Advertisement
eddi+ is a 3-phase energy regulator, with manual/automatic action for use with microgeneration systems. Excess energy from the microgeneration system is used to heat water or rooms rather than exporting it to the grid. Grid current sensors simply clip around the incoming cables. These sensors are used to monitor excess power so eddi+ can automatically adjust the voltage to connected heater. eddi+ can effectively balance excess power across all three phases. eddi+ utilises myenergi's proprietary varisine™ technology to ensure compliance with worldwide power grid standards.
Box Contents
Minimum Clearances
Connections
ELECTRIC SHOCK - An electric shock can be fatal; electrical connection work shall only be carried out by a competent person.
Supply
Supply cable shall meet the requirements of the local wiring regulations.
Strip 8mm insulation from conductors and insert into the terminals. The eddi+ should be connected to a 3-phase 230/400V AC 50Hz supply.
Loads
Only purely resistive loads shall be used with eddi+. The following criteria shall be observed:
Ethernet
If applicable, ensure Ethernet is inserted into the RJ45 port.
Phase Rotation
Phase Rotation is only used on three phase devices and should correspond to the wiring of the input terminals. Only the following specific options are available:
Device Limit
The maximum current that eddi+ will draw per phase (including when boosting). This is useful if the supply current is limited.
Grid Limit /Import Limit
The limit that can be drawn from the grid connection i.e. maximum import current or the main property fuse rating. This is a global limit so all paired myenergi devices will be included when limiting.
Third Party AC Battery
If the property has a static AC-coupled battery system installed, it's possible to get the eddi+ to operate as shown in the following table, provided a CT has been installed to monitor the battery inverter.
Setting | Function Description |
None | There is no battery system installed |
Limit to Gen | Will limit the output of the eddi+(except when boosting), to prevent unwanted draining of an AC coupled battery system. This setting does not require a CT to monitor the battery, but does need a CT to monitor the solar/wind generation. Note: This setting is to support legacy installations – it is preferable to install a CT to monitor the battery and use one of the settings below. |
Avoid Drain | Stops the eddi+ (or other linked myenergi devices) draining the battery when using surplus power from the solar or wind generator. |
Avoid Charge | Effectively allows the eddi+ (or other linked myenergi devices) to take priority over the battery when charging from solar or wind generation. |
Avoid Both | Provides both of the above functions. |
Net Phases
All meter readings from 3-phase myenergi devices will be netted. This means that surplus generation on ANY phase will be considered to be available for consumption on ANY other phase. T his will allow eddi+ to monitor the total grid export and import figures. You will need to net the three phases. To do this, in the eddi+ device menu, navigate to; Supply Grid > Net Phases and enable net phasing.
Exp Threshold
The amount of export that must be exceeded before eddi+ starts diverting power to the connected load. Once diverting starts, all the surplus power less the Export Margin (see below) will be diverted to the connected load.
Export Margin
Sets a minimum level of export power which is maintained when eddi+ is diverting surplus power to the heater. Normally Export Margin would be set to 0W (zero watts) and all available surplus will be diverted to the load, however, it is sometimes desired to have a minimum export level at all times.
Response Delay
Sets a delay before eddi+ starts to divert power (after the Export Threshold is exceeded). The default setting is 0s (zero seconds), however, if there is an AC-coupled battery storage system installed at the property, this may need to be increased.
Load Balancing/Current Limiting
CTs can also be used to limit the current drawn by myenergi devices to avoid overloading circuits; this is referred to as load balancing or load curtailment. There are four different ways to limit current and they can be used alone or combined for more complex situations.
Relays and eSense
eddi+ relays and eSense options allow for numerous wiring configurations and includes the following features:
The two relays can be independently set for several functions, or they can be set to operate as a pair.
The relay functions include:
The load can be 'boosted' to full power for a short period regardless of the amount of available export power, this function is called Manual Boost and is activated from the main screen. The boost can be cancelled at any time.
To activate;
To cancel:
To set;
Before leaving site, it is strongly recommended to perform a several checks to ensure that the sensors and heaters have been correctly installed and are functional.
If you experience any issues with your myenergi device, please visit our Help Centre by scanning the QR Code or clicking the link below.
support.myenergi.com/hc/en-gb
We recommend a routine observation of the eddi+. This should be carried out by a competent person and its main aim is to look for any signs of damage and abnormalities. This is a visual inspection only and should not entail removing cover or dismantling the eddi+ in any way.
Observational Inspection
Operating Environment
Full Maintenance Inspection
Cable, Terminal and Equipment Inspection
Electrical
Rated Supply Voltage (+/- 10%) | 3x 230/400V (3-Ph) |
Supply Frequency | 50Hz |
Rated Current | 16A |
Standby Power Consumption | 4W |
Generator Size Supported¹ | No limit |
Resistive Load Size | 150W min./9kW max. |
Wireless Interface³ | 868 / 915MHz (proprietary protocol) for wireless sensor and remote monitoring options |
Grid Current Sensor² | 100A max. primary current 16mm max. cable diameter |
Supply Cable Entry | Bottom Entry |
Temperature Sensor Inputs | 2x PT1000 |
eSense Input | 230V AC Sensing (2.5kV Isolated) |
Multifunction Relays | 2x 16A / 250V AC rated |
Mechanical
Dimensions (H x W x D) | 330 x 271 x 64mm |
Net Weight | 5.14Kg |
Protection Degree | IP20 |
Enclosure Material | Powder Coated Zintec Steel |
Operating Temperature | -20°C to +40°C |
Mounting Method | Wall Mounting Bracket |
Storage Temperature | -40 to 70°C |
EMC device class | Class B |
Overvoltage category | 3 |
Pollution Degree | 2 |
Performance
Power Control Technology | VariSine TM pure sine wave (Pulse Width Modulation) |
Outputs | 1x 9kW |
Cooling | Rear mounted passive cooled heatsink |
Indicators | RGB - refer to operation manual for details |
Display | Graphical LCD with LED backlight (Shows heating status and savings data) |
PWM Resolution | 0.1% |
Measurement Accuracy | +/- 1.5% typical |
Power Conversion Efficiency | 97.5% typical |
Mode of Operation | Type 1.B |
Compliance
RED 2014/53/EU, EMC 2014/30/EU, LVD 2014/35/EU. EN 60730-1, EN 61000-6-1, EN 61000-6-3, EN301 489-1, EN301 489-3, EN300 220-2. EN 300 228, EN 62311
Model Code
EDDI-16A3P02H
Read all the safety instructions. Failure to install and operate the eddi+ in accordance with these instructions may cause injury or death, damage to the unit or inefficient operation and invalidate the manufacturer's warranty.
Manual Keeping
This manual contains important information about operating the device. Before operating, please read it very carefully. The device should be operated in strict accordance with the instructions in this manual. This manual should be kept for future maintenance.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a notice or 'tip' to guide you.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the Eddi+ and is the answer not in the manual?
Questions and answers