396-3053Y1
Catalyst™ Electric Pump System
for NutriSphere-N® NH3
AFS Pro 700
AccuControl
396-3053Y1
SureFire Catalyst for NutriSphere®-N NH3 for Pro 700
Revised 09/30/2016

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SureFire NUTRISPHERE-N VERDESIAN Catalyst AFS Pro 700 AccuControl and is the answer not in the manual?

Questions and answers

Summary of Contents for Case SureFire NUTRISPHERE-N VERDESIAN Catalyst AFS Pro 700 AccuControl

  • Page 1 396-3053Y1 Catalyst™ Electric Pump System for NutriSphere-N® NH3 AFS Pro 700 AccuControl 396-3053Y1 SureFire Catalyst for NutriSphere®-N NH3 for Pro 700 Revised 09/30/2016...
  • Page 3: Table Of Contents

    Table Of Contents Introduction Read Me First ..................2  Basic Steps to Install your System ............3  Introduction System Overview Drawing ..............4  Components - Liquid Flowmeter, Zip Valves ................5,6  Pressure Sensor, Pump Priming and Air Bleed Valve ......7 ...
  • Page 4: Read Me First

    Read Me First Catalyst™ The SureFire system is designed to give accurate and even row-to-row distribution of NutriSphere-N NH3 at a normal rate of 32 oz/acre. It has the capacity to deliver higher rates if desired. Note: Ounces/acre, not gallons/acre. Ounces per acre means a very small amount of liquid is being pumped and distributed.
  • Page 5: Getting Started

    Ag Leader Liquid Product Control Module  Trimble Field-IQ Rate and Section Control Module  Case IH Pro 700 with AccuControl  SureFire Commander II controller Note: SureFire Ag Systems also has the SureFire Torpedo system, a complete anhydrous ammonia application system.
  • Page 6: System Overview Drawing

    System Overview - Example 1 The following gives a layout of the SureFire Tower 100 system with these components: Introduction  Controller display in cab  Field-IQ module  Tower 100  Flow Indicators with a ZIP valve on each manifold SureFire Adapter Harness–...
  • Page 7: Components Liquid

    Electromagnetic Flowmeter 204-01-4621CUF05 0.08 to 1.6 GPM (10 oz/min to 205 oz/min) Components Liquid Mounting Bracket, Used in Tower 100 410-2106Y1-BK Electromagnetic flowmeters are superior to traditional turbine flowmeters in two basic ways. First, they have no moving parts. This translates into no wear items or potential for contaminants to jam a spinning turbine.
  • Page 8: Components Liquid

    Section Valves and Flow Indicator Manifold Shutoff Valves ZIP Valves Components Liquid ZIP valve on right shown with both electrical connectors plugged (if daisy-chaining from one to the next). Outlets can be plumbed with a variety of fittings depending on the particular scenario.
  • Page 9: Pressure Sensor, Pump Priming And Air Bleed Valve

    Pressure Sensor Components The Pro 700 with AccuControl currently does not support the use of a liquid pressure sensor. Liquid The kit for the Pro 700 system includes a pressure gauge. A pressure reading is helpful troubleshooting information and helps in selecting which metering tube to use.
  • Page 10: Flow Indicators And Manifolds

    Product Distribution To assure proper and even distribution to each row, the product being applied Components must be metered to each individual row. This metering is done by using Liquid metering tubes which create back pressure so an equal amount of liquid is applied to each row.
  • Page 11: Metering Tube Systems

    Flow Indicators and Dual Check Valves Components Liquid Some systems may have a dual check valve system with two metering tubes as shown at the right. On this system, flow can be directed to the small tube, or to the large tube, or to both tubes by opening or closing the valves by twisting the blue caps.
  • Page 12 Metering Tube Plumbing Kits Components Liquid Catalyst The SureFire Tower 100 NutriSphere-N NH3 system comes with a dual metering tube distribution system. These plumbing kits will contain everything you need to distribute product from the flowmeter outlet down to the ground application device. For most applications of NutriSphere-N NH3 at 32 oz/acre on 30”...
  • Page 13: Plumbing Setup, Shank And Knife Points

    Typical plumbing setup Your shanks and plumbing setup may vary from those shown here. The 4’ green tube delivers the product to the shank. Components Liquid 1. Slide a 2’ piece of 3/8” hose over the green tube along with 2 clamps. 2.
  • Page 14 Shanks and Knife Points available from SureFire Ag Systems SureFire Ag Systems and Verdesian have worked closely with an established shank manufacturer to develop a shank and several knife points that will deliver the anhydrous ammonia and NutriSphere-N NH3 where it needs to go.
  • Page 15 Sample of available knife profiles 396-3053Y1 SureFire Catalyst for NutriSphere®-N NH3 for Pro 700 Revised 09/30/2016...
  • Page 16: Toolbox (Spare Parts)

