Page 1
AirGENIO CONTROL ALFA 95 FLAT SQ OPERATION AND HANDLING...
Page 2
9. Display of current temperature, ventilation rate, CO2 com- centration, ventilation mode and date 1. Night cooling 2. Occupancy mode active 3. Time mode active 4. Heater cooling in progres 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 3
VENTILATION LEVEL SETTINGS 1. Display of current airflow 2. Reducing or increasing unit airflow (min 20% - max 100% in 10% increments 3. Display of required airflow 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 4
Week mode Touch a day to set ventilation modes Touch to set individual intervals of ventilation (time ON/OFF, vent. mode, vent. level, temperature) Touch for copying time interval 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 5
Beginning of time interval (Day/Month) End of time interval (Day/Month) Values setting Delete time interval Back When the time interval ends, the unit goes into stand-by • mode. LANGUAGE SETTINGS 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 6
DISPLAY SETTINGS Display brightness in active mode Display brightness in Standby mode 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 7
After scanning QR code from the controller press “Save” for saving the unit to the app. 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 8
Enter the PIN from the controller Name the unit Select language After entering all the information from the controller press “Save” for saving the unit to the app. 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 9
MENU can lead to improper operation of the unit. If you are uncertain, first contact your supplier for more information. 1616 Scroll up/down to select menu then tap on selected menu 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 10
N.close (normally closed) or N.Open (normally open) Option to select function of switching motion sensor or fire contact Possibility to choose the logic of the run contact (N.Clo- se / N.Open) 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 11
Filter calibration Filter calibration has to be carried out during the first commi- ssioning and after a filter class change. 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 12
The Software reset (menu 48) must be performed to save the changes 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 13
The supply air temperature is between the minimum and maximum supply air temperature. According to the setting in the menu 10 - SUPPLY DUCT LIMITS. Room BMS: Temperature information provided by the building management system 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 14
Selecting the sensor in the supply ductwork disables the • maximum temperature setting in the ductwork. Bypass Temperature Setting of minimum outdoor temperature from which the bypass opening is allowed (range 0-20°C) 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 15
Setting the airflow when the FIRE contact opens (input terminals15/16) FIRE VENTILATION input has highest priority (it deacti- vates all other modes, including anti-frost protection). 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 16
The unit will work at the value set prior to its transition into Standby mode. Setting the time interval for which the mode will be active after the BOOST contact is activated Setting the required airflow 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 17
Setting desired temperature (measurement on Exhaust Channel sensor). Range of +12°C to +25°C. Date (for evaluating the activation of NIGHT VENTILA- TION) Setting the time (for evaluating the activation of NIGHT VENTILATION) 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 18
Ext3 - Air intake temperature sensor (inlet to room) Int1 - Exhaust air temperature sensor (exhaust before core) Int2 - Anti-freeze sensor of the heat exchanger (exhaust behind core) 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 19
The NETWORK menu serves for setting the network commu- nications of the unit (TCP Modbus). The Software reset (menu 48) must be performed to save the changes. 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 20
Full - Does not enable any settings without entering password User mode - Enables the unit to be operated per the following screen: After entering the password, the unit can be fully operated and set 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 21
BACnet The BACnet menu is used to set the unit‘s network commu- nication (ModBus TCP). Software reset Power reset 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 22
Pressing FACTORY RESET resets the unit to its factory settings does not change - the configuration AQS - ventilation mode - HW settings - temperature settings - Modbus settings 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 23
ATTENTION! In case that filters will not be replaced properly, func- tionality of the unit may be reduced the preheater can overheat and ventilator can be damaged. 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 24
The unit ventilates insuf- Unit is working Clogged filter or ductwork. Check the filters and whether the ductwork is not clogged ficiently or is noisy 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...
Page 25
In case of any requests or inquiries, contact our sales or technical department. CONTACT Address 2VV, s.r.o., Nádražní 794, 553 51 Pardubice – Rosice, Czech Republic Website: http://www.2vv.cz/ 2VV. Creating innovative solutions for you and your business since 1995. ver.1 20-08-21...