Plumis Automist AP09

  • Page 1 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 DESIGNED BY PLUMIS Design, Installation, Operation and Maintenance (DIOM) Manual Automist AP09 & AP12 Version 1.1 Release date 22 October 2024 Plumis Inc Copyright © 2024. All Rights Reserved...
  • Page 2: Table Of Contents

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Contents Contents ..............................1 1. Administration ............................ 4 1.1 Scope ............................. 4 1.2 Purpose ............................4 1.3 Retroactivity ..........................4 1.4 Equivalency ........................... 5 1.5 Units .............................. 5 2.
  • Page 3 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 5.1 Design Criteria ..........................20 5.2 Position of Spray Heads ....................... 23 5.3 Working Plan Drawing ......................... 29 5.4 Location of Spray Heads ......................30 6 Smoke Sensor Position and Location ....................30 6.1 Design Criteria ..........................
  • Page 4 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 9.12 Clearing the commissioning memory ................... 59 10 Hydraulic Calculations ........................59 Pipe Flow/Friction Factor Calculations I: (U.S. units) ................ 59 11 Acceptance ............................60 11.1 General ............................60 12 Inspection, Testing and Maintenance ....................
  • Page 5: Administration

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 1. Administration 1.1 Scope This DIOM is written to cover the design, installation, and maintenance of Automist, designed for the protection of one- and two-family dwellings, manufactured homes, and townhouses, as analogous to what NFPA 13D does for domestic sprinkler systems 13D sprinklers.
  • Page 6: Equivalency

    . Automist system Automist AP09 & Automist AP12 incorporate at least 1X smoke sensor (EVCA-PY- PL) 1X spray head (SH12) 1X Controller (CT03) 1X pump (AP09 or AP12) associated cables and piping.
  • Page 7: General Requirements

    The controller continually monitors the thermopile sensors by reading the temperature while parked, ensuring that all heads are ready to operate. When triggered by a Plumis wired sensor, all the linked spray heads will begin scanning. They start measuring the temperatures within the room using an infrared thermopile sensor.
  • Page 8 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 1: Interpretation of how the IR sensor views the fire Once the temperature exceeds a threshold that head is deemed to have successfully located a fire. All heads which locate a fire during a scan are then compared to see which has the best view.
  • Page 9 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Some properties may require more than one Automist system to be installed in order to provide adequate suppression coverage. Where more than one system is installed in the property, the designer should avoid having spray heads in the same room connected to different Automist controllers.
  • Page 10: System Diagram

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 4.2 System Diagram 1. Smoke sensor (EVCA-PY-PL) 2. Spray head (SH12) 3. Pump (AP09) 4. Controller (CT03) 5. High-pressure pipe ¼” BSPP connection 6. 2 Core Sensor cable 7.
  • Page 11: Technical Limitations

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 4.3 Technical limitations Automist has been performance tested within the following operational boundaries: • Maximum number of spray heads: 10 • Maximum number of smoke sensors in the system: 10 •...
  • Page 12 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 2 core sensor cable 90 m per leg 10 smoke sensors with 2 in series (5 input channels) 5 core data cable total length 80 m (262.47 ft)
  • Page 13: Spray Head

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 4.4 Spray Head Figure 5: Spray head (SH12) Weight 1.4 kg Size (main body) 133 mm (5.23 inch) (height) x 50 mm (1.96 inch) (depth) x 128 mm (5.03 inch) (width) Size (back box) 119 mm (4.68 inch) (height) x 60 mm (2.36 inch) (depth) x 103...
  • Page 14: Pump

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 4.5 Pump Pressure gauge pressure water supply inlet ¾” NPT female connection Figure 6: Pump isometric view (AP09) Internal check Pressure regulator valve Inlet port for air pressure compressor 3/4"...
  • Page 15: Automist Pump Specification

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Automist Pump Specification AP09 230V 50Hz The Automist pump comes in two variants AP09 and AP12. Ensure you have the correct pump to work with the electrical voltage supply in your country. Using the incorrect pump could result in electrical fires, electric shock and the system not performing as designed.
  • Page 16: Controller

