Contents Page Norms and Regulations Norms and guidelines General Instructions The flame makes up the difference Saving of energy Tendering Installation Dimensions of pitch circle at boilers‘ door Mounting the burner Tips for mounting Check of installation Burner operation Special areas of operation Commissioning Commissioning and settings Adjustment of potentiometers...
- Shut off gas-supply line and safeguard against unintentional opening Safety first!!! HPM1/1.1 10 - 70 kW 1. Norms and Regulations 1 .1 Norms and Guidelines Handling with inflammable On mounting of a gas firing unit DIN...
2 . General Instructions HPM1/1.1 2 .1 The flame makes up the Exhaust-gas-temperature Gas-amount-counter Smoke gas shutoff difference damper The exhaust gas temperature Gas consumption can be Due to many years of expe- will be measured by a ther-...
HPM1/1.1 3. Installation 2 .3 Tendering One step, two step, with booster and modulating regu- lation with potentiometer and pre-aeration and admitted for intermitting operation on cast iron and steel boilers. Components of burner: Premix fan motor Spiral casing (Aluminium) ...
Type If it is not possible to set the HPM1 <10ppm 8,0%-8,1% 30-35ppm -values as shown in the Tab x Type of gaz G 20 at low-load table, check the boiler for H-Gas...
4 . Commissioning HPM1/1.1 4 .2 Adjustment of potentiometer Potentiometer / Output-regulator Gas and Air regu- lation have default settings. Burner output is adjustable by potentiometer (see table p.10). Please carry out any alterations of speed (revoluti- ons per minute) via potentio- meter at a low pace because pulses are possible.
5 . Maintenance HPM1/1.1 5 .2 Output table HPM 1.1 10 - 45 kW HPM 1.1 10 - 45 kW Output table L Gas (G25) in standard values Output table L Gas (G20) in standard values for exact metering see table...
HPM1/1.1 6. Troubleshooting 6 .1 Causes of error and corrections Permanent checks and safety conditions serve safeguarding burner and environment. Demanding tight threshold values serves continous supervision of given safety times and processes Variances in threshold values lead to error messages and lock-out.
6 . Troubleshooting HPM1/1.1 6 .2.1 Error message with lock-out and locking Shut-off of the firing device takes place with error codes 1 to 30 erfolgt mit den Störcodes 1 bis 30 Error 1 No flame after several attempts of ignition;...
HPM1/1.1 7. Technical Documentation 7 .1 Wiring diagramm Wiring diagramm Hansa burner 1-step Power input from boiler panel Observe local rules and regulations Wiring diagramm Hansa burner 2-step Power input from boiler panel Observe local rules and regulations...
7 . Technical Documentation HPM1/1.1 Wiring diagramm Hansa burner modulating 0 - 10 V Input Power input from boiler panel Observe local rules and regulations 7 .2 Measuring fields Hansa Premix HPM 1.1 Measuring field natural gas G 20, G 25 - 1 .0 0...
Our guarantee is valid up to 24 month after putting into operation however 27 month after the date of selling at the longest and is limited to the replacement of defect parts. Please use only HANSA OEM-spares otherwise you will loose your claim under guarantee.
HPM1/1.1 8. Declaration of Conformity/Manufacturer 8 .1 Manufacturer‘s certification Hansa Öl- und Gasbrenner GmbH is certifying approval for pre-mix gasburners as given below: Product Gasburner Trade name HPM 1 / 1.1 Type/ Model No. (BUWAL/VKF) HPM 1 / Norms DIN EN 676 Testing Centre TÜV - Rheinland...