1,000 m above sea level. 2. CONFIGURATION Body of LEL Point 2000 is made of Aluminum alloy and the gas sensor module is made of stainless steel. It consists of a complete explosion-proof enclosure (Ex d IIC T6). This product can be installed in areas with combustible gas leak and explosion hazards.
LEL POINT 2000 Smart Diffusion Flammable Gas Detector 4. NAME AND DESCRIPTION OF EACH PART 4.1. COMPONENTS Figure 2. LEL Point 2000 Components Items Specification Protects PCB Board built in Sensor and Housing from Housing Body external environmental change and shock.
Page 7
It is a multi-color LED that displays status. It serves to fix parts to the compliment part. Shaft Body It serves to fix parts to the opponent. Cable Wire It supplies power and transmits data. Table 1. LEL Point 2000 Description of Components...
LEL POINT 2000 Smart Diffusion Flammable Gas Detector 4.2. LAMP FUNCTION DESCRIPTION • In normal status, green LED lights on and buzzer does not ring. • When Alarm-1 signal is received, red LED flickers in 1 sec interval and buzzer rings in 1 sec interval.
5.2. MAIN PCB CONFIGURATION After detaching the display parts, the Main PCB terminal layout appears as shown in the figure below. Figure 5. Main PCB Terminal Layout Name Description Power & Output Signal Terminal 4~20mA Source / Sink Selection Jumper ( ON: Source Type, OFF: Sink Type) Display LCD Connector Sensor Connector...
Page 10
Table 3. CN8 Terminal Detailed Description • Use CVVS or CVVSB 2.0sq↑ Shield Cable for terminal configuration. • To connect 4 Pin terminal from the existing old LEL Point 2000 model, connect terminals in reference to pin #2, which is +24V.
5.2.1. WIRING FOR 4~20MA SOURCE OPERATION TYPE • Connect 4-20 mA signal terminal at PLC side to 'mA'of LEL Point 2000. GND terminal is used in common with power. Then, turn on the J1 jumper. • HART Communicator can only be used in models using HART Option board.
J1 jumper. Figure 9. 4-20mA 3Wire Sink Configuration 5.3. INSTALLATION CABLE LENGTH • The maximum length between LEL Point 2000 and power supply is decided by wire specification. • Max. Installation Length = VMAXDROP ÷ IMAX ÷ WIRER/m ÷ 2...
1.31 0.02095 0.82 0.0333 0.518 Table 4. LEL Point 2000 Power Cable Installation Length 6. INSTALLATION 6.1. INITIAL OPERATION STATUS (POWER ON) • After wiring to power terminal at the top of Main PCB board then supply power, the following contents are displayed on LCD.
Timeout for Level1 and Level2 are 10 sec. It is set to 1 hour for Level2 Calibration and Test Mode. • When "RESET" key contacts at Program Mode Screen, it returns to Measuring Mode. When "RESET" key contacts at each Program Setting Screen, it returns to the parent step. LEL Point 2000 Figure 11. LEL Point 2000 Mode Configuration...
• Operation keys for detector system mode are defined as below. Item Name Description Detector Mode Setting Entry Function (Insert Magnetic-bar for 2 sec or longer in measuring mode) Level2 Next stage FUNC Function key entering function and setting saving function Move to the previous stage from the level entered.
• Mode that sets gas measuring unit and contacting "↑" or "↓"key changes UNIT SEL gas measuring unit. ( % / %LEL / PPM / PPB ). [ %LEL ] • When a desired gas measuring unit is displayed, contact "FUNC" key to set the unit and enter Program Mode.
LEL POINT 2000 Smart Diffusion Flammable Gas Detector ZERO >> • When zero calibration is successful, "ZERO SUCCESS" is displayed for 2 [SUCESS] sec on LCD display then it changes to "CALIBRATION DATA" Mode. • When zero calibration is not successful, "ZERO FAIL" is displayed for 2 sec and it changes to "Calibration Data Mode".
SPAN >> • After completing standard gas value setting, contacting "FUNC" key [SUCESS] automatically runs Span Calibration. When it suceeds, "SPAN SUCCESS" is displayed on LCD display for 2 sec then it changes to "CAL DATA" Mode. • When span calibration is not successful, "SPAN FAIL" is displayed for 2 sec SPAN >>...
Page 20
LEL POINT 2000 Smart Diffusion Flammable Gas Detector • It is a mode that sets Dead band value for Alarm1 operation. Use "↑" or "↓" key to set a value. • It is a function where Alarm1 operates at values above the sum of Alarm1...
10. DRAWINGS AND DIMENSIONS 10.1. SELECTING A PLACE FOR INSTALLATION (OCCUPATIONAL HEALTH & SAFETY ACT DATA) A gas leak detector alarm shall be installed in the following places. • Around chemical equipment and accessories that have concerns of gas leak. This includes compressors, valves, reactors, pipe joints, etc.