Advertisement
Please read this Owner's Manual carefully before installation and use. Save this manual.
The SimpliSafe Wireless Smoke/CO Detector (CA002) is a combined photoelectric Smoke Detector and Carbon Monoxide Detector (referred to in this Owner's Manual as the "Smoke/CO Detector").
The Smoke/CO Detector is designed to sense smoke that comes into the detector chamber and gives early warning of developing fires with an alarm sound from its built-in siren. The built-in wireless transmitter also causes your SimpliSafe Base Station siren to sound.
These sirens can provide precious time to escape before a fire spreads. However, such pre-warning of fire is only possible if the Smoke/CO Detector is located, installed and maintained properly as described in this Owner's Manual.
The Smoke/CO Detector also monitors low battery and sensor malfunctions.
These trouble conditions will cause an audible chirp from the Smoke/CO Detector as described in Section "Usage, Operation and Operating Modes'' below.
The Smoke/CO Detector also monitors the level of CO gas in your home and gives early warning when a potentially dangerous level exists. It does not detect any other gas.
If a dangerous concentration of CO is detected, the red light on the front of the detector turns on and flashes four times, and an internal siren sounds (4 loud beeps followed by a pause). The CO detector also transmits an alarm signal to the Base Station.
The alarm automatically resets when CO is no longer detected.
The Smoke/CO Detector also monitors low battery, wall tamper and sensor end-of-life conditions. These trouble codes are NOT transmitted to the Base Station. You will hear and see them coming from the Smoke/CO Detector.
The SimpliSafe Smoke/CO Detector is intended only for residential indoor applications and other areas approved by an Authority Having Jurisdiction (AHJ), which in many jurisdictions may be your local fire department or fire marshall. It is not intended for use in commercial applications.
ELECTRICAL SHOCK HAZARD.
Installation
The Smoke/CO Detector is intended for Residential USE ONLY and is not to be used in a MOBILE HOME or COMMERCIAL application(s).
This product is intended for use in ordinary indoor locations of family living units. It is not designed to measure compliance with Occupational Safety and Health Administration (OSHA), commercial, or industrial standards. It is not suitable for installation in hazardous locations as defined in the National Electric Code.
The installation of this device should not be used as a substitute for proper installation, use and maintenance of fuel burning appliances, including appropriate ventilation and exhaust systems. It does not prevent CO from occurring, nor can it solve an existing CO problem.
This device is designed to protect individuals from acute effects of carbon monoxide exposure. It may not fully safeguard individuals with specific medical conditions. If in doubt, consult a medical practitioner. Individuals with medical problems may consider using warning devices which provide audible and visual signals for carbon monoxide concentrations under 30 PPM.
This carbon monoxide alarm requires a continuous supply of electrical power. It will not work without power.
This carbon monoxide alarm has not been investigated for carbon monoxide detection below 70 PPM.
Never remove the battery from the Smoke/CO Detector to stop a nuisance alarm. Open a window or fan the air around the Smoke/ CO Detector to get rid of the smoke. The detector will turn itself off when the smoke is gone. If nuisance alarms persist, attempt to clean the Smoke/ CO Detector as described in this Owner's Manual, or relocate it to a better location.
Not suitable for installation in areas where air velocities exceed 300 meters/minute (985 FPM)
Do not stand close to the Smoke/CO Detector when the alarm is sounding. The alarm is loud in order to wake you in an emergency. Too much exposure to the horn at close range may be harmful to your hearing.
Do not connect the Smoke/CO Detector to any other alarm or auxiliary device. Connecting anything else to this detector will keep it from working properly.
Never use an open flame of any kind to test your detector. You may damage it as well as your home. The built-in test switch accurately tests all functions as required by Underwriters' Laboratories.
When you are not testing the unit and the alarm siren sounds, the detector is warning of a possible serious situation, which requires your immediate attention.
This device contains a wireless transmitter that can actuate a remote audible siren. When used in a typical single level or multilevel dwelling, or in apartment buildings where adjacent apartments may have similar systems, it is possible that interference for another system could prohibit the remote siren from sounding in the event of an alarm. Never rely solely on the remote siren for notification of an alarm. Always make sure that the internal siren in the Smoke/CO Detector can be heard from all bedrooms and living areas.
Actuation of your CO alarm indicates the presence of carbon monoxide which can KILL YOU. If the alarm signal sounds:
Smoke detectors CANNOT provide warnings for fires resulting from explosions, smoking in bed or other furniture, ignition of flammable liquids, vapors and gasses, children playing with matches or lighters.
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows:
A smoke alarm or detector installed in each separate sleeping room, outside of each separate sleeping area, in the immediate vicinity of the sleeping rooms, and on each level of the dwelling unit, including basements and heat or smoke detectors in living rooms, dining rooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, and attached garages.
