8 - MAINTENANCE ......................................15 8.1 General recommendations ..................................15 8.2 Servicing ........................................15 8.3 Access to the main components ................................16 9 - CONTROL AND ANALYSIS OF BREAKDOWNS ............................18 10 - FINAL SHUTDOWN .....................................19 ORIGINAL TEXTS: SPANISH VERSION AquairPremium BCP E N - 2...
1 - INTRODUCTION Operation mode AquairPremium BCP are dehumidifi cation units by cooling circuit, with total condensing heat recovery, specially designed for conventional This unit consists of three stages of dehumidifi cation by means of covered pools and other dehumidifi cation applications.
● Repair the leak detected and recharge the circuit with the total refrigerant charge, as indicated on the unit's nameplate. Only charge All interventions on the refrigerating circuit must be performed in liquid refrigerant at the liquid line. accordance with applicable legislation. AquairPremium BCP E N - 4...
The unit bears, legibly and indelibly, a nameplate located in a prime space, as appears in the attached image. It is necessary to check that this is the model requested. AquairPremium BCP Weight (kg) 2.220 2.270 Año\An.Year...
- Minimum ambient temperature: -30°C Foresee appropriate damping devices in these fi xings to - Maximum ambient temperature: 50°C ensure that noise and vibration transmission is avoided. - Maximum relative humidity: 95% (to avoid condensation) AquairPremium BCP E N - 6...
2 and at 1,5 meters from the ground. larger space around it may be required to ensure proper air circulation and therefore the correct operation of the unit. AquairPremium BCP Total dB(A) 62,5 63,5 Note: The sound pressure level depends on the installation conditions and, as such, it only indicated as a guide.
Access door to the servomotor of the new air damper Hot water coil outlet Water circuit outlet Hood for outdoor installation (optional) Water circuit inlet Access door to New air intake damper the supply fans AquairPremium BCP E N - 8...
Connection chart ● The nameplate data. ● The wiring diagram included with the unit. AquairPremium BCP 270 and 360 ● Norms in eff ect that regulate the installation of air conditioning units and electrical receivers in the country of installation.
Caution: If the supply fan is accessible from any point of the duct network, the installer must place a protective mesh at Please ensure that the connection is completely watertight. the fan outlet in compliance with current regulations. AquairPremium BCP E N - 1 0...
Corrosion behaviour above 150 ppm increase the risk of scaling. The plates exchangers of AquairPremium BCP units are made up of Legend: stainless steel SS-316, and the material used for the plates welding + Good resistance under normal conditions.
The water condenser circuit will operate as second stage if neccesary. • The hot water coil will operate whenever there is a demand for 7 8 9 10 Flow (m³/h) heating. AquairPremium BCP E N - 1 2...
Magnetothermal switch that protects the operation circuit against continuous surges as well as against high currents of short duration ● HEATING mode: this closes outdoor air damper and opens HWC valve. (short circuits). E N - 1 3 AquairPremium BCP...
7 - COMMISSIONING Warning: The commissioning of the installation should be carried out by by CIAT’s Technical Assistance staff . ● It is advisable to create a detailed layout of the installation, including ● Doors and windows must be closed to facilitate the increase of air the position of the unit and all utilized components.
● Check the unit’s alarm report (see the control manual); all these operations: use appropriate PPE (personal ● Check for any general signs of deterioration, protective equipment), comply with all industry and local regulations, use common sense. ● Check the anti-corrosion coatings. E N - 1 5 AquairPremium BCP...
8.3 Access to the main components tons (t CO2e) for each model: It is mandatory to use all required PPE for work at height. AquairPremium BCP C1: 7,5 / C2: 7,0 / C1: 7,8 / C2: 7,3 / Charge (kg)
Page 17
It is advisable to check the condition of the servomotors of the mixing box. shut-off valves at the input and output, and a drain for emptying. E N - 1 7 AquairPremium BCP...
Disassembly the probe encapsule Proceed to clean the sensor with some soft cotton element and non-abrasive fl uid, without pressing it Reassemble the casing, checking that the cable is in contact externally with the metallic mesh AquairPremium BCP E N - 1 8...
● Energy transfer fl uid: depending on the installation, water, glycol/ Important: In order to recycle these units follow the water mix. stipulations of Directive 2012/19/EU on Waste electrical and electronic equipment (WEEE). ● Compressor oil E N - 1 9 AquairPremium BCP...
Page 20
The quality management system of this product’s assembly site has been certifi ed in accordance with the requirements of the ISO 9001 standard (latest current version) after an assessment conducted by an authorized independent third party. The environmental management system of this product’s assembly site has been certifi ed in accordance with the requirements of the ISO 14001 standard (latest current version) after an assessment conducted by an authorized independent third party.