73mm EC-MAC 50mm 50mm 38mm 38mm 44mm 44mm 137mm 137mm 73mm Ø7mm Equipment instruction manual The content of this manual is written for standard equipment, but it is also applicable to related equipment.
Page 2
Table of Contents Receiving notice Safety instructions 3-1 Marking description 3-2 Precautions during installation 3-3 Precautions when using 3-4 Precautions when abnormal Functions and specifications 4-1 Process of air cleaning and filtering 4-2 Parts description Installation method 5-1 MAC-EC51(E)/101(E)/201(E) 5-2 Precautions Control Panel Specifications 6-1 button description-There are two types of control panel Operation 7-1 Wiring instruction-Type 1...
Page 3
Preface Thank you for purchasing our company’s EC-MAC. Please read the manual carefully and use the product correctly. Improper operation will cause serious accidents. Please make sure to appoint the operation and management personnel of this equip- ment. If any abnormal accident occurs, please report to the manager immediately.
Page 4
Marking Description If you do not comply, there is a high possibility of serious Danger harm to life or body and mind. If you do not comply, it may cause minor injuries or mal- Cautions function of the machine. Forbidden Prohibited matters Follow Indicates to matters that need to be enforced.
Page 5
Install the device in a stable position. If the device is installed in an unstable position and tilted, it may cause problems with the operation of the blower. Do not block the return air vent. Blocking will reduce the return air volume, and thus reduce the performance of the equipment.
Page 6
Do not damage the power cord. Do not place heavy objects on the power cord or arbitrarily place it. Damage to the power cord may cause accidents such as fire or electric shock. Do not modify the equipment. It may cause electric shock, fire, and equipment performance degradation. It is forbidden to use volatile oil or thinner to clean the equipment.
Page 7
4. Functions and specifications Process of air cleaning and filtering PRE-FILTER Blower MAIN FILTER Contaminated Air High Efficiency Pre-Processing Pressurized Air Filtering Figure 1 Parts description a. Pre-Filter It is made of Nylon and the purpose is to prevent the large particles from falling in. 73mm This filter can be reused after washed with water or vacuumed.
Page 8
Please refer to below chart for the hole-opening size and use the screws to fasten the equipment to the fixing base. Code EC-51(E) EC-101(E) EC-201(E) 1190 EC-MAC 73mm Opening Base Figure 2 5-2 Precautions Please connect the power supply to the terminal block of the equipment according to the voltage shown in the specifications and be sure to be grounded.
Page 9
6. Control Panel Specifications button description-There are two types of control panel Type 1:The Chip-type PCB control panel is as above Figure 3. Figure 3 (1) Big Trip Light (When motor is overloading, easier to be seen) (2) Small Trip Light (When motor is overloading) (3) Low Air Velocity (On when selecting Low Air Velocity) (4) Medium Air Velocity (On when selecting Medium Air Velocity) (5) High Air Velocity (On when selecting High Air Velocity)
Page 10
Operation Wiring instruction-Type 1:The Chip-type PCB Type 1:The Chip-type PCB wiring instruction is as above Figure 5. F.F.U. CONTROL LAYOUT D- D+ D- D+ Figure 5 73mm (1 ) Power set:This is a single-phased product. Please follow R.T.E to connect the wires.
Page 11
7-2 Wiring instruction-Type 2:Simple-type PCB Type 2:The Simple-type PCB wiring instruction. COM1 (NO) (NC) COM2 (NO) (NC) CONNECTOR 6P CONNECTOR 4P CONNECTOR Figure 6 TRIP POWER terminal type 73mm Figure 7 (1 ) Power:This is a single-phased product. The connector is 4P, and please follow the location of the CONNECTOR 4P in Figure 6;...
Page 12
Restart after power failure air supply unit Wind speed is too low FILTER blockage Replace FILTER during operation Short circuit of the electronic control parts Please disconnect the power Burnt odor and contact AIRTECH. Wire fire caused by overload 73mm...
Page 13
9. Maintenance Main Filter (HEPA & ULPA FILTER) The wind speed is reduced when the filter is clogged. When the wind is reduced to the half of the original, you need to change the filter. The filter replacement time is also depending on the clean room environment.