This carbon monoxide alarm is designed to detect carbon monoxide from ANY source of combustion. It is NOT designed to detect fire, or any other gas.
The CO alarm will only indicate the presence of carbon monoxide at the sensor. Carbon monoxide may be present in other areas.
This Smoke/CO Detector comes with cover latches that will prevent the Smoke/CO Detector cover from closing if the batteries are not installed. This tells you that the Smoke/CO Detector will not work until a new battery is properly installed.
Continuous exposure to the high sound level of this alarm over an extended period of time may cause hearing loss.
You should never disable the unit to avoid nuisance alarms.
Instead, relocate the detector to a better location.
Always refer to your national and local codes before beginning any installation. Instructions for the State of California are detailed in Important Warning Statements Section.
The Smoke/CO Detector should be installed in accordance with the NFPA 72 - National Fire Alarm and Signaling Code created by the National Fire Protection Association (NFPA).
The Smoke/CO Detector must be replaced within 10 years of the date of manufacture. This date can be found on the label on the back of the device.
i. NFPA 72, Section 29.8.1:
Required Detection: where required by applicable laws, codes, or standard(s) for a specific type of occupancy, approved single and multiple station smoke alarms shall be installed as follows
Where the area addressed in (2) is separate from the adjacent living areas by a door, a smoke alarm shall be installed in the area between the door and the sleeping rooms, and additional alarms shall be installed on the living area side of the door as specified.
In addition to the requirements of (1) - (3), where the interior floor area for a given level of a dwelling unit, excluding garage areas, is greater than 1000 ft2, smoke alarms shall be installed as below
All points on the ceiling shall have a smoke alarm within a distance of 30ft travel distance or shall have an equivalent of one smoke alarm per 500 ft2 of floor area
Where dwelling units include great rooms or vaulted/cathedral ceilings extending over multiple floors, smoke alarms located on the upper floor that are intended to protect the aforementioned area shall be permitted to be considered as part of the lower floor(s) protection scheme used to meet these requirements.
NFPA 72 29.11.3 contains the following requirements:
Peaked Ceilings. Smoke alarms mounted on a peaked ceiling shall be located within 36 inches horizontally of the peak, but not closer than 4 inches vertically to the peak
Sloped Ceilings. Smoke alarms mounted on a sloped ceiling have a rise greater than 1ft in 8ft horizontally shall be located within 36 inches of the high side of the ceiling, but not closer than 4 inches from the adjoining wall surface
Wall Mounting. Smoke alarms mounted on walls shall be located not farther than 12 inches from the adjoining ceiling surface
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows:
A smoke alarm or detector installed in each separate sleeping room, outside of each separate sleeping area, in the immediate vicinity of the sleeping rooms, and on each level of the dwelling unit, including basements and heat or smoke detectors in living rooms, dining rooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, and attached garages.
For information about establishing a household emergency evacuation plan, please refer to FIRE PREVENTION AND ESCAPE Section of this Owner's Manual entitled.
Recommended locations (single sleeping area)
Recommended locations (multiple sleeping areas)
Recommended locations (multi-floor residence)
Install the sensor in the center of the ceiling
To avoid false alarms and optimize detection of real alarms, do not install a Smoke/CO Detector:
You should never disable the unit to avoid nuisance alarms. Instead, relocate the detector to a better location.
Never remove the battery from the Smoke/CO Detector to stop a nuisance alarm. Open a window or fan the air around the Smoke/ CO Detector to get rid of the smoke. The detector will turn itself off when the smoke is gone. If nuisance alarms persist, attempt to clean the Smoke/ CO Detector as described in this Owner's Manual, or relocate it to a better location.
Not suitable for installation in areas where air velocities exceed 300 meters/minute (985 FPM)
Do not stand close to the Smoke/CO Detector when the alarm is sounding. The alarm is loud in order to wake you in an emergency. Too much exposure to the horn at close range may be harmful to your hearing.
ELECTRICAL SHOCK HAZARD. Turn off power to the area where you will install this unit at the circuit breaker or fuse box before beginning installation. Failure to turn off the power before installation may result in serious electrical shock, injury or death.
ELECTRICAL SHOCK HAZARD. Do not restore power until all detectors are completely installed. Restoring power before installation is complete may result in serious electrical shock, injury or death.
Install the Smoke/CO Detector on a ceiling or wall:
NOTE: After you install the Smoke/CO Detector and whenever you change its battery, you must test it according to the instructions below to make sure it is functioning correctly.
Do not connect the Smoke/CO Detector to any other alarm or auxiliary device. Connecting anything else to this detector will keep it from working properly.
