O V E R H E A D D E H U M I D I F I E R INNO-225pOHDh User Manual The installation and maintenance of this unit must be performed by a professional technician who holds a professional qualification certificate that meets the local installation and maintenance requirements and who has experience in the installation and maintenance of this model.
FEATURES Overhead type dehumidifier is powered by electricity, and through the principle of freezing and dehumidifying, the indoor air is dehumidified and processed, and sent to the required dehumidified room. Energy-saving and high efficiency As the unit adopts the principle of condensing heat recovery to re-temperature the air after dehumidification, it reduces the unit's heating energy consumption and improves the operating efficiency of the whole unit.
COMPONENTS Fan section The fan section consists of the impeller/worm housing assembly of the fan and the fan motor. There is a thermal insulation layer between the water collection tray and the box of the unit to avoid condensation of the box. The fan of the unit is a high-efficiency centrifugal fan, and the noise of the fan motor is much lower.
Page 5
2. Condensate discharge: (see Figure 3) When installing the condensate pipe or hose, there must be installed water storage bend at least 1 inch (25mm) height on the condensate pipe, such as static pressure greater than 250Pa storage bend height should increase (1mmH2O = 9.8Pa).
MAINTENANCE 1. Start up: After the unit is installed, the air duct, condensate discharge pipe and power supply line are connected, and all internal wiring and wiring with external control devices are checked for correctness, it is ready to start. 2.
Page 7
Open filter clogged Check the filter, if found too dirty, should be cleaned or replaced Unit running If the compressor is running and the evaporator is not cooling, it Compressor failure or refrigerant leakage indicates that the compressor is malfunctioning or the refrigerant dehumidifying is leaking Clogged air filter...
OPERATION Control System The microcomputer control system of the unit has the following functions. -Random start relay -Protection against frequent compressor start/stop -High and low-pressure protection -Motor thermal overload protection -Filter cleaning reminder (optional) -Self-start for incoming calls Note: The function to prevent frequent compressor start/stop prevents the compressor from restarting within 3 minutes after stopping operation.
Page 9
Power button Minus On/Off to switch the machine on or off. Press Mode Press to choose Dehumidifying or Ventilating mode. Fan speed By pressing the button, you can set the fan speed. The fan speed conversion order: 1 gear-2 gear-3 gear-4 gear-5 gear-6 gear-1 gear Only available in the ventilation mode.
Page 10
select the hour of timer on, press the to select the minute of timer on. After setting, press and hold the 5 seconds to exit and save the timer start time. You can also wait for the timer to finish all set and then long-press the for 5 seconds to exit and save.
Page 11
Fan speed Machine type Mainboard program version number In-line control program version number Compressor 1 status 1=on;0=off; Compressor 2 status 1=on;0=off; Fan status 1=on;0=off; Water pump status 1=on;0=off; High-pressure switch 1 1=on;0=off; status Low-pressure switch 1 1=on;0=off; status High-pressure switch 2 1=on;0=off;...
Page 14
WITH THIRD PARTY HARDWARE OR THE ABILITY TO CONNECT TO AND CONTROL THIRD PARTY HARDWARE FOR THE CUSTOMER’S INTENDED PURPOSE. THEPROTECTOR ADDITONALY AND SPECIFICALLY DISCLAIMS ANY AND ALL LIABILTY FOR CHANGES, ADDITIONS OR UPDATES IN ANY WAY TO A THIRD PARTY MANUFACTURES PRODUCTS. Innovative Tool and Design, Inc. 10725 Capital St Oak Park MI 48237 USA www.shoptheprotector.com...