Page 2
TC-DEX – cap for delivering test gases to the DEX detector enclosure – can be used when the detector is placed in IIA or IIB gas-hazardous zone; MD – two-threshold alarm modules manufactured by GAZEX, types MD-(1, 2, 4)… or measuring modules MDP-(4, 8, 16)…;...
Page 3
‘n’ is for digits comprising the code of the sensor module (calibration gas). MS sensor modules for DEX-nn, DEX-nn/N, DEX-nE/N, DEX-nK/N, DEX-nKL/N, DEX-nR and DEX-nR/N are interchangeable, i.e. different modules can be used for the same DEX/F body (except for DEX-nn.K detectors).
Page 4
(values for individual substances in accordance with PN–EN 60079-20-1:2010). NOTE: Detecting media in other ranges or different media is possible = special version, requires consultation with GAZEX; in particular cases, it is possible to tailor detector parameters to a specific application = ANALYSIS OF OPERATING CONDITIONS IS REQUIRED.
Page 5
The data for Tables 1.1.nE and 1.2.nE were sourced from materials provided by electrochemical sensor manufacturers (updated November 2023). GAZEX assumes no responsibility for the reliability of the above data. NOTE: When selecting a detector for a specific Customer application, GAZEX may use sensors with different parameters than those listed above.
Page 6
(updated July 2007). Coefficients for other media (if provided by the manufacturer) are available at GAZEX. The above coefficients should be regarded as approximate; they may differ from the actual values for a given sensor and may change over the course of operation.
Page 7
SL – selectivity as per Figure 1.2.nR Detecting other media or in other ranges is possible = special version, requires consultation with GAZEX; in particular cases, it is possible to tailor detector parameters to a specific application = ANALYSIS OF OPERATING CONDITIONS IS REQUIRED.
Page 8
F4-C,F4-CM,F4-S-C,F4-S-CM,F4-HT-C,F4-HT-CM versions KDB 04ATEX133X Ex detector certificate Standard Gazex 3-Year Plus Warranty (SGG3Y+) covering the period until the Warranty end of the year in which the device was manufactured and the following 3 years (year of manufacture indicated on the nameplate => no warranty cards required);...
Page 15
9.3.3 of the PN-EN 60079-14:2014-06 . As this requirement is not precise in the standard, GAZEX recommends the use of flexible standard control cables with polyvinyl chloride (PVC) or similar plastic insulation, designed by the manufacturer for industrial applications, for permanent installation, including outdoors and directly in the ground, with a rated voltage of 0.6/1 kV.
Page 17
‘Ex’ junction box with at least four terminals (available from GAZEX). The cable connecting the junction box to the control module should then meet the requirements listed in section 5.1.1.1: a) with an outer diameter selected for the cable gland used in the junction box, b) with core cross-sections appropriate for the terminals in the junction box, d), e), g), h).
Page 21
® 6.4. STORAGE OF DEX DEX/F detectors should be stored in a place free from vibrations, moisture, dust, exhaust fumes, free of any chemically active substances (especially those containing silicones and derivatives), in a tightly sealed polythene bag.
Page 22
GAZEX reserves the right to make minor changes to the technical specifications of the products supplied, while such changes and not included in this User Manual, and to modify the latter.
Page 23
SGG3Y+ available at www.gazex.pl. Selected extracts from the SGG3Y+ terms and conditions: … 1. GAZEX guarantees the efficient operation of devices of its own manufacture for the period up to the end of the year in which the device was manufactured and for another three years.
Page 24
DEX/F Detector – Recommended for Normal Operating Conditions MAINTENANCE SCHEDULE v2406 INSPECTION INSPECTION OF INSPECTION OF OPERATIONAL GAS SENSOR MAINTENANCE OF SENSOR COVER DETECTOR BODY ACTIVITY CHECK CALIBRATION THREADED PERMEABILITY SEALING CONNECTIONS Sensor shield with Threads on detector Cable gland...