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 4.6 Controller Figure 8: Automist Controller (CT03) Automist Controller Specification Input Supply Single phase Input Voltage 230V AC 50 Hz 240V AC 60 Hz Input Current Standby mode Up to 0.5 A...
  • Page 17: Controller Terminals

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 v1.13_AP-0-99e119e Software version number Dimensions 325 mm (12.79 inch) W x 310 mm (12.2 inch) H x 80 mm (3.14 inch) D Weight 6.75 kg (including battery) Mounting Location...
  • Page 18: Smoke Sensor

    4.7 Smoke Sensor EVCA-PY-PL The EVCA-PY-PL is a conventional photoelectric 2-wire smoke sensor only for use with the Plumis Automist Fire Suppression System. Only the base model number EVA-UB4 or EVA-UB4-6 should be installed. Operating voltage of 24 VDC. Quiescent current of 50 µA @ 24 V and alarm current of 50mA at 24V.
  • Page 19: Pipes And Fittings

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 The Model EVA-UB4-6 mounting base is intended for applications where a 6-inch square or octagonal electrical junction box is required. Figure 10: Plumis EVCA-PY-PL sensor No alternative model of smoke or heat sensor can be used with the Automist system 4.8 Pipes and Fittings...
  • Page 20: Data And Sensor Cables

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 • Avoid coating the last two threads of the male fitting to avoid compound breaking free and potentially causing a blockage in the nozzle. 4.9 Data and Sensor Cables Data cable specification •...
  • Page 21: System Strainer

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 4.11 System Strainer The Automist pump has a strainer incorporated to help prevent contaminants from entering the system and potentially causing blockages. This is a Y-type strainer with a port for inspection and flush-out.
  • Page 22 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 1.5 m (4.92 ft) Figure 12: Top view of the keep clear zone 1.5 m (4.92 ft) 1.5 m (4.92 ft) Figure 13: Obstructions are not allowed in the keep clear zone Plumis Inc Copyright ©...
  • Page 23 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Visibility extends radially from each mist head and ends wherever there is an obstruction. If an obstruction is fixed (e.g. a kitchen island with splashback, large fridge, bookshelf, or a built-in wardrobe) and equal or more than 0.9 m (2.95 ft) high, it must be regarded as blocking the line of...
  • Page 24: Position Of Spray Heads

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 sprayhead cannot be located away from an obstruction, an additional sprayhead shall be located to cover the other side of the obstruction. The overall objective of a working plan is to ensure the coverage pattern covers all the square footage within the property as required in NFPA 750.
  • Page 25 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 16: Automist spray pattern Figure 17: Automist in a kitchen Plumis Inc Copyright © 2024. All Rights Reserved Page 24 of 77...
  • Page 26 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Spray head >100 mm (>4 inch) 400 mm (15.75 inch) Figure 18: Automist spray head above a worktop The spray head must be positioned at least: • 1.5 m (4.92 ft) away from any hob •...
  • Page 27 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 0.55 m Bookshelf (21.66 ft) Figure 20: Bookshelf blocking a spray head (left) in keep clear zone an internal corner (right) • 0.9 m (2.95 ft) from the door hinge so the head is not located behind the door and is considerate of the direction of the swing.
  • Page 28 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 2. Select a position with a direct and unobstructed line of sight to the fire risks. Ensure most of the potential fire risks are in front of the spray head (e.g. the kitchen hob and dish washer or washing machine under the work surface).
  • Page 29 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 25: Spraying across the length room Figure 24: Spraying with the length of the room If there is a concern a spray head may be obstructed, it is advisable to add another spray head into the affected room to add redundancy.
  • Page 30: Working Plan Drawing

    5.3 Working Plan Drawing Plumis provides an online working plan tool required to facilitate the positioning of spray heads. The Automist installation shall be designed to facilitate easy maintenance. Parts requiring service or access (e.g. the pump and controller) shall be installed in an accessible location. Automist designs shall only be created by designers who have completed the Automist design training course.
  • Page 31: Location Of Spray Heads

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 5.4 Location of Spray Heads When the system is used to meet the Building Code, the locations of spray heads and therefore the coverage or protected area shall follow the requirements in NFPA 750. Section 10.3.2.8 details which type of room requires suppression and which are excluded (e.g.
  • Page 32: Water Supply

