Summary of Contents for IGS T18D

  • Page 1 Artificial Destratification Module Manual Designed to replicate natures winter thermal flow during the hot summer months +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 2: Systems Specifications

    • Pump Pressure No Aerator – 4 Bar (60 PSI) to 7 Bar (10 5PSI) • Pump Pressure With Aerator –6 Bar (90 PSI) to 7 Bar (10 5PSI) +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 3 Dropping Down To The Lower Levels. Nutrients And Contaminants Settle At The Bottom Of The Lake! Contaminants Entering The Lake Need To Be Reduced! +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 4 To The Surface Of The Lake. Oxygen Levels In The Deeper Water Become Depleted! Contaminants Entering The Lake Need To Be Reduced! +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS...
  • Page 5 Artificial Destratification Involves Increasing The Circulation Of The Water That Circulation Between The Shallower And Deeper Layers Of The Lake. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS...
  • Page 6 • This can be achieved by one of two methods; – IGS Water Aerator being installed at the lowest point of the dam, or – A conditioned water fountain can achieve the same results. • A circulation pattern is set up that reduces the differences in temperature, oxygen and nutrients between the top and the bottom waters.
  • Page 7 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 8 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 9 Washing Machines & Dishwasher Rigs +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 10 The global water problem +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 11 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS...
  • Page 12 ✓ Swimming pool water is clearer, softer, backwashing is reduced, saltwater chlorinators work more effectively, and chemical usage is reduced ✓ Ability to irrigate with brackish water +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS...
  • Page 13 INSTALLATION GUIDE Congratulations on your purchase of Your IGS Water Conditioner, ...The Water Conditioner That Works! The following instructions MUST BE ADHERED TO in order to obtain maximum efficiency. Treatment Chemicals Treatment chemicals which react with dissolved solids will also break down suspension. Typical examples are detergents, phosphates, acids, etc.
  • Page 14 E. BOILERS - must be fitted to the supply line after make-up water is added and positioned as close to the boiler as possible. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS...
  • Page 15: Installation

    TUF should be installed on the cold-water supply line. Maximum operating pressure 1000 KPA. Average Flow Rates Installer Instructions Components used for water treatment purposes shall comply with AS3500.1.2 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 16 Installation, Operation and Maintenance Manual Metric Models: FW100EX & FW150, 100 & 150 mm (4” - 6”) Piston models Electric Controls +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 17: Features Include

    ▲ Simple and quick installation. ▲ Full support and after sales service. ▲ Designed, built, owned and tested in Australia +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS...
  • Page 18: Operating Principal

    2.0 Operating Principal Put simply the IGS filter cleaning cycle works in a similar way to a vacuum cleaner, cleaning the solids off the fine screen with suction nozzles that rotate and spiral up and down to clean the whole fine screen area.
  • Page 19: Technical Specification

    * Other materials of construction 316 etc. are available on request. Filtration Apertures Available * Most common sizes used. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 20 4.0 Dimensional Details +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 21: Safety Instructions

    If not, the line pressure will drop too low and the filter will not clean itself effectively. If you do not have enough flow/pressure available you may need to restrict the flow after the filter during the backflush cycle. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS...
  • Page 22 Whilst doing this check the line pressure on the inlet side of the filter during the backflush cycle and ensure it remains above 200 kPa (30 psi). +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 23: Operation

    9.0 Maintenance Generally, your IGS filter should be trouble free, however you may need to remove the Fine Screen on a regular basis to remove any large debris from the Coarse Screen that has come into the system.
  • Page 24: Troubleshooting

    Drain the filter body if required so that the Fine Screen assembly is fully visible inside the filter. f) Remove the Fine Screen from the filter using the IGS screen removal tool (Part No. 15040). This locks into the Screen Handle and levers the fine screen out.
  • Page 25 Piston seals. Check that the Collector Assy rotates and moves freely inside the Fine Screen. If not check what is obstructing it. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 26 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 27 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 28 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 29 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 30 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 31 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 32 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 33 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 34 +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 35 The unit is equipped with a customized LCD display and key board. The unit counts separately the number of flushing cycles triggered by DP, by time and manually +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 36 The configuration process is described below. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 37 When the system does not include the built-in electronic DP sensor but is connected to an external DP sensor, the flushing request signal arrives in the shape of a closed dry contact. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 38 3. Alarm output, Delay-Valve and Main-Valve when defined, will be allocated in this order, right after the last backflush valve (whether in use or not). +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 39 Calibration - Zero calibration of the built-in electronic DP sensor. While the sensor ports are disconnected select Calibration = Yes. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS...
  • Page 40 A flushing sequence can be manually activated by the “MANUAL” key. When manually activated the icon will appear on the display. The same key will be used for manually terminating a sequence in progress. +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 41 Timing Diagram +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 42 + 6v - + 12v - Wiring of embedded electronic DP Sensor 24v AC Pressure Sensor (dry contact) Normally Closed solenoids +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 43 24v AC Wiring of embedded electronic DP Sensor 24v AC 24v AC Pressure Sensor (dry contact) Normally Closed solenoids +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 44 Outputs : 24v AC solenoids. DP: Embedded electronic analog DP sensor or external dry contact DP sensor. Pressure Sensor: Dry contact pressure sensor Operating temperature: 0-60 C +61 (03) 7035 6313 IGS Asia Pacific, info@igsw ater.co m Ground floor 470 St Kilda Rd Melbourne, VIC 3004, AUS www.igswater.com...
  • Page 45 14.0 Warranty Triangle Waterquip warrants all IGS® products against defects in material and workmanship for a period of 24 months from commissioning date or 18 months from delivery date, whichever date comes first. The warranty is limited and valid only when the product is used in accordance with the manufacturer’s standards and instructions and on condition that the customer fulfils their obligations set forth in this manual.

This manual is also suitable for:

T18T34T56T70T100T220 ... Show all