Advertisement

Myenergi Eddi+ Manual

Introduction

eddi+ is a 3-phase energy regulator, with manual/automatic action for use with microgeneration systems. Excess energy from the microgeneration system is used to heat water or rooms rather than exporting it to the grid. Grid current sensors simply clip around the incoming cables. These sensors are used to monitor excess power so eddi+ can automatically adjust the voltage to connected heater. eddi+ can effectively balance excess power across all three phases. eddi+ utilises myenergi's proprietary varisine™ technology to ensure compliance with worldwide power grid standards.

Box Contents

Minimum Clearances

Connections
Connections

Installation

  1. Remove eddi+ from packaging.
  2. Place device on a flat surface, loosen the pozi-head captive screw (1) and lift cover off in a tilting motion.
     Installation - Step 1
  3. Loosen the two mounting bracket screws (2) and separate the bracket from the eddi+.
     Installation - Step 2
  4. Place the bracket against the wall of the chosen location and mark the holes ready for drilling and fixing.
    information Suitable fixings must be used dependant on application/mounting surface. To be determined by the installer.
  5. Pierce holes in grommets and pass all cables through and terminate to the corresponding terminals relative to the installation.


ELECTRIC SHOCK - An electric shock can be fatal; electrical connection work shall only be carried out by a competent person.

Supply
Supply cable shall meet the requirements of the local wiring regulations.
Strip 8mm insulation from conductors and insert into the terminals. The eddi+ should be connected to a 3-phase 230/400V AC 50Hz supply.

Loads
Only purely resistive loads shall be used with eddi+. The following criteria shall be observed:

  • Maximum rating of load: 3kW per phase
  • Minimum load rating: 150W
  • The load's neutral conductor shall be connected to the load output N terminal
  • No electronic controls shall be connected to the load terminals; mechanical thermostats only
  • No timers shall be connected to the load terminals, including mechanical timers

Ethernet
If applicable, ensure Ethernet is inserted into the RJ45 port.

  1. Fit CT(s) to live conductors as necessary, with arrow marked in direction of current flow.

    informationOnly one Grid CT (per phase) for the whole installation. Extending CT To extend the CT sensor cable, a single pair from a CAT5 cable may be used.
    Extending CT
    To extend the CT sensor cable, a single pair from a CAT5 cable may be used.
     Installation - Step 3
  1. Clamp all cables, using the cable clamps provided.
  2. Refit the eddi+ cover and tighten the pozi-head screw (1) to secure.
  3. Carry out all relevant tests and inspections in accordance with local regulations, before applying power.
  4. Once powered up, follow through the installation assistant set-up screens to configure the device settings. This will include setting a passcode to the Installer Settings Menu.

Installer Settings

Phase Rotation
Phase Rotation is only used on three phase devices and should correspond to the wiring of the input terminals. Only the following specific options are available:

  • 1/2/3 (Ph-1 to "L1", Ph-2 to "L2", Ph-3 to "L3")
  • 2/3/1 (Ph-2 to "L1", Ph-3 to "L2", Ph-1 to "L3")
  • 3/1/2 (Ph-3 to "L1", Ph-1 to "L2", Ph-2 to "L3")

Device Limit
The maximum current that eddi+ will draw per phase (including when boosting). This is useful if the supply current is limited.

Grid Limit /Import Limit
The limit that can be drawn from the grid connection i.e. maximum import current or the main property fuse rating. This is a global limit so all paired myenergi devices will be included when limiting.

Third Party AC Battery
If the property has a static AC-coupled battery system installed, it's possible to get the eddi+ to operate as shown in the following table, provided a CT has been installed to monitor the battery inverter.

Setting Function Description
None There is no battery system installed
Limit to Gen Will limit the output of the eddi+(except when boosting), to prevent unwanted draining of an AC coupled battery system. This setting does not require a CT to monitor the battery, but does need a CT to monitor the solar/wind generation.
Note: This setting is to support legacy installations – it is preferable to install a CT to monitor the battery and use one of the settings below.
Avoid Drain Stops the eddi+ (or other linked myenergi devices) draining the battery when using surplus power from the solar or wind generator.
Avoid Charge Effectively allows the eddi+ (or other linked myenergi devices) to take priority over the battery when charging from solar or wind generation.
Avoid Both Provides both of the above functions.

