4.10.1 Product conformity ..................4.10.2 Dimensions ....................4.10.3 Temperature detection................Scope of Delivery ......................Condition-monitoring sensor CMSVT38 ..............Preparations for installation and commissioning............Installation ........................Mechanical Installation.................... 7.1.1 General Information for the Installation of Condition-Monitoring Sensors 7.1.2 Cable Routing ...................
Page 3
Fritz Kübler GmbH Table of contents Commissioning ....................... Status LEDs ......................Settings ..........................Functions and properties that can be set..............Setting via FDT/IODD ..................... 10 Maintenance ........................10.1 Reassembly ......................11 Software-Supported IO-Link Parameterization ............12 IO-Link-Parameter ......................12.1 IO-Link-Parameter ....................12.1.1 General Parameters .................
3 General information Fritz Kübler GmbH 3 General information Read this document carefully before working with the product. It guides you or the technical personnel of the machine and plant manufacturer or operator in the safe assembly, installation, commissioning, and operation of the product.
Fritz Kübler GmbH 3 General information 3.2 Symbols used/classification of warnings and safety instructions Classification: DANGER This symbol, in connection with the signal word DANGER, warns of an imminent danger to the life and health of persons. Failure to observe this safety instruction will result in death or serious damage to health.
3 General information Fritz Kübler GmbH The storage must: • be free of any compressive stress to prevent damage or deformation. • be dry, dust-free, and in accordance with the technical data, see chapter "Technical Data [} 12]” or "Applicable documents [} 8]”. 3.6 Applicable documents Technical Data All technical data, as well as mechanical and electrical characteristics, can be found in the data...
Due to different electrical operating conditions in the sensor, the measured temperature may differ from the ambient temperature. 4.2 Intended Use The CMSVT38 series condition-monitoring sensors monitor temperature and vibration of machines. The process values are output by the device via IO-Link.
Fritz Kübler GmbH 4.3 Examples of Applications Combination CMSVT38 with signal column and IO-Link master In IO-Link mode, the vibration sensor CMSVT38 can be connected to an Ethernet network via an IO-Link master. By communicating with the controller, the IO-Link signal column ST40, for example, can signal the detected statuses on site again.
IO-Link, which output the oscillation acceleration or the oscillation speed depending on the parameterization. The vibration acceleration or vibration speed can be output as an RMS value or a peak-to-peak value. Additionally, the vector sum is output as a 16-bit telegram. Fig. 1: CMSVT38 Measuring axes IMG-ID: 404805515 D000085279.0002 - 01...
4 Product description Fritz Kübler GmbH 4.10 Technical Data NOTICE Technical Data All technical data, as well as mechanical and electrical characteristics, can be found in the data sheets of the corresponding product versions, or in the corresponding bid / customer drawing of the product for specially-designed models.
Fritz Kübler GmbH 5 Scope of Delivery 5 Scope of Delivery 5.1 Condition-monitoring sensor CMSVT38 The scope of delivery includes: • Condition-monitoring sensor • Supplement with QR code and link to https://www.kuebler.com/ D000085279.0002 - 01 EN | 13...
6 Preparations for installation and commissioning Fritz Kübler GmbH 6 Preparations for installation and commissioning Please observe the following instructions before beginning to install the condition-monitoring sensor. ATTENTION Damage to the product due to transport or storage Product failure, malfunction, reduction of the product service life. •...
Fritz Kübler GmbH 7 Installation 7 Installation 7.1 Mechanical Installation ATTENTION Damage to the product due to transport or storage Product failure, malfunction, reduction of the product service life. • Check the packaging and the product for possible damage. • Do not use or operate the product in the event of visible damage. •...
7 Installation Fritz Kübler GmbH • Separate the wiring in line groups such as motor and power supply lines as well as signal and data lines. • Route the signal and data cables as closely as possible to ground surfaces (support beams, metal rails, cabinet panels) and not parallel to motor and power supply lines or other lines with a high level of interference.
Fritz Kübler GmbH 7 Installation 7.2 Electrical Installation 7.2.1 General Instructions for the Connection ATTENTION Destruction of the device Before plugging or disconnecting the signal line, always disconnect the supply voltage and secure it against being switched on again. NOTICE General safety instructions Make sure that the entire system is de-energized during electrical installation.
7 Installation Fritz Kübler GmbH IMG-ID: 9007199375147403 Order code 8.0000.4G06.0312 8.0000.4G06.0718 Material Spring steel, galvanized Shield diameter 3.0 … 12.0 mm 7.0 … 18.0 mm Kübler offers a wide range of connection cables in various designs and lengths, see www.kuebler.com/anschlusstechnik. Kübler provides various solutions for EMC-compliant installation, e.g. shielding clamps for the control cabinet, see www.kuebler.com/zubehoer.
Fritz Kübler GmbH 7 Installation 7.2.4 Sensor Terminal Assignment • Connect the coupling of the connecting cable to the plug of the sensor. • Connect the open end of the connecting cable to the power source and/or the evaluation devices. Interface M12 connector, male pin, 4-pin, A-coded Signal:...
8 Commissioning Fritz Kübler GmbH 8 Commissioning After connecting and switching on the supply voltage, the device is automatically operational. 8.1 Status LEDs Fig. 4: Status LED IMG-ID: 404421899 Display Meaning PWR/ Green Device ready for operation Green, flashing IO-Link communication active Out 1 Yellow Switching status switching output 1 (parameterizable)
Fritz Kübler GmbH 9 Settings 9 Settings 9.1 Functions and properties that can be set Parameter Meaning Reset device The device is restarted. The communication is temporarily interrupted. The measured maximum values of the vibration are reset. Reset application The application-specific parameters are reset. Communication is not interrupted.