    Toolbox (no tools, just spare parts) Components A toolbox containing critical items will be included with each system. The toolbox will Liquid contain:  12 volt electric pump  flow indicator columns  size 6 hose clamps  3/8” HB 90 degree electric pump fitting ...
  • Page 17 396-3053Y1 SureFire Catalyst for NutriSphere®-N NH3 for Pro 700 Revised 09/30/2016...
  • Page 18: Connecting To Pro 700 Accucontrol With Field-Iq Module

    Pro 700 display are included showing exactly what settings are required and recommended for the SureFire system. Check with your Case (NH) dealer at least annually to be sure that the Pro 700 display and the Field-IQ module have the latest software/firmware updates.
  • Page 19 Section Control Module. Use this information to verify if the AccuControl system is providing the correct output. If the module is not providing the correct output, contact your Case IH dealer to repair the problem. Also review any applicable settings on the display to verify the system is properly set up.
  • Page 20: System Layout

    Sections: 2 Wiring & Elec. Field IQ module P/N 201-215464Y4 30-Pin to twin 16-Pin Pro 700 Adapter Harness display in 2-pin power connector Case/Trimble harnesses Implement Lift Switch Connector (optional) P/N 207- 3057Y1 Flow Pressure (not used on Pro 700)
  • Page 21: Pwm Epd

    40 Amp PWM EPD (Pulse Width Modulated Electric Pump Driver) Wiring & Elec. Item Number: 205-19024 with Anderson connectors Replaces 205-18385 with 480 connectors The Electric Pump Driver powers the electric pump by providing a pulse width modulated signal to control pump speed.
  • Page 22: Wiring Harness Drawings

    Wire Size: 18 AWG unless Length: 3ft 201-215464Y4 Sections otherwise specified Trimble Field IQ Adapter Cable – 30 pin to twin 16 pins- 2 pressure 16 Pin Round – AMP Cinch Connector Valve GND Male pins in male body Section 2 +12V (with threads for Section 3...
  • Page 23 207-3057Y1 Tower Final harness w 2 sections Section 1 WP Tower PWM Pump Cable – Flowmeter, PWM & Pressure 3-PIN RED 14 AWG Length: 10ft +12VDC BLK 14 AWG Wire Size: 18 AWG Signal Section 2 WP Tower 3-PIN RED 14 AWG +12VDC 150 MP BLK 14 AWG...
  • Page 24: Installation Overview

    SureFire Catalyst Verdesian NS-N NH3 and Case Pro 700 AccuControl— Harness hookup Installation Harnesses for your particular system may vary from the list here. Not all of these harnesses Overview will be used on all systems. 205-3118Y1 Anderson 40 Amp Fused Power Harness (connect to battery)
  • Page 25: Tower 100 Plumbing Overview And Valve Operation, Recirculation

    Tower 100 Plumbing Overview & Valve Operation Installation Overview Outlet from flowmeter EPD (Electric Pump to flow indicators Driver) see section D for details Continuous recirculation flow regulated by 1/4 turn valve. Valve will normally be closed. 12 volt diaphragm Metering tube diameter pump and length can be...
  • Page 26: Tower 100 Plumbing Detail

    Catalyst Tower 100 Plumbing Detail (Bottom of Product Tank) Installation Overview To System (Tower) From Product Tank Common Port of valve always goes to System / Pump From 3 gal rinse tank Drain Valve to drain tank— 3-Way Valve 1/4 turn valve The long end of the handle points toward the source—product tank or to open or...
  • Page 27: Tower 100 Tank Cradle And Mounting Brackets

    Tower 100 Mounting Options Various brackets and u-bolts are available to provide a way to mount the Tower 100 to Installation almost any implement. Overview Your SureFire configuration specialist will get your implement information at ordering time and make sure that all of the hardware needed for your system is included. ITEM NO.
  • Page 28: Pro 700 Display General Setup

    Pro 700 Display Setup for AccuControl and SureFire Systems General Pro 700 Operation Setup & Operation Home Screen Status and Warning Left-hand Area— -Created by the vehicle -Is always displayed -Some parts may be configurable on the Layout screen -A window placed here has priority over the same window placed on a “Run”...
  • Page 29 Setup & Operation Items in Work Condition include: Layer Valve Operation Controller Product Assignment Calibration Setup Setup Calibration You must create or select a Work Condition to complete the setup for product application. Items in Run include Run1 through Run6. Items under the Performance icon could include: Profile Sum1...
  • Page 30: Accucontrol Configuration

