OWNER'S MANUAL
INSTALLATION INSTRUCTIONS
MONTARA
8,000 BTU/hr.
TECHNICAL AND USER MANUAL
HP003
SAVE THIS MANUAL FOR FUTURE REFERENCE. BEFORE
INSTALLING AND USING THIS AIR CONDITIONER PLEASE
READ ALL INSTRUCTIONS CAREFULLY.
Silent Inverter, Silent Hybrid Inverter, Clima Puro are conform to Below : 
 
 
 
 
 
 
 
 
 
 
 
Waste  electrical  products  should  be  disposed  of  with  household  waste.  Please  recycle  where 
facilities exist. Check with your local authority or retailer for recycling advice. 
Do not dispose this product as unsorted municipal waste. Collection of such waste separately for 
special treatment is necessary.  
Any  batteries  used  in  the  remote  control  contain  materials,  which  are  hazardous  to  the 
environment. They must be removed from the remote control when they reach the end of their 
life and disposed of responsibly.  
 
1.6 TECHNICAL FEATURES(P1,P2) 
 
M M o o d d e e l l
Cooling capacity* W / BTU/h
Heating capacity* W(BTU/h)
Electrical heat* W(BTU/h)
250 West Laurel Street, Colton CA 92324
Hot water capacity** W(BTU/h)
Rated voltage (V/Hz)
Absorbed power in cooling* (W)
Absorbed current in cooling* (A)
HEAT PUMP
S S I I L L E E N N T T
S S I I L L E E N N T T H H Y Y B B R R I I D D
I I N N V V E E R R T T E E R R
I I N N V V E E R R T T E E R R
2350(800~2590)
2350(800~2590)
/8020(2730~8840)
/8020(2730~8840)
2320(800~3820)
2320(800~3820)
/7920(2730~13040)
/7920(2730~13040)
1550(5300)
1550(5300)
1160(3960)
208/230/60,1ph
208/230/60,1ph
900
900
4.4
4.4
VISITE NUESTRA PÁGINA WEB PARA LA VERSIÓN EN ESPAÑOL DE ESTE MANUAL
https://https://www.williamscomfort.com/product/montara-heat-pump/
EN 
WARNING: This product can expose you to
chemicals including epichlorohydrin which is known to
the State of California to cause cancer and birth defects
and/or other reproductive harm. For information go to
www.p65warnings.ca.gov
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause injury or
property damage. Refer to this manual. For assistance or
C C L L I I M M A A P P U U R R O O
for additional information consult a qualifi ed installer,
2350(800~2590)
service agency or the gas supplier.
/8020(2730~8840)
2320(800~3820)
/7920(2730~13040)
1550(5300)
www.williamscomfort.com
208/230/60,1ph
900
4.4
1-888-444-1212
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MONTARA HP003 and is the answer not in the manual?

Questions and answers

Summary of Contents for Williams MONTARA HP003

  • Page 1 OWNER’S MANUAL INSTALLATION INSTRUCTIONS VISITE NUESTRA PÁGINA WEB PARA LA VERSIÓN EN ESPAÑOL DE ESTE MANUAL https://https://www.williamscomfort.com/product/montara-heat-pump/ MONTARA HEAT PUMP ™ 8,000 BTU/hr. TECHNICAL AND USER MANUAL HP003 SAVE THIS MANUAL FOR FUTURE REFERENCE. BEFORE INSTALLING AND USING THIS AIR CONDITIONER PLEASE EN ...
  • Page 2: Table Of Contents

    CONTENTS TABLE OF CONTENTS SAFETY RULES INTRODUCTION ELECTRIC WIRING DIAGRAM INSTALLATION REMOTE CONTROL OPERATION MAINTENANCE HP003 EXPLODED VIEW HP003 REPLACEMENT PARTS TECHNICAL DATA DISPOSAL INFORMATION MONTARA HEAT PUMP...
  • Page 3: Safety Rules

    SAFETY RULES refrigerant can possibly be released to the surrounding WARNING R32 Refrigerant : Do not use means to space. Prior to work taking place, the area around accelerate the defrosting process or to clean, other than the equipment is to be surveyed to make sure that those recommended by the manufacturer.
  • Page 4 equipment during servicing, then a permanently operating Removal and evacuation: form of leak detection shall be located at the most critical When breaking into the refrigerant circuit to make point to warn of a potentially hazardous situation. repairs – or for any other purpose – conventional procedures shall be used.
  • Page 5 Decommissioning: Recovery: Before carrying out this procedure, it is essential that the When removing refrigerant from a system, either for technician is completely familiar with the equipment and servicing or decommissioning, it is recommended good all of its detail. It is recommended good practice that all practice that all refrigerants are removed safely.
  • Page 6: Introduction

    INTRODUCTION 1.1 INTRODUCTION: Avoid prolonged direct contact with the flow of the air from the air conditioner and the room being closed with PLEASE NOTE: Do not dispose of any packaging until the no ventilation for a long period of time. installation of the air conditioner is completed.
  • Page 7 1.6 DISPOSAL OF WASTE Waste electrical products should be disposed of with household waste. Please recycle where facilities exist. Check with your local authority or retailer for recycling advice. Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.
  • Page 8: Electric Wiring Diagram

    OPERATING CONDITIONS IN HEATING MODE:  ‐Inside 21.1℃ DB, 15.6℃ WB  ELECTRIC WIRING DIAGRAM ‐Outside 8.3℃ DB, 6.1℃ WB    1.7 WIRING DIAGRAM  1.8 WIRING DIAGRAM                                                        ...
  • Page 9: Installation

