OVERVIEW
This detector model samples the air in the protected area. An alarm condition is raised when the detected environmental smoke quantity
exceeds the alarm threshold.
COMPATIBILITY
This detector is compatible only with wireless systems based on the Sagittarius protocol.
For more specific information concerning compatibility refer to your fire security system supplier.
INSTALLATION - IMPORTANT NOTES
For detector spacing, placement and special applications refer to your specific national standards.
Mount the detector as far as possible from metal objects, metal doors, metal window openings, etc. as well as cable conductors, cables
(especially from computers), otherwise the operating distance may greatly drop. The detector must NOT be installed near electronic devices
and computer equipment that can interfere with its wireless link quality.
This detector must be installed according precisely to the procedures described in this manual.
Test this detector after installation.
BEFORE INSTALLING THE DETECTOR
1) Extract the batteries cover from the back of the detector.
2) Power-up the detector removing the isolating tab in the battery
housing. LED indicators signal "Power up".
3) Link the detector to the Sagittarius wireless system (LINKING).
4) Check the WIRELESS LINK QUALITY.
5) SELECT A GOOD LOCATION FOR THE DETECTOR.
6) Tag device's loop and address data (IDENTIFICATION).
7) Fix the detector supporting base to the wall (BASE INSTALLATION).
LED INDICATORS
Picture 1: provide visual indication for functional conditions and battery
levels as indicated in table 1.
Detector's status
Power up
Linking to the
system
Link failure
Normal condition
Alarm
Battery 1 fault
Battery 2 fault
Both batteries fault
Other fault
Tamper
Lost link with wire to
wireless translator /
wireless expander
Test Mode - Detec-
tor is more reactive
to aerosol stimulus
EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville
Hampshire - PO7 7XN - United Kingdom
BI-DIRECTIONAL WIRELESS ADDRESSABLE DUAL PATH
OPTICAL SMOKE DETECTOR WITH VARIABLE SENSITIVITY
LEDs indication
1 second GREEN, then 4 X 0.5 second RED blink
Blinking GREEN until linking is completed
RED on (continuous)
LEDs off
Blinking RED: 0.5 second on and 0.5 second off
0.1 second ORANGE blink, then 5 seconds off
0.1 second GREEN blink, then 5 seconds off
0.1 second ORANGE, then 5 seconds off
0.1 second GREEN, then 5 seconds off
sequential ORANGE / GREEN 0.5 second blinking
LEDs off
LEDs off
Blinking GREEN every 1 second for 1 minute
EUW-PA-02
Picture 1
Table 1
LED INDICATORS
www.eurotechfire.com