Replacing Components
Replacing a Fan Module During Operations
All fan and power supply modules must have the same airflow direction or else an error can occur with the
switch overheating and shutting down. You can determine the airflow direction of a fan module by the color
of the stripe on the front of the module. If the fan module has a blue stripe for port-side exhaust airflow, the
power supplies must have blue coloring for the same airflow direction. If the fan module has a burgundy stripe
for port-side intake airflow, the power supplies must have burgundy coloring for the same airflow direction.
To avoid over heating the switch, make sure that the fan modules are positioned in one of the following ways:
• For port-side exhaust airflow with blue coloring, position the fan modules in a cold aisle.
• For port-side intake airflow with burgundy coloring, position the ports in a cold aisle.
Before you begin
Before you can replace a fan module, ensure that the following conditions exist:
• There are four functioning fan modules in the other fan slots. In order to replace a fan module during
• The replacement fan module must have the same airflow direction as the other modules in the chassis.
If you must replace the fan module during operations and the above conditions are not met, leave the fan
module that you need to replace in the chassis to preserve the designed airflow until you have the required
module.
Procedure
Step 1
Remove the fan module that you need to replace as follows:
Replacing a Fan Module During Operations, on page 1
Replacing a Power Supply Module, on page 3
Installing and Removing Small-Form Pluggable Modules, on page 6
operations, there must be three fan modules circulating air in the chassis at all times. The other fan module
is redundant and can be replaced.
Replacing Components
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NXASFAN-160CFM2PE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cisco NXASFAN-160CFM2PE

  • Page 1 Replacing Components • Replacing a Fan Module During Operations, on page 1 • Replacing a Power Supply Module, on page 3 • Installing and Removing Small-Form Pluggable Modules, on page 6 Replacing a Fan Module During Operations All fan and power supply modules must have the same airflow direction or else an error can occur with the switch overheating and shutting down.
  • Page 2 If you are not able to push the module all the way into the slot, carefully slide the module out of the slot and check its electrical connectors for damage. If damaged, contact Cisco Technical Assistance for help. If undamaged, repeat this step to reinstall the module.
  • Page 3: Replacing A Power Supply Module

    If the STS LED does not turn on, slide the module out of the chassis, and visually check the electrical connectors on the back side of the chassis for damage. If damaged, contact Cisco Technical Assistance for help. If undamaged, repeat the previous step to reinstall the module.
  • Page 4 Replacing Components Installing an HVAC/HVDC Power Supply Procedure Step 1 Holding the replacement power supply with one hand underneath the module and the other hand holding the handle, turn the power supply so that its release latch is on the side. Align the back end of the power supply (the end with the electrical connections) to the open power supply slot.
  • Page 5: Installing A Dc Power Supply

    Replacing Components Installing a DC Power Supply Procedure Step 1 Holding the replacement power supply with one hand underneath the module and the other hand holding the handle, turn the power supply so that its release latch is on the side. Align the back end of the power supply (the end with the electrical connections) to the open power supply slot.
  • Page 6 Verify that the power supply is operational by making sure that the power supply LED is green. Installing and Removing Small-Form Pluggable Modules Before you begin See the Cisco Nexus 9364C-H1 Switch datasheet on cisco.com for a list of supported SFP and SFP+ modules.
  • Page 7: Summary Steps

    Replacing Components Installing and Removing Small-Form Pluggable Modules SUMMARY STEPS 1. Attach an ESD-preventive wrist strap to your wrist and to an earth ground surface. 2. Find the send (TX) and receive (RX) markings that identify the top of the SFP/SFP+ module. 3.
  • Page 8 Replacing Components Installing and Removing Small-Form Pluggable Modules Replacing Components...