Net Phases
All meter readings from 3-phase myenergi devices will be netted. This means that surplus generation on ANY phase will be considered to be available for consumption on ANY other phase. T his will allow eddi+ to monitor the total grid export and import figures. You will need to net the three phases. To do this, in the eddi+ device menu, navigate to; Supply Grid > Net Phases and enable net phasing.

Exp Threshold
The amount of export that must be exceeded before eddi+ starts diverting power to the connected load. Once diverting starts, all the surplus power less the Export Margin (see below) will be diverted to the connected load.

Export Margin
Sets a minimum level of export power which is maintained when eddi+ is diverting surplus power to the heater. Normally Export Margin would be set to 0W (zero watts) and all available surplus will be diverted to the load, however, it is sometimes desired to have a minimum export level at all times.

Response Delay
Sets a delay before eddi+ starts to divert power (after the Export Threshold is exceeded). The default setting is 0s (zero seconds), however, if there is an AC-coupled battery storage system installed at the property, this may need to be increased.

Load Balancing/Current Limiting
CTs can also be used to limit the current drawn by myenergi devices to avoid overloading circuits; this is referred to as load balancing or load curtailment. There are four different ways to limit current and they can be used alone or combined for more complex situations.

Relays and eSense
eddi+ relays and eSense options allow for numerous wiring configurations and includes the following features:

  • Two independent relays rated at 250V AC, 16A.
  • eSense input (Range 3.3-230Vrms. Volt Free Contact; 24V DC Supplied from the zappi).
  • Two temperatures sensor inputs (PT1000)

The two relays can be independently set for several functions, or they can be set to operate as a pair.
The relay functions include:

  • Export Threshold
  • Import Threshold
  • Operate when heating
  • De-stratification pump control
  • Timed operation

Operations

Manual Boost

The load can be 'boosted' to full power for a short period regardless of the amount of available export power, this function is called Manual Boost and is activated from the main screen. The boost can be cancelled at any time.
To activate;

  1. From the main screen, press (+).
  2. Select "Boost to Max." or set a time duration.
  3. The boost duration may be altered by pressing the (↑) or (↓) arrows during the boost.

To cancel:

  1. Press the (+) button twice.

Boost Timer

To set;

  1. From the main screen, press ( ) to enter the Main Menu.
  2. Select Boost Timer, then press (+).
  3. Use the (↑) or (↓) arrow buttons to highlight the time slot you wish to change.
  4. Alter the start hour with the (↑) or (↓) arrow buttons and then press (+) to move to minutes.
  5. Edit the duration in the same way and then press (+) again to edit the days of the week you want the boost to be active for; each day of the week and can be toggled on/off with (↑) or (↓) arrow buttons, press (+) to go to the next day. Pressing (+) on the last day (Sunday) will confirm the boost time slot and the whole line will be highlighted again.
  6. Press ( ) to exit the BOOST TIMER screen.

Testing

Before leaving site, it is strongly recommended to perform a several checks to ensure that the sensors and heaters have been correctly installed and are functional.

  1. Test the heater by activating a manual boost by pressing (+) button, twice.
  2. Check the power reading on the screen for the load corresponds to the load rating or a previously set limit.
  3. Cancel the boost by pressing the ( ) button twice during the boost.

Help Centre

If you experience any issues with your myenergi device, please visit our Help Centre by scanning the QR Code or clicking the link below.

support.myenergi.com/hc/en-gb

Routine Maintenance & Cleaning

We recommend a routine observation of the eddi+. This should be carried out by a competent person and its main aim is to look for any signs of damage and abnormalities. This is a visual inspection only and should not entail removing cover or dismantling the eddi+ in any way.

Observational Inspection
Operating Environment

  • By sight only, carefully observe whether there are any signs of damage to the eddi+

Full Maintenance Inspection
Cable, Terminal and Equipment Inspection

  • Check for loose cable connections
  • Check for aging and/or damaged cables
  • Check for loosening of the cable terminal screws
  • Check for any signs of overheating

eddi+ Specification

Electrical

Rated Supply Voltage (+/- 10%) 3x 230/400V (3-Ph)
Supply Frequency 50Hz
Rated Current 16A
Standby Power Consumption 4W
Generator Size Supported¹ No limit
Resistive Load Size 150W min./9kW max.
Wireless Interface³ 868 / 915MHz (proprietary protocol) for wireless sensor and remote monitoring options
Grid Current Sensor² 100A max. primary current 16mm max. cable diameter
Supply Cable Entry Bottom Entry
Temperature Sensor Inputs 2x PT1000
eSense Input 230V AC Sensing (2.5kV Isolated)
Multifunction Relays 2x 16A / 250V AC rated

