INSTALLATION INSTRUCTIONS
Victaulic
VicFlex
®
Style AB7 Bracket
Flexible Hose Listing and Approval Information
Flexible Hose
AH1
AH1-CC
AH2
AH2-CC
AH2-300
AH2-638
AH3*
AH4
AH5
* SERIES AH3 – REGIONAL AVAILABILITY ONLY
NOTES: Victaulic
®
VicFlex
flexible hoses are City of Los Angeles (RR5659) Approved, accepted for use by the City of New York Department of
Buildings (MEA 60-05-E), and have the OSHPD Pre-Approval (OPA-2255-07).
Flexible hoses are available in lengths from 31 - 72 inches/787 - 1829 mm with either 1/2-inch/DN15 or 3/4-inch/DN20 NPT or BSPT threaded outlets.
Maximum Working Pressure Rating of Flexible Hose:
200 psi/14 Bar/1379 kPa (FM)
175 psi/12 Bar/1207 kPa (UL)
16 Bar/1600 kPa/232 psi (VdS)
16 Bar/1600 kPa/232 psi (LPCB – Series AH1, AH2)
1.4 MPa/1400 kPa/203 psi (CCCf – Series AH1, AH2, AH3)
300 psi/21 Bar/2068 kPa (FM – Series AH2-300)
Maximum Ambient Temperature Rating of Flexible Hose:
225° F/107° C (UL, FM, VdS, LPCB)
135° C/275° F (CCCf – Series AH3)
Connection to Sprinkler Piping:
1 inch/DN25 NPT/BSPT (UL, FM, CCCf)
1 inch/DN25 IGS (FM, VdS)
DN20/3/4 inch BSPT (VdS)
DN32/1 1/4 inch BSPT (LPCB)
Minimum Bend Radius of Flexible Hose:
4 inch/102 mm (UL – Series AH5)
7 inch/178 mm (FM – Series AH1, AH1-CC, AH2, AH2-CC, AH3,
AH4, AH2-638)
76 mm/3 inch (VdS – Series AH1, AH1-CC, AH2, AH2-CC, AH3,
AH4)
76 mm/3 inch (LPCB – Series AH1, AH2)
178 mm/7 inch (CCCf – Series AH1, AH2, AH3)
8 inch/203 mm (FM – Series AH2-300)
REV_I
Flexible Hose with Fittings
• Read and understand all instructions before attempting to install any Victaulic
• Wear safety glasses, hardhat, and foot protection.
• These installation instructions are intended for an experienced, trained installer.
• The user shall understand the purpose of these products, c ommon industry standards for safety,
and the potential consequences of improper product installation.
• It is the system designer's responsibility to verify suitability of stainless steel flexible hose for use
with the intended fluid media within the piping system and external environment.
• The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level,
and flow rate on the stainless steel flexible hose shall be evaluated by the material specifier to
confirm system life will be acceptable for the intended service.
Failure to follow these instructions could cause improper sprinkler operation and product failure,
resulting in death or serious personal injury and property damage.
With AB7
With AB7
With AB7
With AB7
With AB7
With AB7
With AB7
With AB7
With AB7
for Fire Protection Service
WARNING
G412024
With AB7
With AB7
With AB7
With AB7
With AB7
With AB7
Maximum K-Factor of Sprinkler to be Connected to Sprinkler
Reducing Nipple:
K8.0 US/K115 metric for 1/2 inch/DN15
K14.0 US/K200 metric for 3/4 inch/DN20
K115 metric/K8.0 US for 3/4 inch/DN20 (VdS and LPCB)
Maximum Number of 90° Bends Per Flexible Hose:
Refer to the "Friction Loss Data" section. NOTE FOR SERIES AH5
FLEXIBLE HOSES: The flexible hose shall not be bent within
2 1/2 inches/64 mm of the connection nut at both ends.
Flexible Hose Bend Characteristics:
NOTE: For out-of-plane (three-dimensional) bends, care shall be
taken to avoid imparting torque on the flexible hose.
Minimum
Bend Radius
90°
Minimum
Bend Radius
I-VICFLEX.AB7
®
VicFlex
104l
With AB7
With AB7
With AB7
With AB7
With AB7
2X
Minimum
2X
Bend
Minimum
Radius
Bend
Radius
OR
OR
Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
I-VICFLEX.AB7_1
products.
Minimum
Bend Radius
Minimum
Bend Radius

Advertisement

loading
Need help?

Need help?

Do you have a question about the VicFlex AB7 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Victaulic VicFlex AB7