    2.1 POSITIONING THE AIR CONDITIONER(P3)    To maintain the best performance from your air conditioner, prevent breakdowns or hazards, you  INSTALLATION must position it correctly. Please follow the guidelines and instruction below in full, as failure to do  so could cause potential installation problems.   P3    ‐The  air  conditioner  must  be  installed  on  an    2.1 POSITIONING THE HP003 MONTARA HEAT PUMP After determining the best location for installation as exterior  wall  that  has  access  to  the  outside  AIR CONDITIONER Refer to Reference P2 : described above, please check to ensure that the wall can  ...
  • Page 10 EN  2.3 AIR CONDITIONER UNIT DIMENSIONS 23.26in (591mm)     21.69in (551mm)         6.45in (164mm)       3.14in (80mm)   1.417in (36mm)                              ...
  • Page 11 2.4 DRILLING THE WALL P4 : Please note: If you are drilling the hole above ground floor level, please ensure that an area has been secured and while the holes are drilled the outside area is supervised, EN  until the drilling is completed. Intake and outlet holes: This operation should be carried out using the proper tools (diamond tip or core borers drills with high...
  • Page 12 EN  2.6 INSTALLATION OF THE PIPES P9 stic  sheet  WARNING: The appliance should not be installed in ed  to  be  After drilling the holes, the a laundry room. plastic sheet supplied with the The appliance must be positioned so that the plug is air conditioner needs to be t supplied ...
  • Page 13: Operation And Maintenance

    EN   OPERATION AND MAINTENANCE REMOTE CONTROL OPERATION   EN  TION OF LCD ICONS  3.1 INTRODUCTION OF ICONS ON 3 CONTROL OPERATION AND MAINTENANCE   Infrared Sensor LED Flashlight YOUR REMOTE CONTROL   3.1 INTRODUCTION OF LCD ICONS      Means   Icons Means DEFINITION     Auto     AUTO MODE Auto  ...
  • Page 14: On Board Control Function

        N AND MAINTENANCE   Icons Means 3.1 INTRODUCTION OF LCD ICONS          Auto       Icons Means CONS      CONTROL FUNCTIONS     Cooling   Auto                 Cooling        ...
  • Page 15: Program Settings

    3.5   PROGRAM SETTING    3.4 WI FI CONNECTIONS 3.5 PROGRAM SETTINGS Unit can work with different program modes, P1~P6 as below are available for the unit.   Unit can work with different program modes. P1~P6, as shown Before using your Wi Fi function for the first time, you   below are available for the unit. must configure the Wi Fi signal and settings through your 1.
  • Page 16: Maintenance

    MAINTENANCE 4.1 FILTER CLEANING FOR PRE FILTER The filter should be regularly cleaned to keep the air conditioner running efficiently. Clean the filter every two weeks. Take out the filter with two handles How to proceed: Disconnect the air conditioner from the electrical supply. Remove the top inlet grille as shown.
  • Page 17: Troubleshooting

    4.3 TROUBLESHOOTING 4.4 ERROR CODE DESCRIPTION: Error Anomaly Possible Cause Solution Fault description Running State Code Check the voltage (by turning the Over-voltage/ under-voltage protection Not working light on, for example). Indoor temperature sensor fault Not working Check that the exclusive magneto-thermic switch that Indoor coil temperature sensor fault Not working...
  • Page 18 4.5 CLEAN CONTACT FUNCTION WINDOW OR KEY CARD 4.6 6 3 8 in 162MM SOFT GRATING INSTALLATION To fix the two external soft gratings, please proceed This unit has a CLEAN CONTACT function on the main PCB, as following: mainly used for hotels and offices. This function can be used 8.2 Clean contact function(window or key card) ...
  • Page 19: Hp003 Exploded View

    HP003 EXPLODED VIEW...
  • Page 20: Hp003 Replacement Parts

    HP003 REPLACEMENT PARTS HP003 Replacement Parts List Description Window display cover Step motor Display PCB+connection cable Main PCB Main PCB box Condenser fan Inverter compressor Outlet grille Indoor AC motor Indoor cross fan PTC heater Fresh air filter Wall bracket Drain pipe 4-way valve coil Remote control...
  • Page 21: Technical Data

    TECHNICAL DATA Technical Data Unit Model HP003 Indoor D.B. 80 (26.7), W.B. 67 (19.4) °F (°C) Outdoor D.B. 95 (35), W.B. 75 (23.9) Cooling Capacity Nominal BTU/h (min-max W) 8000 (800-2590 W) Cooling Input Power Efficiency Efficiency SEER2 13.9 Indoor D.B.
  • Page 22 TECHNICAL DATA Volt range 208/230 Hz/Phase 60Hz 1 / 1 Phase Power Factor 0.96 Fuse (T3, 15L) Rated Absorbed Current for cooling Electrical Rated Absorbed Current for heating Rated Absorbed Current for PTC Electric Heater 6.65 Heating Max (Heating pump + PTC electric heater) WiFi device included in the Machine Tuya App in (cm) 39.7 (100) W x 21.9 (55) H x 6.5 (16) D...
  • Page 23: Disposal Information

    DISPOSAL INFORMATION...
  • Page 24 www.williamscomfort.com | 888-444-1212 | 250 West Laurel Street, Colton CA 92324 USA Subject to change without notice | © 2024 MONTARA D113681-A 10/24 HEAT PUMP...

Table of Contents