Mechanical

Dimensions (H x W x D) 330 x 271 x 64mm
Net Weight 5.14Kg
Protection Degree IP20
Enclosure Material Powder Coated Zintec Steel
Operating Temperature -20°C to +40°C
Mounting Method Wall Mounting Bracket
Storage Temperature -40 to 70°C
EMC device class Class B
Overvoltage category 3
Pollution Degree 2

Performance

Power Control Technology VariSine TM pure sine wave (Pulse Width Modulation)
Outputs 1x 9kW
Cooling Rear mounted passive cooled heatsink
Indicators RGB - refer to operation manual for details
Display Graphical LCD with LED backlight (Shows heating status and savings data)
PWM Resolution 0.1%
Measurement Accuracy +/- 1.5% typical
Power Conversion Efficiency 97.5% typical
Mode of Operation Type 1.B

Compliance
RED 2014/53/EU, EMC 2014/30/EU, LVD 2014/35/EU. EN 60730-1, EN 61000-6-1, EN 61000-6-3, EN301 489-1, EN301 489-3, EN300 220-2. EN 300 228, EN 62311

Model Code
EDDI-16A3P02H

Application Examples

  1. eddi+ fitted to a single cylinder with a single phase immersion heater.
    Application Examples - Part 1
    Key
  1. eddi+ three phase Solar Power Diverter
  2. 230/400V AC power supply
  3. Hot Water Storage Tank
  4. Single phase immersion heater
  5. 3kW Immersion heater
  6. Auxilary Gas Boiler
  7. Supplied PT1000 temperature sensor
  1. eddi+ fitted to a single cylinder with a three phase immersion heater.
    Application Examples - Part 2
    Key
  1. eddi+ three phase Solar Power Diverter
  2. 230/400V AC power supply
  3. Hot Water Storage Tank
  4. Three phase immersion heater
  5. 9kW Immersion heater internal view with Cylinder thermostat & thermal cut out
  6. Auxilary Gas Boiler
  7. Optional PT1000 temperature sensor

Safety

Read all the safety instructions. Failure to install and operate the eddi+ in accordance with these instructions may cause injury or death, damage to the unit or inefficient operation and invalidate the manufacturer's warranty.

Manual Keeping
This manual contains important information about operating the device. Before operating, please read it very carefully. The device should be operated in strict accordance with the instructions in this manual. This manual should be kept for future maintenance.
cautionIndicates a hazardous situation which, if not avoided, could result in death or serious injury.
informationIndicates a notice or 'tip' to guide you.

  • Only have the system installed and commissioned by qualified personnel with the appropriate skills.
  • Prior to performing any work on the eddi+, disconnect from all voltage sources, as described in this document.
  • Do not install or operate the system in potentially explosive atmospheres or areas of high humidity.
  • The unit must be installed indoors and should be mounted to a flat vertical surface or wall, in the vertical orientation only and using the dedicated mounting bracket which comes attached to the unit.
  • Do not install the unit in any environment of temperature below -20°C or over 40°C.
  • Suitable fixings must be used dependant on application/mounting surface. To be determined by installer.
  • The supply cord to/from this control can be replaced only by the manufacturer or his accredited service agent and shall conform to the requirements of EN 50525-2-11.
  • This device must be supplied by an upstream 3-pole 16A type A or B MCB or equivalent overcurrent device..
  • Only purely resistive loads must be connected to the eddi+ output terminals.
  • The unit is not to be used by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they are supervised or have been given instruction concerning use of the device by a person responsible for their safety.
  • The heat sink can exceed 70°C during normal operation, therefore do not touch.
  • Do not put any heavy objects on top of the system.
  • Do not damage the system with sharp objects.
  • Only use replacement parts supplied or recommended by myenergi. Replacing of parts must be carried out by a suitably qualified installer.
  • Under short-circuit conditions, the relays for heaters/outputs 2 and 3 may weld. If power to the device can not be reinstated at the upstream MCB, please consult your installer for repair or replacement options.


  • Ensure the device always has adequate ventilation; do not block the vents or obstruct airflow at the back or sides of the unit.
  • The earth conductor must be correctly installed and reliably connected.
  • Do not touch the system with wet hands.
  • Do not wipe the system with a damp cloth.

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Myenergi Eddi+ Manual

Advertisement

Need help?

Need help?

Do you have a question about the Eddi+ and is the answer not in the manual?

Questions and answers

Table of Contents