Multifunctional three phase voltage monitoring relay (8 pages)
Summary of Contents for Novatek OM-110
Page 1
Review the Operating manual before using the unit. Dear Customer, NOVATEK-ELECTRO Ltd. Company thanks you for purchasing our products. You will be able to use properly the device after carefully studying the Operating Manual. Store the Operating Manual throughout the service life of the device.
Page 2
8. Autoreclosing time delay (ton) – adjustment knob 9. Tripping time delay (toff) – adjustment knob 10. Output terminals ~250V AC, 8A (terminals of load control relay) 11. Hole of integrated current transformer Figure 1 – Front panel and main knobs and controls ОМ-110 NOVATEK-ELECTRO...
Measured range is from 0 to 20 kVA. The function of OM-110 is to cut off the power load in case of exceeding the preset threshold for maximal level of permitted power load consumed by the user (with user defined time delay) and automatic autoreclosing with adjusted time delay or prohibited restart.
*** To increase operational range to low voltage ОМ-110 has function to disable LED digital indicator if voltage level gets lower than 130V. If voltage level is less than 110V then OM-110 automatically opens its output terminals to initial cold state position and thus tunrs OFF.
Page 5
3.1.4 The wire of the circuit which should be under the device control must be inserted through the hole in the case of OM-110 (item 11; Figure 1). If the limiter is used as the load priority relay, pass the wire that supplies power to both loads (priority and non-priority) through the hole CТ...
Page 6
1.75 kW. When load power up to 20 kW, AB1 should be installed for current no more than 100 A. AB2 is circuit breaker for non-priority load, it protects both the load and OM-110 against short-circuit (SC). Figure 3 – Wiring diagram for ОМ-110 as the load priority relay 3.2.3 If the autoreclosing time delay knob is set up to position inF (mark «∞»...
(autoreclosing prohibited) and current value of power. To turn ON the power load it’s necessary to take OFF the power supply for the input terminals of OM-110 or to change the position of the autoreclosing time delay (adjustment knob (item 8; Figure 1) to another value different from inF. When moving the autoreclosing time delay knob to the position of prohibited autoreclosing (inF) then on the digital LED indicator is being displayed “inF”...
Page 8
Manufacturer is grateful to you for the information about the product quality as well as comments and proposals concerning the unit operation. With questions and comments, please contact manufacturer at the following address: "Novatek-Electro" Ltd. 59, Admiral Lazarev str., Odessa, Ukraine, 65007 Tel: +38 048 738-00-28; +38 0482 37-48-27;...
Need help?
Do you have a question about the OM-110 and is the answer not in the manual?
Questions and answers