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 7 Water Supply 7.1 Flow, Pressure and Temperature Requirements The Automist fire pump is a positive displacement pump designed to discharge a constant flow of 9 litres (2.37gallons) per minute because only one Automist spray head will ever discharge at a fire, as this is electronically controlled.
  • Page 33: Installation

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 9. Installation 9.1 Water Supply (stock cock and pressure gauge) • Install a 3/4” water supply (connection) with a certified lock lever valve positioned so that the connection point will not be obstructed when the pump is installed. The cold-water supply must deliver the following dynamic flow and pressure: 11 litres (2.9 Gallons) per minute and maximum of 3 bar (43.5 Psi), minimum of 1 bar (14.5...
  • Page 34: High-Pressure Pipes And Fittings (Indoor Install)

    IMPORTANT REMINDER! Before installation ensure the high-pressure pipes are in line with Plumis guidelines. The maximum total length of the high-pressure pipe is 60 m. The maximum allowable distance between the pump and the furthest spray head is 30m.
  • Page 35: Data Cables

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 IMPORTANT! Pipes must be closed with caps to prevent contaminants from entering the water path until the second fix. IMPORTANT! So that fire separating is effective, every joint, or imperfection of fit, or opening to allow services to pass through the element which has fire-resisting function, should be adequately protected by sealing or fire stopping so that the fire resistance of the element is not impaired.
  • Page 36: Spray Head Installation

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 30: Wiring connection when 1 smoke sensor is connected to the alarm channel. IMPORTANT: The installer should consult with the designer with regard to the wiring configuration of the smoke sensors. If 2 smoke sensors are wired in series but will be programmed into different zones at the commissioning stage, both zones will be activated if either sensor is triggered.
  • Page 37 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 31: Electrical wire connectors ferrules After inserting the red, black, green, and white wires as indicated on the terminals, turn the screw clockwise until tight. Use a torque screwdriver on the following setting: minimum 0.22 Nm, maximum 0.25 Nm.
  • Page 38: Controller Installation

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 32: Electrical connections on the spray heads with ferrules 9.6 Controller Installation The controller should be mounted securely to the wall with 4 fixings, the installer should consider the type / material of the wall the controller is being mounted on and that the controller weighs 6.75KG including the battery when choosing which fixings to use.
  • Page 39 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Connect the Live and Neutral from the electrical supply to the inlet supply terminals at the top of the PCB. Connect the 230/240V AC supply cable to the pump to the outlet terminals at the bottom of the PCB.
  • Page 40: Connecting The Backup Battery

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 34: Ferrite installed to AC power cable 9.6.1 Connecting the Backup Battery When installing or replacing the battery connect the red battery lead to the positive terminal and the black lead to the negative terminal.
  • Page 41: Pump Installation

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 35: Controller Battery Securely attach the earth wire ring terminal to the lid and secure the lid to the controller with the screws provided. IMPORTANT: The earth connector to the lid must be connected, failure to do so could result in electric shock causing death or serious injury.
  • Page 42 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure : 1/4" BSP Parallel Male x M22 x 1.5 Metric Female adapter NOTE: For ease of installation connect the adapter to the high pressure pipe before connecting the adapter to the pump.
  • Page 43 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 38: Pump bung The AC power cable between the controller and the pump must be rated for 230V 20 amp as a minimum specification. The AC power cable between the controller and the pump for a 240V 60Hz pump must be rated as 240V 15amp as a minimum specification.
  • Page 44 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Crimp an insulated ring terminal connector M5 stud size to the Live, Neutral and Earth wire of the supply cable. Connect the 230/240V AC Power supply to the pump's AC Power terminal as pictured below. The terminal prewired with the red wire is Live, the terminal prewired with the black wire is Neutral and the terminal with the prewired green cable is Earth.
  • Page 45: Zone Configuration

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 IMPORTANT: The earth connector to the lid must be connected, failure to do so could result in electric shock causing death or serious injury. 9.8 Zone Configuration The Automist system can have up to 10 zones configured to the system. Each room would generally be classed as 1 zone;...
  • Page 46: Powering Up The System

