Xvent ATACAMA Operating And Assembly Instruction Manual

Heating and destratification unit
Table of Contents

Advertisement

Quick Links

OPERATING AND ASSEMBLY
INSTRUCTIONS FOR THE ATACAMA
HEATING AND DESTRATIFICATION UNIT
1
Version 002 – GBR (25/09/2024)
D-502-0165

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ATACAMA and is the answer not in the manual?

Questions and answers

Summary of Contents for Xvent ATACAMA

  • Page 1 OPERATING AND ASSEMBLY INSTRUCTIONS FOR THE ATACAMA HEATING AND DESTRATIFICATION UNIT Version 002 – GBR (25/09/2024) D-502-0165...
  • Page 2: Table Of Contents

    AIN DIMENSIONS AND MINIMUM WORKSPACE REQUIREMENTS FOR TACAMA UNITS 2.4................................. 8 ECHNICAL 2.4.1. Basic technical data of the Atacama heating and cooling unit ..................8 2.4.2. Basic technical data Atacama destrification unit ......................8 2.5........................9 ECHNICAL ATA OF THE...
  • Page 3 ONNECTING UNITS WITHOUT REGULATION COMMISSIONING ................................... 23 6.1. : ..................23 HECK THE FOLLOWING BEFORE STARTING FOR THE FIRST TIME 6.2................................23 CTIVATION REGULAR MAINTENANCE AND CLEANING OF THE ATACAMA UNIT ..................23 7.1............................23 EGULAR AINTENANCE 7.2............................... 24 LEANING ROCEDURE SERVICING....................................
  • Page 4: General

    1. General 1.1. Introduction This “Assembly and Operating Instructions” document is designed for the Atacama unit (hereinafter the “unit” only), which is used to heat or cool a desired space with hot or cold air. Detailed familiarity with this document is important for the unit’s proper and safe assembly and operation.
  • Page 5: Using The Unit

    1.3. Using the Unit The Atacama heating unit is designed for heating or cooling (with cold water) and filtration of air in the indoor environment (filters can be ordered as accessories) of industrial halls, warehouses, sports facilities, workshops, and smaller plants.
  • Page 6: Technical Parameters

    2. Technical Parameters 2.1. Atacama unit design - horizontal fins (ATA1-x-ECVxCL-0A0) EXHAUST ENCLOSURE EC AXIAL BRACKET WATER EXCHANGER Fig. 1 2.2. Atacama unit design - textile sleeve connection throat (ATA1-x-ECVxTH-0A0) EXHAUST ENCLOSURE EC AXIAL BRACKET WATER EXCHANGER WITH THROAT Fig. 2 EXHAUST ENCLOSURE 2.2.1.
  • Page 7: Main Dimensions And Minimum Workspace Requirements For Atacama Units

    2.3. Main dimensions and minimum workspace requirements for Atacama units MIN. INSTALLATION SPACE with condensation tray MIN. INSTALLATION SPACE with condensation tray with condensation tray Version 002 – GBR (25/09/2024) D-502-0165...
  • Page 8: Technical Data

    2.4. Technical Data Basic technical data of the Atacama heating and cooling unit 2.4.1. Tab.1 Basic technical data Atacama destrification unit 2.4.2. Tab.2 EC Declaration of Conformity - the current and full version of the EC Declaration of Conformity can be found on our website www.xvent.cz in the Atacama product documents...
  • Page 9: Technical Data Of The Water Heater

    2.5. Technical Data of the Water Heater ATA1-3-ECV1CL-0-A-0 Tab.3 ATA1-3-ECV2CL-0-A-0 Tab.4 ATA1-3-ECV3CL-0-A-0 Tab.5 Version 002 – GBR (25/09/2024) D-502-0165...
  • Page 10 Tab.6 ATA1-4-ECV1CL-0-A-0 ATA1-4-ECV2CL-0-A-0 Tab.7 ATA1-4-ECV3CL-0-A-0 Tab.8 ATA1-4-ECV4CL-0-A-0 Tab.9 Version 002 – GBR (25/09/2024) D-502-0165...
  • Page 11: Technical Data Of Water Coolers

    2.6. Technical Data of Water Coolers Operation of the cooling unit is only allowed for the ATA1-x-ECVxCL-0A0 version with the ATA- CONDENSATE-TRAY accessory ATA1-3-ECV3CL-0-A-0 Tab.10 ATA1-4-ECV3CL-0-A-0 Tab.11 ATA1-4-ECV4CL-0-A-0 Tab.12 Version 002 – GBR (25/09/2024) D-502-0165...
  • Page 12: Assembly - Assembly Of Heating Units In Their Working Position

    3. Assembly - Assembly of heating units in their working position 3.1. General information, recommendations, and safety during the Atacama unit assembly 3.1.1. Electrical safety before the unit assembly Before starting any assembly work, it is necessary to switch off the power supply to the prepared wiring for subsequent recovery of the unit.
  • Page 13: Ceiling Assembly

