Page 1
DL-11 User Manual RS-485 Remote Temperature and Humidity Ver. 1.0, Jul. 2024 WARRANTY All productsanufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery to the original purchaser. WARNING ICP DAS assumes no liability for damages consequent to the use of this product.
Page 2
PC .......................... 9 NSTALLING OFTWARE ON ............................... 9 EARCHING ODULE What to do when DCON Utility Pro cannot find the DL-11 module? ................. 13 ............................14 ONFIGURING ODULE Configuration ................................15 Temperature ................................16 MODBUS REGISTER TABLE (BASE 0) ......................17 ) ..............................
Page 3
The DL-11 module supports Modbus RTU communication protocol for getting measured temperature and humidity values. DCON Utility Pro provides easy and convenient interfaces for users to configure the module. Based on an amazing tiny form-factor, the DL-11 achieves the maximum space savings that allows it to be easily installed anywhere.
Page 5
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module 2.2 Specification Temperature Sensor Measuring Range -25 ~ +75 °C (-13 ~ +167 °F) Resolution 0.1 °C Accuracy Typical: ± 0.4 °C @ 0 ~ 60 °C; refer to Figure 2 ± 0.1 °C...
Page 6
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module Power Input Range +10 ~ +30 V Consumption 0.05 W Mechanical Dimensions (W x L x H) 25 mm x 20.2 mm x 30 mm Installation Magnetic mount; Wall mount Cable Length...
Page 7
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module 2.3 Dimensions Unit: mm Top View Left Side View Front View Right Side View Rear View Bottom View 2.4 Factory Default Settings Item Default Item Default Device ID Data Format N, 8, 1...
Page 8
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module 3. Getting Started This chapter provides a basic overview of how to configure and operate your DL-11 module. 3.1 Connecting the Power and the Host PC Prepare for device RS-232 to RS-485 Converter: tM-7520A (optional) ...
Page 9
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module 3.2 Installing Software on Your PC Download DCON Utility Pro.zip from the ICP DAS web site and decompress it https://www.icpdas.com/en/download/show.php?num=1046 3.3 Searching Module Step 1 Run the DCON Utility Pro software Pro.exe.
Page 13
DL-11 when normal wiring and power up, please follow the procedures described below to solve the situation: 1. Use the blade of a flat-head screwdriver to set the “Init Switch 1” on the DL-11 to the “ON” (Init Mode) position, and reboot the module.
Page 14
In the DCON Utility Pro software, click the module name to open the configuration window, allowing you to configure the settings for DL-11 and verify the readings on the module, each of which will be described in more detail below.
Page 15
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module Configuration You can view and configure the settings on the DL-11 module, including the Address, Baud Rate and Data Format on the “Configuration” page. The following is an overview of the parameters:...
Page 16
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module Temperature On the “Temperature” page, you can view the measured values and set the offset for each item. The following is an overview of the parameters: Item Description Humidity(%) Displays humidity value...
Page 17
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module 4. Modbus Register Table (Base 0) Discrete Inputs (1xxxx) Register Points Description Data Format Attribute 00283 011B Write1 to save sea level pressure to non-volatile memory 10272 0110 Read the reset status of a module.
Page 18
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module Read the firmware version (Minor number) 30480 0x0000 Hexadecimal Representation Read the firmware version (Major number) 30481 0xA202 Hexadecimal Representation Read the module name 30482 High byte = 0x00 0x0011 Low bye = 0x11...
Page 19
DL-11 – RS-485 Temperature/Humidity/Atmospheric pressure/Dew Point Sensing Module 00: no parity, 1 Stop bit 01: no parity, 2 Stop bits 10: even parity, 1 Stop bit 11: odd parity, 1 stop bit Read/Write the response delay 40487 0 ~ 30...
Need help?
Do you have a question about the DL-11 and is the answer not in the manual?
Questions and answers