  • Page 1 Flexible Hose with Fittings for Fire Protection Service ® ™ Style AB7 Bracket WARNING • Read and understand all instructions before attempting to install any Victaulic ® VicFlex ™ products. • Wear safety glasses, hardhat, and foot protection. • These installation instructions are intended for an experienced, trained installer.
  • Page 2 These submittals are located in Sections authority having jurisdiction may have additional maintenance, 10 and 40 of the Victaulic G-100 Catalog or on the Victaulic testing, and inspection requirements that shall be followed. website at victaulic.com. In addition, when installing Victaulic FireLock ®...
  • Page 3 I-VICFLEX.AB7 / Victaulic VicFlex Style AB7 Bracket / Installation Instructions ® ™ STYLE AB7 BRACKET ASSEMBLY DRAWING Refer to pages 7 – 11 of this manual for bracket installation instructions. Item Description 24-inch/610-mm or 48-inch/1219-mm Square Bar* Center Gate Assembly with Wing Nut...
  • Page 4 If any of these conditions exist, • The flexible hose shall not be bent or fluctuated up-and-down or apply a thin coat of Victaulic lubricant or silicone lubricant to the side-to-side when it is pressurized for test.
  • Page 5 I-VICFLEX.AB7 / Victaulic VicFlex Style AB7 Bracket / Installation Instructions ® ™ GOOD ASSEMBLE JOINT: Assemble the joint by inserting the grooved end of the sprinkler piping into the opening of the coupling. The grooved sprinkler piping shall be inserted into the coupling until contact with the center leg of the gasket occurs.
  • Page 6 I-VICFLEX.AB7 / Victaulic VicFlex Style AB7 Bracket / Installation Instructions ® ™ CONNECTION TO THE SPRINKLER PIPING INSTALLATION OF THE SPRINKLER REDUCING USING AN ADAPTER NIPPLE AND A SERIES NIPPLE ONTO THE FLEXIBLE HOSE AH1, AH2, AH3, AH4, AH5, AH2-300, OR...
  • Page 7 Install the sprinkler by following the manufacturer’s installation assembly and into the ceiling grid. NOTE: A tamper-evident label is instructions. For Victaulic sprinklers, refer to the I-40 Victaulic ® available and can be applied to one or both of the end brackets.
  • Page 8 I-VICFLEX.AB7 / Victaulic VicFlex Style AB7 Bracket / Installation Instructions ® ™ INSTALLATION FOR WOOD JOISTS/STUDS INSTALLATION FOR ASTM C645 METAL JOISTS/ (FM ONLY) STUDS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS (FM ONLY) Install the flexible hose into the sprinkler piping and the sprinkler...
  • Page 9 I-VICFLEX.AB7 / Victaulic VicFlex Style AB7 Bracket / Installation Instructions ® ™ ALTERNATIVE WOOD JOIST/STUD INSTALLATION ALTERNATIVE METAL JOIST/STUD INSTALLATION (FM ONLY) (FM ONLY) Install the flexible hose into the sprinkler piping and the sprinkler Install the flexible hose into the sprinkler piping and the sprinkler...
  • Page 10 Coupling housings. Inspect all components for damage or wear. housings' keys engage with the spacer. If any damage or wear is present, replace with new Victaulic- supplied components. NOTE: Replacement gaskets shall be of the same grade that is suitable for the intended service.
  • Page 11 I-VICFLEX.AB7 / Victaulic VicFlex Style AB7 Bracket / Installation Instructions ® ™ TECHNICAL DATA FOR FLEXIBLE HOSES The following section provides friction loss information for flexible hoses that can be used with the Style AB7 Bracket. WARNING • It is the system designer’s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment.
  • Page 12 * 7-inch/178-mm minimum bend radius (tested with standard 5 3/4-inch/146-mm length straight reducer) # 3/4-inch/DN20 outlet data shown with K14.0 - For other K-factor friction loss data, refer to Victaulic submittal 10.95 § A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends (e.g.
  • Page 13 * 8-inch/203-mm minimum bend radius (tested with standard 5 3/4-inch/146-mm length straight reducer) # 3/4-inch outlet data shown with K14.0 - For other K-factor friction loss data, refer to Victaulic submittal 10.84 § A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends (e.g.
  • Page 14 * 7-inch/178-mm minimum bend radius (tested with standard 5 3/4-inch/146-mm length straight reducer) # 3/4-inch/DN20 outlet data shown with K14.0 - For other K-factor friction loss data, refer to Victaulic submittal 10.85 § A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends (e.g.
  • Page 15 * 4-inch/102-mm minimum bend radius (tested with standard 5 3/4-inch/146-mm length straight reducer) # 3/4-inch outlet data shown with K14.0 - For other K-factor friction loss data, refer to Victaulic submittal 10.89 § A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends (e.g.
  • Page 16 I-VICFLEX.AB7 / Victaulic VicFlex Style AB7 Bracket / Installation Instructions ® ™ SERIES AH1, AH1-CC, AH2, AH2-CC, AH3*, AND AH4 FLEXIBLE HOSE FRICTION LOSS DATA (VDS) Series AH1 and AH1-CC Series AH2 and AH2-CC Series AH3* Series AH4 Length of...
  • Page 17 I-VICFLEX.AB7 / Victaulic VicFlex Style AB7 Bracket / Installation Instructions ® ™ SERIES AH1 FLEXIBLE HOSE FRICTION LOSS DATA (CCCf) Equivalent Length – meters/feet Length of Flexible Hose Model mm/inches Straight Configuration Bend Configuration 4.78 5.80 AH1-31 15.7 19.0 5.59 10.15...
  • Page 18 For complete contact information, visit victaulic.com I-VICFLEX.AB7 6829 REV I UPDATED 01/2018 Z000AQUFLX VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND/OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND/OR OTHER COUNTRIES. © 2018 VICTAULIC COMPANY. ALL RIGHTS RESERVED.