Doc Ref: M311 Issue 1.1 May 2022 ® PSDE User, Installation & Servicing Manual Issue 1.1 May 2022 ErP COMPLIANT S E P T E M B E R 2 0 1 8 w w w . p o w r m a t i c . c o . u k...
1. The appliance type and serial number. 2. The original commissioning documentation. As much detail as possible on the fault. 3. Your supplier, or installer, will then contact Powrmatic to make a guarantee claim on your behalf. Conditions of Guarantee The Radiant plaque heater must have been installed by a competent qualified installer, and in accordance with the manufacturer’s instructions, building regulations and local regulations.
Additionally, it is recommended that the equipment be installed with a downward slope, away from the burner. The rate of declination should be 6mm (¼") in height per 3m (10') in length to allow the start-up condensation to drain. Series PSDE Page 3 M311 May22...
Only personnel who have been trained and understand all applicable codes should undertake the installation. Codes and Regulations PSDE Series radiant heater is designed and manufactured according to EN 419-1 “Non-domestic gas-fired overhead luminous radiant heaters”. This appliance must be installed in accordance with the rules in force. It shall be used in a space ventilated in accordance with the requirements of EN 13410 “Gas-fired overhead radiant heaters - Ventilation requirements for...
Alternating current Voltage 230 V, 50 HZ with L, N and PE Power consumption 12 W CONFIGURATION Model # PSDE10 PSDE20 PSDE30 PSDE40 PSDE45 Natural Gas 10.5 Nominal Input (kW gross) Propane 26.5 33.5 M311 May22 Series PSDE Page 6...
Work counter for light assembly, space is 4.5 m x 7.6 m, ambient air temperature 4C, located near shipping doors. Approximately 540 W/m x (4.5 x 7.6) m = 18.5 kW Two heaters at opposing locations would be preferred. M311 May22 Series PSDE Page 9...
9.2 – 18.3 15.2 – 24.4 22.9 – 33.5 27.5 – 35.0 30.5 – 38.1 interior row, (m) * Distance between heaters along interior rows should be up to twice the indicated number M311 May22 Series PSDE Page 10...
INSTALLATION Heater Mounting Figure 3 illustrates typical rigid and chain mounting configurations for the Series PSDE heaters; verify which is permissible by local codes. Heaters must be hung at an angle between 10° and 35°. Typically, at the walls they are at 35° facing into the building.
Test and confirm that inlet pressures are correct. Refer to the heater data plate and packaging to verify fuel type. Electric Figure 4 illustrates typical wiring arrangements for the Series PSDE heater. A 230Volt, 50Hz, single-phase supply is required.
When applicable, the exhaust air flow rate shall take into account any exhaust air flow rate required for other purposes. The fan capacity is then computed based on the higher of these air flow rates. M311 May22 Series PSDE Page 14...
Ensure that continuous waterproof barriers are used on the inside of all insulated surfaces. Ensure that exhausters pull air from the entire space and across the condensing surface. Humidistat controls may be integrated into the electrical control circuit of the heaters. M311 May22 Series PSDE Page 15...
2. With an air hose regulated to no more than 100 kPa blow away accumulated dust. Blow across the face of the ceramic tiles, not directly at them. Blow into each venturi for about one minute. 3. Verify that there are no cracked tiles. 4. Review the wiring for any loose connections. M311 May22 Series PSDE Page 16...
3. Affix the gas adjustment label (Natural Gas, 20mbar) supplied with conversion kit onto the Data Label adjacent to the headings, "Adjusted For" and "Setting Pressure" to cover the original gas adjustment label (Propane, 37mbar). 4. No need to change the first burner head. M311 May22 Series PSDE Page 17...
4. Turn pressure controller screw 5. Turn right - pressure increases / turn left - pressure decreases 6. Set the specified manifold pressure 7. Cover pressure controller with cap 8. Close test screw Figure 6 M311 May22 Series PSDE Page 18...
Verify and/or replace LED CODES: STEADY ON: NORMAL OPERATION 2 FLASHES: FLAME DETECTED OUT OF SEQUENCE 3 FLASHES: IGNITION FAILURE 4 FLASHES: CONTROL FAULT RESET LOCKOUT BY OPENING THERMOSTAT OR INTERRUPTING POWER FOR 10 SECONDS. M311 May22 Series PSDE Page 19...
85.6 85.6 85.6 th,nom Envelope Loss Factor Control type Single Stage 0.012 0.012 0.012 0.012 Electrical Power Consumption Ignition losses pilot NOx seasonal (GCV) (mg/kWh) Seasonal Space Heating Energy Efficiency η (minimum Eco-design requirements) M311 May22 Series PSDE Page 22...
Energy Association Powrmatic pursues a policy of continues improvement in both design and performance of its products and therefore reserves the right to change, amend or vary specifications without notice. Whilst the details contained herein are believed to be correct they do not form the basis of any contract and interested parties should contact the Company to confirm whether any material alterations have been made since publication of this brochure.