EMS FireCell FCX-500-004 Installation Manual

Radio hub

Advertisement

Quick Links

Radio Hub
Installation Guide
1 Pre installation
Installation must conform to applicable local installation codes
!
and should only be installed by a fully trained competent person.
Ensure the Hub is installed as per the site survey.
Refer to step 3 to ensure optimised wireless performance.
If using remote aerials with this product, refer to the remote aerial
installation guide (MK293) for more information.
This device contains electronics that may be susceptible to damage
from Electrostatic Discharge (ESD). Take appropriate precautions when
handling electronic boards.
3 Mounting location guidelines
For
optimum
performance, the following
must be observed:
Ensure the Hub is not installed
within 2 m of other wireless or
electrical equipment (not including
the panel).
Ensure the Hub is not installed
within 0.6 m of metal work.
Ensure the Hub is close coupled
above the panel.
5 Remove cable entry points
Drill the cable entry
points as necessary.
= DO NOT use
= Available cable
entry points
©2024 EMS Ltd. All rights reserved.
wireless
2 m
0.6 m
Hub
FIRE
Panel
Fire Alarm Control
Part no
Product description
FCX-500-004
4 Loop Radio Hub
FCX-500-444
4 Loop Radio Hub c/w Remote Aerial Facility
2 Components
1
2
3
1
4x corner covers,
4 Optional PCB removal
Remove the three circled retaining screws, before unclipping the PCB.
HEALTHY
FAULT
SYS FAULT
LOOP 1
IN OUT IN OUT
-
-
6 Fix to the wall
All five circled fixing
positions are available
for use as required.
The key hole can also
be used for locating
and
fixing
where
required.
Page 1 of 2
4
2
4 x lid screws,
3
Hub lid,
4
Hub PCB,
5
Hub back box
RF1R
F2
RESET
BACK
LOGON
LOOP 2
LOOP 3
LOOP 4
IN OUT IN OUT
IN OUT IN OUT
IN OUT IN OUT
-
-
-
-
-
-
TSD052-99 (Issue 21) 18/09/2024 AJM
5

Advertisement

loading
Need help?

Need help?

Do you have a question about the FireCell FCX-500-004 and is the answer not in the manual?

Questions and answers

Summary of Contents for EMS FireCell FCX-500-004

  • Page 1 • The key hole can also be used for locating fixing where required. = DO NOT use = Available cable entry points ©2024 EMS Ltd. All rights reserved. Page 1 of 2 TSD052-99 (Issue 21) 18/09/2024 AJM...
  • Page 2 March 2012. Fire detection and fire alarm systems. IP rating IP54 European Union Operating frequency EMS declares that this device is in compliance with Directive 868 MHz Directives 2014/53/EU. The full text of the EU declaration of conformity Output transmitter power 0 to 14 dBm (0 to 25 mW) is available at the following internet address: www.

This manual is also suitable for:

Firecell fcx-500-444