    3.3. Ceiling Assembly O nly the ATA1-x-ECVxCL-0A0 (without assembly of the ATA-CONDENSATE-TRAY accessories for cooling) and ATA1-x-ECSODI-0A0 versions 3.4. Wall Assembly Only the ATA1-x-ECVxCL-0A0 (with the option of assembling the ATA-CONDENSATE-TRAY accessories for cooling) and ATA1-x-ECVxTH-0A0 versions 3.5. Textile Sleeve Assembly The textile sleeve may only be assembled in the ATA1-x-ECVxTH-0A0 unit version It is possible to assemble a textile sleeve with a spout to the unit: o Nozzles - greater range of warm air flow.
  • Page 14 Assemble the textile sleeve on the unit according to the separate instructions included with the textile sleeve All the assembly accessories required for assembly are included with the Atacama unit as well as the textile sleeve. Except for the anchoring material.
  • Page 15: Assembly Of Accessories - Condensate Trays (Ata-Condensate-Tray)

    1) Remove the masking tape 2) Centre and glue the condensation tray to condensation tray must from the double-sided adhesive the Atacama unit. Make sure the tub is match the rear side of the tape properly pressed against the unit - activating ATACAMA unit the adhesive on the tape.
  • Page 16: Examples Of Atacama Units Chaining

    3.7. Examples of ATACAMA Units Chaining Ceiling Assembly Wall Assembly 3.8. Sample assembly of the ATACAMA ATA1-x-ECVxTH-0A0 unit with textile sleeve Fig. 7 3.9. Water Exchanger Connection 3.9.1. Connection of the Unit to the Existing Hot Water Distribution System Connect the unit to the heating or cooling (cold water) system using a flexible connection (e.g. flexo hose with braid - armour).
  • Page 17: Vent (Drain) Valve

    3.9.3. Vent (Drain) Valve The water inlet and outlet throats are marked with coloured dots on the water exchanger collectors. Red point - hot water inlet; blue point - return. The marking is made for the unit designed for heating. Use a 6-corner fitting on the water heat exchanger throat to tighten the piping connected to the unit.
  • Page 18: Wiring And Electrical Connections

    Wiring and Electrical Connections 3.10. 3.10.1. General Information – Safety The relevant wiring and electrical assembly of the units may only be carried out by persons qualified for this activity with valid authorization and knowledge of the relevant standards and guidelines. Before starting any assembly work, it is necessary to switch off the power supply to the prepared wiring for subsequent recovery of the unit.
  • Page 19: Connection To The Mains

    that they cannot be interconnected or confused. This would result in the destruction of the unit's fan and possible further damage to property and personal health. 3.10.4. Connection to the Mains Connection to the mains is recommended using a wiring box with the appropriate electrical protection class (depending on the assembly space).
  • Page 20: Setting The Directional Fins

    Setting the Directional Fins 3.11. This applies to the ATA1-x-ECVxCL-0A0 (with the option of installing the ATA-CONDENSATE-TRAY accessory for cooling) and ATA1-x-ECSODI-0A0 versions Adjust the exhaust fins by deflecting the fins in the front exhaust enclosure. The minimum fin deflection for proper operation of the unit is from 45°, which allows ideal direction of the blown air into the heated space.
  • Page 21: Atacama Unit Wiring Diagram

    5. Atacama Unit Wiring Diagram 5.1. Connection of ATA1-x-ECVxxx-0A0 units with ELEMENTAIR-E-M1 controller Fig. 15 5.2. Unit connections - chaining ATA1-x-ECVxxx-0A0 with the ELEMENTAIR-E-M1 controller Fig. 16 Version 002 – GBR (25/09/2024) D-502-0165...
  • Page 22: Connecting The Ata1-X-Ecsodi-0A0 Units With The Elementair-B-M1 Controller

    5.3. Connecting the ATA1-x-ECSODI-0A0 units with the ELEMENTAIR-B-M1 controller Fig. 17 5.4. Unit connections - chaining ATA1-x-ECSODI-0A0 with the ELEMENTAIR-B-M1 controller Fig. 18 Version 002 – GBR (25/09/2024) D-502-0165...
  • Page 23: Connecting Units Without Regulation

    Check the other functions of the whole assembly according to the operating instructions of the selected controller. 7. Regular Maintenance and Cleaning of the Atacama Unit Before any maintenance and cleaning of the unit, the unit must be disconnected from the power supply and the heating water supply to the unit heat exchanger must be switched off.
  • Page 24: Cleaning Procedure

    Regular maintenance must include: o Check the heat exchanger and clean it of dust and grease, if any. o Check the motor and fan (bearings), remove dust and grease from the protective basket and fan fins. o Checking all the bolt connections on the unit for tightness (e.g. bolts for fixing the unit to the bracket, wall mounting bolts), including checking for mechanical damage to the unit (e.g.
  • Page 25: Servicing

    8. Servicing Observe the generally applicable provisions for the country. During any servicing, the unit must be disconnected from the mains, and the heating water supply to the unit's heat exchanger must be switched off. Works must be carried out after the heat exchanger has cooled down. Any electrical service works must be carried out by a qualified person.
  • Page 26: Warranty

    11. In Conclusion If you have any questions about this product, do not hesitate to contact us. Contact Address: Xvent s.r.o. Poděbradská 289 530 09 Pardubice-Trnová Czech Republic www.xvent.cz Version 002 – GBR (25/09/2024) D-502-0165...