Page 22
9 Settings Fritz Kübler GmbH Parameter Meaning ISO 10816-3 The ISO 10816-3 standard specifies the exact vibration limits for industrial machines. The vibration limit values are used to assess industrial machines with a power of ≥15 kW and a rated speed of 120 rpm.
Fritz Kübler GmbH 9 Settings Parameter Meaning Time slots The effective values of the vibration speed, acceleration or peak-to- peak values are determined and output over the set period of time. The following time windows for vibration detection can be defined: •...
9 Settings Fritz Kübler GmbH 24 V DC Fig. 5: Setting of switching outputs using IO-Link master IMG-ID: 407225867 1 Vibration sensor 2 IO-Link Master USB 3 Application 4 Adapter cable 5 USB interface 6 Laptop with software Connection The vibration sensor ① is or will be disconnected from the application ③. The IO-Link Master USB ②...
Fritz Kübler GmbH 10 Maintenance 10 Maintenance Troubleshooting If the device does not function as expected, check whether there is ambient interference. If there is no ambient interference, check the device connectors for errors. If none are present, there is a device fault. In this case, take the device out of service and replace it with a new device of the same type.
11 Software-Supported IO-Link Parameterization Fritz Kübler GmbH 11 Software-Supported IO-Link Parameterization The ports of the IO-Link master can be configured in IO-Link mode (IOL) or in Standard IO mode (SIO). When a port is configured in SiO mode, the IO-Link master on that port behaves like a normal digital input.
Fritz Kübler GmbH 12 IO-Link-Parameter 12 IO-Link-Parameter 12.1 IO-Link-Parameter 12.1.1 General Parameters Parameter Contents Vendor ID Vendor Name Fritz Kuebler GmbH Device ID 0x700011 IO-Link version Bitrate COM3 Minimum cycle time 1.3 ms Supports SIO True M-Sequence Capability PREOPERATE = TYPE_1_2 with 2 octet data on request OPERATE = TYPE_2_V with 2 octet data on request ISDU supported Block parameters...
Page 28
12 IO-Link-Parameter Fritz Kübler GmbH Name Byte.Bit Subindex Data Value Description offset length access Type supported X-axis True UInteger 0…65535 Resolution in 0.01 g or mm/s Y-axis True UInteger 0…65535 Resolution in 0.01 g or mm/s Z-axis True UInteger 0…65535 Resolution in 0.01 g or mm/s Magnitude True...
Fritz Kübler GmbH 12 IO-Link-Parameter 12.1.3 Standard Parameters Name Index Index Sub- Sub- Subindex Acces Byte.Bit Data Value De- Description (dec) (hex) index index access offset length Type fault (dec.) (hex.) supported Minimum cycle True read UInteger time IO-Link Version True read UInteger...
Page 30
12 IO-Link-Parameter Fritz Kübler GmbH Name Index Index Sub- Sub- Subindex Acces Byte.Bit Data Value De- Description (dec) (hex) index index access offset length Type fault (dec.) (hex.) supported Local user False Read/ Boolean false/ Block device access interface block write true Manufacturer...
Fritz Kübler GmbH 12 IO-Link-Parameter 12.1.4 Parameter Name Index Index Subin Subin Subindex Acces Byte. Data Value Default Description (dec) (hex) access length Type supported offset (dec.) (hex.) Function tag 25 0x19 True read/ String NaN... The parameter contains the write description of the function of a profile device in an...
Page 32
12 IO-Link-Parameter Fritz Kübler GmbH Name Index Index Subin Subin Subindex Acces Byte. Data Value Default Description (dec) (hex) access length Type supported offset (dec.) (hex.) Group 3 flexible Group 4 rigid Group 4 flexible Temperature manual X-axis pre- 0x 104 1 True read/ 14.0...
Page 33
Fritz Kübler GmbH 12 IO-Link-Parameter Name Index Index Subin Subin Subindex Acces Byte. Data Value Default Description (dec) (hex) access length Type supported offset (dec.) (hex.) Operating 0x 106 0 True read UInteger NaN... Time in hours during which hours the device is in operation counter Process data...
Page 34
12 IO-Link-Parameter Fritz Kübler GmbH Name Index Index Subin Subin Subindex Acces Byte. Data Value Default Description (dec) (hex) access length Type supported offset (dec.) (hex.) Self-test Self-test, 0x 10B 0 True read UInteger 0…2 Result of the self-test result Device not tested Device is not in order Device is in order...
Page 35
Fritz Kübler GmbH 12 IO-Link-Parameter Name Index Index Subin Subin Subindex Acces Byte. Data Value Default Description (dec) (hex) access length Type supported offset (dec.) (hex.) Output 2 0x 110 0 True read/ UInteger 0…1 Configuration of the second Configuratio write output Alarm...
13 Disposal Fritz Kübler GmbH 13 Disposal Always dispose of unusable or irreparable products in an environmentally friendly manner in accordance with country-specific requirements and valid waste disposal regulations. We are happy to help you with the disposal of the products. See chapter Contact [} 37].
Fritz Kübler GmbH 14 Contact 14 Contact If you want to get in touch with us: Technical advice For technical advice, analysis or support during installation, Kübler is available directly on site with its global application team. Support International (English-speaking) +49 7720 3903 849 support@kuebler.com Kübler...
Glossary Fritz Kübler GmbH Glossary BOOL SINT Data type, a BOOLEAN, stands for a Data type, short integer, an operand of truth value that can be either true or the data type SINT (Short INT) has a false. length of 8 bits and consists of two components: a sign and a numerical value.