Dutypoint ResiPOWER RK Installation And Operation Manual

Three phase ups, 3:3&3:1 10-20kva ups 3:3 30-40kva ups

Advertisement

Quick Links

ResiPOWER RK Three Phase UPS
Installation and Operation Manual
3:3&3:1 10-20kVA UPS
3:3 30-40kVA UPS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ResiPOWER RK and is the answer not in the manual?

Questions and answers

Summary of Contents for Dutypoint ResiPOWER RK

  • Page 1 ResiPOWER RK Three Phase UPS Installation and Operation Manual 3:3&3:1 10-20kVA UPS 3:3 30-40kVA UPS...
  • Page 2: Table Of Contents

    Table of Contents 1. Preface ........................1 2. Important Safety Information..................1 3. Function Description ....................1 3.1 UPS Block Diagram .................... 1 3.2 UPS Outlook View ....................2 4. Installation and Wiring ....................3 4.1 Storage and Installation Environment ..............3 4.2 Unpacking, Removing and Fixing UPS ...............
  • Page 3: Preface

    1. Preface We thank you for the trust in selecting our UPS. This equipment has been tested and comply with the European Community directives for Class I electrical device and is authorized to use the CE marking. The purpose of this manual is to introduce the operating principles of the UPS and to provide instructions for its safe operation.
  • Page 4: Ups Outlook View

    3.2 UPS Outlook View 10-15-20-30-40kVA Side View 10-15-20kVA with Batteries 30-40kVA Front View 10-15-20kVA Front View (1) Control Panel with Colorful LCD Touch Screen (3) Caster Wheels for Easy Handling (2) Ventilation Grille (4) Battery Tray 10-15-20kVA Rear View Please find the detail descriptions of above items on section 4-6.
  • Page 5: Installation And Wiring

    30-40kVA Rear View (1) Communication Slot 1 (2) Communication Slot 2 (3) Dry Contacts (4) External Battery Temperature Connector (5) RS-232 Port for Setting Software (6) Parallel Communication Ports(Option) (7) Communication Selector for Service Only (8) USB Port for Service Only (9) Terminal Resistor Setting Switch for Parallel Communication...
  • Page 6: Unpacking, Removing And Fixing Ups

    4.2 Unpacking, Removing and Fixing UPS Inspect the UPS upon receipt. The packaging is robust, but accidents and damage may still occur during shipment. Notify the forwarder and dealer if there is damage. This section describes the unpacking and removing processes for wheel type. STEP 1&...
  • Page 7 Cross Jumper 4.4.2 3:1 UPS Power Cables Connection The drawing below shows the cables connections specifically for 3:1 UPS (3 phase input and 1 phase output) only. Only specific 10kVA & 20kVA UPS model are allows converting from 3: 3 to 3:1 UPS.
  • Page 8 4.4.6 Electrical System Connections witch various UPS configurations UPS with single input UPS with dual inputs and isolation transformer (Option) 3P+N L oad 3P N L oad UPS with single input and isolation transformer 3P N Load 3P N L oad UPS with dual inputs (Option) 3P N 3P N...
  • Page 9: Auxiliary Power Supply Control Switch And Button

    UPS in parallel with output transformer Please do not use separate output transformer for each UPS. A common output transformer is recommended. Load Load 4.5 Auxiliary Power Supply Control Switch and Button  AC Power This is auxiliary power switch for the working power.
  • Page 10: Ups Parallel Connections (Option)

     Paral-1&Paral-2—parallel communication port Parallel communication cables are required to connect UPS each other when UPSs operation in parallel. Please refer to section 4.7for detail connections.  H↔U—communication selector This switch is to select HMI or USB port. Please ensure this switch on “H” position for ensure HMI port is workable.
  • Page 11 Recommended 1+1 parallel system configuration Recommended N+1 parallel for single input system configuration Parallel Parallel Communication Communication Cables Cables 1+1 parallel, Single Input 1+1 parallel, Dual Inputs(Option) Recommended N+1 parallel for dual inputs system configuration Parallel Communication Cables...
  • Page 12: Operation Descriptions

    5. Operation Descriptions 5.1 Operating Mode The UPS provides the following operating modes:  Normal Mode(Online Mode) In Normal mode, grid power is passed through Rectifier then used to charge the battery and provide power through the Inverter simultaneously. Different output voltages settings can be set in VFI mode. The three options are 380/220V, 400/230V and 415/240V. These can be fine-tuned by ±8V.
  • Page 13 5.4.1.4 Return to Mimic Display. Wait for few minutes, the rectifier 5.4.1.5 Close the battery switch/fuses to connect the batteries after will be started. rectifier has been turned on. 5.4.1.6 The inverter will be started and supply output voltage. 5.4.1.7 Close UPS Output Switch to supply the power to the load. 5.4.2 Cold Start 5.4.2.1 User can start-up UPS by battery when main input power is not available.
  • Page 14: Control Panel Operation And Function Description

    6. Control Panel Operation and Function Description Each UPS is equipped with a LCD touch panel to provide the user with a simple and intuitive user interface that is easy to learn. Please refer to below section for learn more detail information and functions of the LCD touch panel. 6.1 Screen Introduction 【A】Display current time, status and information of UPS.
  • Page 15 Force Charger on Other Recovery Backfeed Protection Signal Clear UPS Maintenance Alarm Command Battery Test. Battery Test Turn off The Battery Test. Identification Display UPS information Real Time Information Display real time measurements of input, output, bypass and battery. Monitor Maintenance Code Display the maintenance code for technician to check the status of the UPS.
  • Page 16: Output Transformer

    FV Charger voltage [V/cell] 2.000~2.550 2.250 Vbatt. Low [V/cell] 1.850 ~ 1.900 1.850 Battery Vbatt. Min [V/cell] 1.600 ~ 1.850 1.670 Battery test 2 minutes Yes / No 220 、 230 、 240 Output voltage 50 、 60 Output Output frequency Fine adjustment voltage -8 ~ 8 Input transformer...
  • Page 17 【J】Overload counter...
  • Page 18: Options

    7. Options 7.1 Hardware Setup 1. Connect to either RS-232 communication or USB communication. 2. Connect a male RS-232 connector or a USB cable* to the UPS communication port. Connect the female RS-232 connector or the other end of the USB cable to the computer. *Note: RS-232 and USB cables are optional.
  • Page 19: Troubleshooting

    8. Troubleshooting In the event of failure, the display area on the control panel will highlight the problem area in red. The “Alarm” symbol will also blink to warn that there is a problem with the UPS. Click to have an alarm list as below picture. We recommend using the following method when troubleshooting to export the event log and machine information from LCD panel to the SD card.
  • Page 20: Technical Specification

    9. Technical Specification Capacity 10 kVA 15kVA 20 kVA 10 kVA 15kVA 20 kVA 30 kVA 40 kVA Input Voltage 400V 3 Phase + N ±20% @100% load, -40% @50% load Voltage Tolerance -20%~-40% Output capacity decrease linearly according to the input voltage Frequency 40 ~ 70Hz ≧...
  • Page 21 Over 1000m above sea level, the maximum output capacity must be derated by 1% every additional 100m.
  • Page 22 192321272027001...