    Configuration will probably be set up as an Anhydrous operation with an Anhydrous Toolbar. In that case, the Catalyst system for the NutriSphere N– NH3 will be set up as the second product in the AccuControl Configuration. Scroll down for 2nd product Be sure you have the serial numbers of the Field-IQ modules so that you select the correct module for the NH3 and for the NutriSphere.
  • Page 31 Pro 700 AccuControl Setup for NH3 plus Liquid PWM Control Page 2 of 2nd Prod Drive Setup Set up page as shown. Be sure the Drive R1 SN is for the module that is connected to the NutriSphere NH3 liquid. Flowmeter cal for SureFire 0.8 to 1.6 GPM flowme- ter is 22710 pul/gal.
  • Page 32 Pro 700 AccuControl Setup for Liquid PWM Control (Use these screens if the liquid is the only product controlled by AccuControl) Your system may vary from the screens shown here. See the AFS Setup & AccuControl Rate Controller Software Operating Guide for additional Operation information about configuring your system.
  • Page 33 AccuControl Setup for Liquid 10. Liquid Drive Setup Toolbox > AccuControl > Liquid Drive A. Select Liquid Drive (Yes) B. Press ‘Setup’ C. Assign Liquid Drive Serial Numbers D. Select Drive Type (PWM) E. Select Master Valve Type (NO) F. Select Pump Disarm (No) G.
  • Page 34: Create A Layout, Valve Calibration

    Create A Layout (sample) Go to Toolbox>Layout Select Current Layout and then select New. Name the Layout. Under Run Screen select a screen. In the white boxes consider adding the following items to a Run Screen:  AccuControl Speed  Master Control ...
  • Page 35: Product Setup, Layer Assignment, Work Condition > Control

    Pro 700 & AccuControl Operation for Liquid Application To start applying product (these are not necessarily all the setup you will need) Go to Toolbox>AccuCtrl>Default Speed Enter a default speed. The applicator will default to this speed if all ground speed sources are lost. The Master Apply button may need to be cycled twice to start the application.
  • Page 36: Setup Screenshots-Run Screen, Valve Cal, Liquid Drive Setup, More

    Possible Run Screen Layout Start with these Valve Cal settings Work Condition > Valve Cal > for system with 2 sections Advanced Calibration To use default AccuCtrl speed, turn Radar off. Screen showing Flow Error Timeout set to 45 sec Toolbox >...
  • Page 37: Faqs, Operating Tips, Troubleshooting Tips

    Frequently Asked Questions (FAQ), Operating Tips, and Troubleshooting Tips for SureFire Catalyst System with Pro 700 AccuControl 1. Which metering tube should I use? For most application scenarios using NutriSphere N NH3 with a rate of 32 oz/acre on 30” rows, the purple tube will be used.
  • Page 38 8. What software/firmware versions should I be running? The latest. Check with your Case dealer to see what the current versions are. It is necessary to update the display software, the AccuControl software, and the Field-IQ firmware, along with any other features you are using.
  • Page 39: Row Flow And Pump Output Chart

    10. Where can I get more information on operating the Pro 700 with AccuControl? See the Case IH AFS AFS Pro 700 AccuControl Rate Controller Software Guide and the AFS Pro 700 Display Software Operating Guide or the Quick Reference Cards for these (available on the web or from your Case IH dealer).
  • Page 40: Troubleshooting

    Electric Pump Won’t Run Two Control Signal LED’s EPD Status Lights Trouble- Signal shooting Status LED Status Description Troubleshooting Steps Status LED On Steady Power input is good No Problem, and PWM input Signal Typical operating is detected condition. Power Supply To Pump(s) Steady Blink Power input is good Typical ‘Off’...
  • Page 41 Electric pump will not turn on Trouble- shooting EPD flashing 4 times 1. Find the EPD (electric pump driver) shown above. Should have a steady blinking light in the middle when pump should be off. If Status LED is flashing 4 times, then pausing, EPD has tripped due to low voltage condition.
  • Page 42: Important Setup And Troubleshooting Procedures

    Setup and Troubleshooting the Pro 700 AccuControl Liquid PWM System (aka Intellivew IV Intellirate) Note to SureFire people: The Default speed setting that works on our test stand does not work when the tractor is not moving when the Pro 700 is plugged into a tractor that has Radar, Wheel, or GPS speed capability. This makes testing the system in a Run mode impossible without driving the tractor.
  • Page 43: Application Rate Fluctuates, Slow Getting To Target Rate

    Application Rate & Flow Troubleshooting Application Rate Fluctuates Trouble- Due to the very low application rate used on this system, pump speed changes must shooting be made very slowly since even small changes in pump speed will result in a relatively large change in flow.
  • Page 44: Maintenance & Parts

    Recommended Care and Maintenance Winterization Maintenance & Parts SureFire recommends flushing your product pump and complete system with adequate amounts of water first. Next, use RV antifreeze to winterize your system by pumping an adequate amount through all components. At the beginning of the next season, begin with water to verify the system is in working order with no leaks.