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 42: Zone Diagram 9.9 Powering up the system Connect the battery, see section 7.6.1. Connect the red lead to the positive terminal and the black lead to the negative terminal of the battery.
  • Page 47: Setting The Time And Date

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 9.9.1 Setting the time and date When the system is first powered up, or a commissioned system has been down powered for a long period of time, the controller will go straight to the time and date menu.
  • Page 48: Commissioning Stage 1 - Addressing

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 4. Discharge (or flow). Test each spray head to verify the correct pressure and water flow is being expelled from the nozzle. This replicates a response to a fire while allowing for the water to be collected.
  • Page 49 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 45: Commissioning Stage 1 Poke each head by briefly and firmly pressing the side of the pivot head. Figure 46: Gently press the outside surface of the spray head with your finger to address it The spray head’s LED will change from flashing yellow to green and the controller will beep to...
  • Page 50: Commissioning Stage 2 - Self-Test

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 9.9.2.2 Commissioning Stage 2 - Self-test The display will show Testing Heads with a progress counter from 0-100%. The spray heads will start to scan the room during the self-test. When the test is 100% complete the spray heads will return to the flush position with a green light.
  • Page 51: Commissioning Stage 4 - Flow Test

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 48: Commissioning stage 3 If you assign a spray head to the smoke sensor in error, poke the spray head again to unpair the spray head with the smoke sensor, the spray head will turn red to indicate it has been unpaired.
  • Page 52 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 49: Gently poke the spray head The nozzle will then rest at a 90-degree position and the LED will turn solid yellow waiting for the flow test to begin.
  • Page 53 By leaving an installed system with pressures outside the specified range, you could be liable for deaths or injuries. If the achieved output pressure is outside the specified range, refer to the commissioning troubleshooting guide and contact Plumis if the issue cannot be resolved.
  • Page 54: Commissioning Stage 5 - Drainage

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 52: Remove the commissioning hose and gently poke to close the spray head Repeat the process for every spray head. When all the spray heads have been tested the controller’s display will show the number of spray heads tested compared to the number of spray heads programmed in the system.
  • Page 55 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 54: Commissioning stage 5 Connect an air compressor with a Schrader type female connector to the pump’s inlet port. inlet port for air compressor Figure 55: Pump inlet port for air IMPORTANT! The high-pressure pipe must be cleared of water by an air compressor pump with a maximum pressure of 8 bar (116 Psi).
  • Page 56: Commissioning Stage 6 - Sensor Test

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 NOTE: The spray heads when released from the locked position will expel some low-pressure water from the nozzle, be prepared to catch the water in a bucket or paper towel as soon as the spray head is poked.
  • Page 57 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 When temperature difference is detected, it will flash green and return to the locked position and the LED will turn green. Repeat this process for each spray head, when all sensors have been checked the controller will display FINISH and the total number of tested heads will be displayed.
  • Page 58 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Figure 57: Controller Automist System Healthy Attach and fasten the front plate to the intermediate plate and align, ensuring parallelism to floor and wall. Figure 58: Front plate attached on the spray head Ensure there is good clearance around the rotating head and the front plate.
  • Page 59: Programming The Outputs

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 9.10 Programming the outputs The controllers’ relays will default to operate as per table below Relay Configuration System is healthy and protecting Possible reasons: (default) from fire. System is not commissioned.
  • Page 60: Enabling The Sounder Monitoring

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 NOTE: when in the Menu mode, if a button is not pressed for 1 minute the system will time out and revert back to idle mode, any changes not saved will need to be reprogramed by following the steps above.
  • Page 61: Acceptance

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 f = [1.14 + 2 log ε Pipe Diameter, D = 0.315 in, Pipe ID = 8 mm Pipe Diameter, D = 0.0263 ft Pipe Roughness, ε = 0.00015 ft, Commercial Steel Friction Factor, f = 0.03159...
  • Page 62: Inspection, Testing And Maintenance

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 If plumbing or construction work takes place, new smoke sensors are installed, or • maintenance work occurs which could affect the system. After an activation following a fire.
  • Page 63: Smoke Sensor Activation Test

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 • The sensitivity of the EVCA-PY-PL sensor must be in the range of 3.56%/ft to 4.78%/ft. If the sensor fails the sensitivity test it must be cleaned and retested, if the sensor fails again, it must be replaced.
  • Page 64: Testing The Sounder Output

