Addressable Heat Sensor instruction manual • Ref No: NISM/EV-H2-SCI/02 • 29.08.23 • Issue: 2 • Evolution • EV-H2-SCI • Heat Sensor with Integrated Isolator instruction manual Quality System Certificate No. 041 Assessed to BS EN ISO 9001 NITTAN EUROPE LTD. Hipley Street, Old Woking, Surrey, England, GU22 9LQ. UK www.acornfiresecurity.com...
Page 2
The evolution analogue addressable range all feature the very latest technological advancements such as microprocessor design, increasing reliability and performance.
Section 1 - INTRODUCTION The EV-H2-SCI is an attractively-styled, low profile heat sensor for use with Nittan ‘evolution’ protocol control panels. The EV-H2-SCI has a chemically etched, stainless steel insect screen therefore reducing the ingress of insects and airborne contaminants.
• Ref No: NISM/EV-H2-SCI/02 • 29.08.23 • Issue: 2 www.acornfiresecurity.com • EV-H2-SCI • analogue addressable heat sensor with integral isolator Section 4 - INSTALLATION In normal use, the EV-H2-SCI sensor will be installed at ceiling level. Pass the field wiring through the cable hole in the centre and from the rear of the base.
Page 5
Note: When carrying out site testing of Analogue Addressable Evolution detectors, the CIE shall be set to test mode prior to beginning the tests. i) Take any necessary precautions at the control panel to limit the sounding of the alarm sounders/bells and any fire service summoning device.
Page 6
• Ref No: NISM/EV-H2-SCI/02 • 29.08.23 • Issue: 2 www.acornfiresecurity.com • EV-H2-SCI • analogue addressable heat sensor with integral isolator ii) Test the heat sensor using ‘Detector Testers – Solo’ heat sensor tester, alternatively, ‘Detector Testers – Testifire’ equipment may be used. Check that the sensor gives an alarm condition within 15 seconds.
• Ref No: NISM/EV-H2-SCI/02 • 29.08.23 • Issue: 2 www.acornfiresecurity.com • EV-H2-SCI • analogue addressable heat sensor with integral isolator Section 9 - ADDRESS SETTING (EV-AD2-EXT) 1 Stand by mode The information displayed by the 7 segment LED cycles EV-AD2-EXT will switch to STAND-BY MODE to save every second and stops whilst displaying the [address] battery power if there is no key operation for more than at the end of the second cycle.
• Ref No: NISM/EV-H2-SCI/02 • 29.08.23 • Issue: 2 www.acornfiresecurity.com • EV-H2-SCI • analogue addressable heat sensor with integral isolator Section 10 - CONNECTIONS EV-H2-A1R EV-H2-CS +ve Line Out +ve Line In +ve Line Out UB-6-EV or UB-6-SL-EV UB-6-EV or UB-6-SL-EV Cable shield Wire Continuity connection EV-H2-SCI -ve Line Out...
• Ref No: NISM/EV-H2-SCI/02 • 29.08.23 • Issue: 2 www.acornfiresecurity.com • EV-H2-SCI • analogue addressable heat sensor with integral isolator Section 12 - DISPOSAL This symbol on the EV-H2-SCI indicates that this product must not be disposed of with household waste. Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment.
Need help?
Do you have a question about the NITTAN EV-H2-SCI and is the answer not in the manual?
Questions and answers