This Smoke/CO Detector comes with cover latches that will prevent the Smoke/CO Detector cover from closing if the batteries are not installed. This tells you that the Smoke/CO Detector will not work until a new battery is properly installed.
NOTE: Use only Panasonic or Duracell CR123A batteries. This Smoke/CO detector may not operate properly with other kinds of batteries.
This section describes the basic steps for pairing the Smoke/CO Detector to the Base Station.
To determine a strong communication path with the Base Station, this verification test should be performed in accordance with NFPA 72 inspection, testing and maintenance requirements found in Regular Maintenance Section of this Manual.
This Smoke/CO Detector CAN ONLY BE interconnected with other SimpliSafe alarms by connecting it to a SimpliSafe Base Station as specified in the Compatible Equipment Table below. This Smoke/CO Detector is not intended to be connected to any non-SimpliSafe devices or systems and you should not attempt to do so. Attempting to connect the Smoke/CO Detector to non-SimpliSafe devices or systems may result in nuisance alarms, failure to alarm or damage to one or all of the devices in the non-SimpliSafe system.
CA 002 Compatible Equipment | ||
Description | Manufacturer | Model Number |
Base Station | SimpliSafe | SSBS3 |
Before you test the Smoke/CO detector, make sure the detector does not have low batteries.
If the Smoke/CO detector has low batteries, it will fail the self-test. Test your Smoke/CO Detector weekly by pressing the test button (the white button on the front of the sensor) for 10 seconds. The sensor's siren will sound (3 beeps, pause, 4 beeps, pause, 4 beeps) and the light will flash at similar intervals.
If this detector is paired to a Base Station, the Base Station will also sound during this test if no issues are found.
If the Smoke/CO Detector and Base Station do not sound, the detector either has a low battery, or the detector is malfunctioning. Replace the batteries in the detector, and repeat the test.
This is the only way to make sure that the Smoke/CO Detector unit is working properly. If the unit fails to test properly with new batteries, have it replaced immediately.
Continuous exposure to the high sound level of this alarm over an extended period of time may cause hearing loss.
Never use an open flame of any kind to test your detector. You may damage it as well as your home. The built-in test switch accurately tests all functions as required by Underwriters' Laboratories.
When you are not testing the unit and the alarm siren sounds, the detector is a warning of a possible serious situation, which requires your immediate attention.
Go/No-Go Field Test: Please use Home Safeguard Model 25S UL Listed aerosol Smoke/CO detector tester, following the instructions listed on the canister.
Press the "Test/Silence" button (the white button on the front of the detector) to temporarily quiet an alarm for up to 10 minutes. If smoke is still present around the Smoke/CO Detector after 10 minutes of silence, the unit will re-alarm.
The LED light on the front of the Smoke/CO Detector indicates the operating mode of the unit:
Red LED blinks 3 times rapidly: the Smoke/CO Detector has sensed a potentially dangerous level of smoke and is in smoke alarm mode. The buzzer and alarm siren will also sound. Please follow the "in case of fire" instructions.
Green LED blinks about once per minute: the Smoke/CO Detector is functioning normally.
Yellow LED blinks AND chirps once per minute: the Smoke/CO Detector battery is low. This low battery warning signal should last for up to 30 days, but you should install two new CR123A 3V lithium batteries immediately.
Yellow LED blinks once and chirps 2 times every minute: this indicates the Smoke/CO Detector is in low sensitivity and needs to be cleaned.
Yellow LED blinks twice and chirps 2 times every minute: this indicates the Smoke/CO Detector is in high sensitivity and needs to be cleaned.
Yellow LED blinks once and chirps 3 times every minute: this indicates the Smoke/CO Detector is no longer operating within its intended sensitivity and must be replaced.
If CO alarm signal sounds on the Smoke/CO Detector:
Green LED Flashes: the Smoke/CO Detector is turning on.
Green LED flashes once every 50 seconds: the Smoke/CO Detector is in Standby which means the unit is receiving power and also indicates it is functioning properly.
Red LED light flashes rapidly and the buzzer sounds loudly with repeating 4 quick beeps and pauses for 5 seconds and then 4 quick beeps: the Smoke/ CO Detector is in CO Alarm Mode. After 4 minutes of an alarm, the pause will increase to 60 seconds.
Yellow LED blinks AND chirps once per minute: the Smoke/CO Detector battery is low. This low battery warning signal should last for up to 30 days, but you should install two new CR123A 3V lithium batteries immediately.
Yellow LED flashes two times a minute and buzzer chirps once a minute: this indicates the Smoke/CO Detector is malfunctioning and needs to be replaced.
Yellow LED flashes four times a minute and buzzer chirps once a minute: this indicates the detector is reaching the end of its useful life (10 years after the unit was manufactured).