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 • The smoke sensor test mode is deactivated by pressing the STOP button; this will be confirmed by the GREEN LED returning to constantly lit and the display showing System healthy.
  • Page 65: Replace The Consumables

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 Do not disassemble, repair, or modify the smoke sensors. It may cause a fire or electric shock. 1. Carefully remove the sensor head from its base. 2. Use a soft, lint-free cloth, moistened with alcohol for sticky deposits, to clean the plastic enclosure.
  • Page 66: Troubleshooting

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 13 Troubleshooting If the Automist controller detects a fault the yellow LED will flash, and the controller will beep. The display will show an error ID code. Use the table below to identify the description of the error code and the suggested corrective action to resolve the issue.
  • Page 67 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 ERR_HEAD_ERROR_SMOKE The smoke sensor input on the 1. Find which spray head is flashing 7x red pulse per cycle. SENSOR_SHORT_CIRCUIT spray head is shorted. 2. Check the smoke sensor wiring.
  • Page 68 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 ERR_CTLR_PAIRED_SMOKE SENSOR_NOT_BROADCASTING ERR_SMOKE Commissioned smoke sensor 1. Check if every smoke sensor is secured on its base. SENSOR_OPEN_CIRCUIT end-of-line resistor is not 2. Check the smoke sensor’s wiring.
  • Page 69 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 ERR_SM_COMMS_PM_COMMA NDS_FAILING ERR_SM_COMMS_UI_COMMA NDS_FAILING ERR_PUMP_TEST The pump motor test failed. Possible cause: a. Short circuit (motor + wiring resistance < 0.3 Ohms). b. Open circuit (motor + wiring resistance > 3 Ohms).
  • Page 70 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 3. If the error persists - replace the controller. ERR_AR_RELAY_FAULT The controller relay outputs Replace the controller. driving circuit is faulty. ERR_GROUND_FAULT_LIMIT_L Ground is shorted to 0V. 1. Check the wiring.
  • Page 71 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 3. If the error persists – replace the controller. ERR_COMM2_24V_DRIVE_FAUL ERR_COMM1_OVERCURRENT_F Controller RS485 bus 24V 1.25 A current limit is exceeded. AULT overcurrent. Steps to resolve: 1. Disconnect all the wires from the controller RS485 primary connector.
  • Page 72 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 ERR_PRES_IN_FAULT_LIMIT_HI ERR_SND_24V_FAULT_LIMIT_L The sounder's driving voltage is 1. Disconnect sounder. too low. 2. If the error goes away – replace the sounder. 3. If the error persists - replace the controller.
  • Page 73 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 ERR_PM_BATTERY_UNDERVOLT The backup battery voltage is The measured battery voltage is < 11V. AGE_LIMIT low. 1. Wait for a few hours, the battery should charge automatically, and the error will disappear.
  • Page 74 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 4. If the error persists – replace the controller. ERR_RTC_HARDWARE Controller internal error. Replace the controller. ERR_PCB_TEMP_SENSOR_HARD WARE ERR_SERVO_FEEDBACK_OUT_O The spray head's main body Possible cause: F_RANGE position is not in the requested 1.
  • Page 75 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 ERR_UI_LED_DRIVER_HARDWA User Interface LEDs and LCD Replace the controller. backlight are not working. ERR_HEAD_FAILED_WIGGLE_TE During periodic head movement, 1. Check which spray heads are blinking red or yellow.
  • Page 76: Appendix

    Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 14 Appendix Table of Figures Figure 1: Interpretation of how the IR sensor views the fire ..............7 Figure 2: System Diagram ........................9 Figure 3: Understanding the maximum hose lengths ................10 Figure 4: Technical Limitations Summary .....................
  • Page 77: Plumis Part Numbers

    Figure 58: Front plate attached on the spray head ................57 15 Plumis part numbers Plumis manufacture and supply the core components of the Automist system, other components can be sourced locally from various suppliers such as flow and pressure gauges, cable ferrules and data cable.
  • Page 78 Automist AP09 & AP12 DIOM version 1.1 Release date 22 October 2024 may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off...