Do you have a question about the XEV22D and is the answer not in the manual?
Questions and answers
Subscribe to Our Youtube Channel
Summary of Contents for Copeland XEV22D
Page 1
USER MANUAL XEV22D Driver for Stepper Electronic Expansion Valves Release 1.5...
Page 2
Copeland 1065 Big Shanty Road NW, Suite 100 Kennesaw, GA 30144 USA 770-425-2724 • 1-800-829-2724 www.copeland.com Email: ColdChain.TechnicalServices@copeland.com...
• Fit the probe where it is not accessible by the end user. The controller must not be opened. CAUTION • In case of failure or faulty operation, send the instrument back to the distributor or to Copeland (see address) with a detailed description of the fault.
(SH) of the fluid that runs into refrigerating unit in order to obtain optimized performance and functioning of the evaporator independent by climatic or load conditions. XEV22D modules are equipped with two (2) probe inputs, one for a 4 to 20mA or 0 to 5V pressure transducer and another one for a NTC-EU, NTC-US or Pt100 temperature probe.
The superheat regulation is performed only when the cooling digital input is enabled. Figure 4-1 shows how the device takes the request of cooling: Figure 4-1 - How XEV22D Acts on Cooling Request See Figure 4-2 for wiring. The “First Level” indicates the connections on the floor of the 4-DIN module and “Second Level”...
P2= Pressure transducer 4.20mA or ratiometric (0-5Vdc). Table 4-3 - Digital Input Connection Supply Connection 4.6.1 Power supply XEV22D is powered at 24VAC/DC. Use Class 2 transformer with at least 20VA as the TF20D. Connect transformer to terminals 11-12. Valve Configuration 4.7.1 Before Connecting the Valve •...
If you can locate the value in the table, select the value through the tEP parameter. This way, you can be sure of the correct configuration (refer to Table 4-4). Liability Limitation - All the pre-sets have been done according to the documentation available when the XEV22D has been released, see below reference: •...
Page 15
16 or 12 in the “CPP” column. performed at the XEV22D controller or at the valve, and will have the same results. It is no longer necessary to take apart...
0.3A, power down the 4.10.1 Solenoid Valve Connection XEV22D and move the meter red lead from the meter 10A terminal to the meter 400 mA or 300mA terminal. If the meter dial selector has an AC mA selection (~mA), The positive shut-off function eliminate the necessity of change to the AC mA selection.
Supercap and/or the connected XEV22D. 4.11 Absolute Maximum Power The XEV22D controller is capable of driving a wide range of stepper valves; listed in Table 4-7 are the maximum values of current that the actuator can supply to the stepper wiring. Use the TF20D transformer.
In some instances, an installer may be required to mount the XEV22D. There are no restrictions on the location of the XEV22D; however, the controller should be mounted in a location protected from moisture. Typically, mounting inside the electrical control panel of a package unit is acceptable.
Sensors requiring 24VAC should not be powered from the Table 5-2- Transformer Compatible with XEV22D same transformer powering the input board. Any devices that will be connected to the XEV22D’s inputs or outputs must be Transformer powered with a separate 24VAC transformer.
Front Panel Function Key Combinations To lock and unlock the keyboard. To enter programming mode. Table 6-1- XEV22D Front Panel Keys and Functions XEV22D LEDS Each LED function is described in Table 6-2: Mode Function Low pressure alarm Figure 6-1 - XEV22D Front Panel...
(0 to 14) Liability Limitation - All the pre-sets listed on Table 8-3 have been done according to the documentation available when the XEV22D has been released. See below reference: • Danfoss • DKRCC.PD.VD1.C6.02 / 520H8021 @ Danfoss A/S (AC-MCI / sw), 2014-07 •...
Digital Inputs The XEV22D comes with two (2) digital inputs: a voltage-free input and a high voltage input; both can be configured as cooling call. In this way the cooling signal can come from the controllers with direct load outputs or via the controllers with voltage-free outputs.
Technical Data Table 14-1 - XEV22D Specifications Housing Self extinguishing ABS Case: Front: 4 DIN modules, 70 mm x 135 mm with male and female connectors Depth: 60 mm Dimensions Mounting: DIN RAIL mounted in a omega (3) din rail...
Do not connect the shield of the MODBUS network to the E2 PIB center terminal. Instead, use a 100 ohm 1/2 watt resistor to connect the MODBUS cable shield to earth ground. • At each XEV22D device, wire the MODBUS cable to the RS485 +/- terminals and connect the MODBUS shield to the pin 16 terminal. •...
Figure 16-1 - Location of E2 COM Ports (E2 Versions 3.xx and Below) Modem Card POWER INTERFACE BOARD Connecting an XEV22D controller to an E2 requires the E2 to (PIB) be version 2.84 or above. Contact Copeland for upgrade information if the controller is a version before 2.84.
Figure 16-8 - Network Summary Screen 16.4 Wiring Types Copeland specifies Belden #8761 shielded twisted pair cables for use as MODBUS wiring (or Belden #82761 and Belden #88761 for plenum installations). For MODBUS network wiring of XEV series of controllers to E2, Belden #8641 (P/N 135-8641) is the recommended wire type to use.
16.5 MODBUS Termination Blocks Because the XEV22D device has no on-board means of termination, use the MODBUS termination block (P/N 535-2711) for termination that can be wired to the end of the cable segment using the three-pin connector. Wire the two signal wires to the outside terminals, and connect the shield to pin 16, keeping the exposed shield wire length as short as possible (3 inches ideal maximum length).
Page 44
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Copeland reserves the right to modify the designs or specifications of such products at any time without notice.
Need help?
Do you have a question about the XEV22D and is the answer not in the manual?
Questions and answers