Tamper mode: the yellow LED flashes twice every 4 seconds until the Smoke/ CO Detector is mounted back to the bracket properly.
Wireless smoke detectors cannot provide total protection of life or property and are not a substitute for insurance. All wireless smoke detectors are subject to possible compromise or failure-to-warn for a variety of reasons. For example:
Wireless CO detectors provide early warning of the presence of CO, usually before a healthy adult would experience symptoms. This early warning is possible only if your Smoke/CO Detector is located, installed, and maintained as described in this Owner's Manual.
Because CO is a cumulative poison, long-term exposures to low levels may cause symptoms, as well as short-term exposures to high levels. This unit has a time-weighted alarm. The higher the level of CO present, the sooner the alarm will be triggered.
This Smoke/CO Detector can only warn you of the presence of CO. It does not prevent CO from occurring, nor can it solve an existing CO problem. If your unit has alarmed and you've provided ventilation by leaving your windows and doors open, the CO buildup may have dissipated by the time help responds. Although your problem may appear to be temporarily solved, it is crucial that the source of the CO is determined and that the appropriate repairs are made.
Wireless CO detectors have limitations. Like any other electronic device, CO detectors are not foolproof. CO detectors have a limited operational life.
You must test your Smoke/CO Detector weekly, because it could fail to operate at any time.
If your Smoke/CO Detector fails to test properly, or if its self-diagnostic test reveals a malfunction, immediately have the unit replaced. This detector will not monitor CO levels while in a trouble condition.
The Smoke/CO Detector can only sense CO that reaches the unit's sensor. It is possible that CO may be present in other areas without reaching the alarm. The rate and ability with which CO reaches the alarm may be affected by:
For these reasons, we recommend you provide complete coverage by placing a Smoke/CO Detector on every level of the home.
The purpose of an early warning smoke detector is to detect the presence of fire in its early stages and sound an alarm giving the occupants time to exit the premises safely. No detection device can protect life in all situations. Therefore, safeguards should be taken to avoid potentially dangerous situations as follows:
In the event of a fire, you should do the following:
Use the following instructions to create an emergency evacuation plan:
Smoke detectors CANNOT provide warnings for fires resulting from explosions, smoking in bed or other furniture, ignition of flammable liquids, vapors and gasses, children playing with matches or lighters.
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
This device contains a wireless transmitter that can actuate a remote audible siren. When used in a typical single level or multilevel dwelling, or in apartment buildings where adjacent apartments may have similar systems, it is possible that interference for another system could prohibit the remote siren from sounding in the event of an alarm. Never rely solely on the remote siren for notification of an alarm. Always make sure that the internal siren in the Smoke/CO detector can be heard from all bedrooms and living areas.
Carbon monoxide is a colorless, odorless, and tasteless poison gas that can be fatal when inhaled. CO inhibits the blood's capacity to carry oxygen.
Periodically review this Owner's Manual and discuss your CO alarm emergency procedure with all members of your family.
The following common symptoms are related to CO poisoning and should be discussed with ALL members of the household:
If you experience even mild symptoms of CO poisoning, consult your doctor immediately.
Excessive spillage or reverse venting of fuel burning appliances caused by:
Actuation of your Smoke/CO Detector indicates the presence of carbon monoxide which can KILL YOU. If the alarm signal sounds:
Note any combustion equipment not inspected by the technician and consult the manufacturers' instructions, or contact the manufacturers directly for more information about CO safety and this equipment. Make sure that motor vehicles are not, and have not been, operating in an attached garage or adjacent to the residence.
To keep your Smoke/CO Detector in good working order, remove from mounting bracket, remove battery cover and vacuum the dust off the sensing chamber at least once a month.
If the Smoke/CO Detector is defective in any way, do not tamper with the unit. Contact SimpliSafe at 1-888-910-1215
Power Source: Required batteries | 2x Panasonic CR123A 3V lithium battery |
Smoke Sensor | Photoelectric 1.60 to 2.60%/ ft obscuration sensitivity |
CO Sensor | Electrochemical |
Audible alarm | Over 85dB at 3m temporal pattern |
Sensitivity | Per UL217 and UL 2034 |
Dimensions | 12cm diameter x 4.5cm |
Weight | 0.6 lbs |
Operating Temperature Operating Relative humidity | 40 to 100°F (4.4 to 37.8°C) 10 to 95% non-condensing |
CO Alarm response times | 70 PPM = 60-240 min. 150 PPM = 10-50 min. 400 PPM = 4-15 min. |
Agency Listings | UL 217 8th (ETL Listed) UL 2034 4th (ETL Listed) |
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the CA002 and is the answer not in the manual?
Questions and answers