MR-HPHD-1C High Performance Vector Control Frequency Converter Thank you for your select and use our MR-HPHD-1C series frequency converter products. Please read this specification carefully before use to make ensure that correct and safety use this product. Please must read [Safety notices] carefully before use.
Chapter 1 Product information Safety information and notices ................01 Naming rules ......................01 MR-HPHD-1C Series converter series index ............02 Product profile figure and installation hole size ............. 02 Chapter 2 Electric installations Main electric circuit terminals and wiring.............. 04 Chapters Operating display Operating and display interface instruction............
MR-HPHD-1C High Performance Vector Control Frequency Converter Chapter 1 Product information 1.1 Safety information and notices Safety definition: the safety notices in this manual divided into the below two types: 4 Danger: the danger caused by that operation not according to requirements maybe caused serious hurt, even though dead;...
MR-HPHD-1C-D75G3 0.75 0.75 MR-HPHD-1C-1D5G3 MR-HPHD-1C-2D2G3 MR-HPHD-1C-004G3 MR-HPHD-1C-5D5G3 MR-HPHD-1C-7D5G3 MR-HPHD-1C-011G3 11.0 MR-HPHD-1C-015G3 15.0 MR-HPHD-1C-018G3 18.0 Table 1-1 MR-HPHD-1C Series converter model and technical data 1.4 Product profile figure and installation hole size Schematic diagrams of the dimensions of the frequency converter...
Page 7
MR-HPHD-1C High Performance Vector Control Frequency Converter 1.4.1 Operation panel shape Model Type Outsize (mm) Outsize (mm) Mounting hole (d) MR-HPHD-1C-D40G1 MR-HPHD-1C-D75G1 MR-HPHD-1C-1D5G1 MR-HPHD-1C-2D2G1 197.2 89.6 Φ5 MR-HPHD-1C-D75G3 MR-HPHD-1C-1D5G3 MR-HPHD-1C-2D2G3 MR-HPHD-1C-004G3 Φ5.6 MR-HPHD-1C-5D5G3 MR-HPHD-1C-7D5G3 242.5 169.5 108.5 Φ6.4 MR-HPHD-1C-011G3 MR-HPHD-1C-015G3 206.2 278.5 Φ7...
MR-HPHD-1C High Performance Vector Control Frequency Converter Chapter 2 Electric installations 2.1 Main electric circuit terminals and wiring 1)Frequency converter main circuit terminal instruction: Terminal marks Name Instruction Connection point of three-phase 380V R.S.T/L.N Power supply input terminals /single-phase 220V AC power supply Brake electric resistance P+.PB Connect brake electric resistance...
Page 9
MR-HPHD-1C High Performance Vector Control Frequency Converter 2.1.3 Control terminals instruction The control circuit terminals layout diagram shown as the below: Fig 2-4 MR-HPHD-1C (isolated version) control circuit terminal layout...
Page 10
MR-HPHD-1C High Performance Vector Control Frequency Converter 2.1.4 Control terminal function instruction: Terminal Terminal Category Function instruction symbol name Generally, 150mA (with short circuit protection) used as the working power supply of outer connect Outer connect electric potential device, electric potential device 10V-GND 10V power electric resistance value range: lkQ 〜5kQ...
Page 11
MR-HPHD-1C High Performance Vector Control Frequency Converter X1-GND Digit input 1 HDI still can be as high speed pulse input X2-GND Digit input 2 passageway except the characteristics of XI- X3-GND Digit input 3 The highest input frequency: 50kHz Digit Input impedance: lkQ input X4-GND...
MR-HPHD-1C High Performance Vector Control Frequency Converter Chapters Operating display 3.1 Operating and display interface instruction Able to process the operations such as modify the function parameters of frequency converter, monitor working status of frequency converter and control frequency converter running (start and stop) through operating panel, the profile and function area shown as the below diagram: Fig 3-1 Schematic diagram of operation panel...
Page 13
MR-HPHD-1C High Performance Vector Control Frequency Converter 1) Function indicate lamp instruction: ◊ RUN: lamp extincted means the frequency converter be at stop machine status, lamp lighting means the frequency converter be at running status. L/R extincted Panel start-stop control L/R normally lighting Terminal start-stop control L/R flashing...
Page 14
MR-HPHD-1C High Performance Vector Control Frequency Converter 4)Keyboard button description table Keys Key name Key function Programming Level 1 menu enter into or withdraw Confirm key Level to level enter into menu tableau, confirm setting ENTER parameters Progressively ▲ Data or function code progressively increase increase key Progressively ▼...
MR-HPHD-1C High Performance Vector Control Frequency Converter Chapter4 Function parameters table 4.1 Bask function parameters simple table “☆” : means the setting value of this parameter in frequency converter be at stop machine and running status, all can be modified; “★”...
Page 16
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range factory Property address code value 0: Digit setting (preset frequency P0-08,UP/DOWN able to be modified, not memory when power off) 1: Digit setting (preset frequency P0-08,UP/DOWN able to be modified, memory when power Main off)
Page 17
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory code address value Frequency source Y 0:opposite to the max frequency ☆ range select P0-05 61445 1:opposite to frequency source X when overlaying Frequency...
Page 18
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range factory Property address code value 0.00Hz 〜the max frequency Preset ☆ P0-08 50.00Hz 61448 frequency (P0-10) Running 0: accordance direction ★ P0-09 61449 direction 1: opposite direction 50.00Hz 〜320.00Hz (P0-22=2) The max 50.00Hz ★...
Page 19
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Function Leave factory Name Setting range Property code address value Accelerate P0-17 61457 timel 0s ~ 65000s (P0-19=0) Model 0.0s 〜6500.0s (P0-19=l) ☆ confirmation 0.00s ~ 650.00s (P0-19=2) Moderate time P0-18 61458...
Page 20
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range factory Property address code value The unit: operating panel order binding frequency source select 0:no binding 1: digit setting frequency 2: All 3:AI2 4: keyboard electric potential Order source 5: HDI pulse setting (X5) binding 6: multiply section speed...
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Fl group-motor parameters Function Name Setting range Property Leave factory code address value 0:General Order source asynchronous motor ★ P1-00 61441 select 1:frequency converter asynchronous motor Motor rated Model 0.1 〜1000KW ★...
Page 22
MR-HPHD-1C High Performance Vector Control Frequency Converter P2 group-vector parameters Function Name Setting range Property Leave factory address code value Speed ring ratio gain ☆ P2-00 1-100 61952 Speed ring integral 0.01 〜10.00s ☆ P2-01 0.50s 61953 timel ☆ P2-02 Shift frequency 1 0.00-P2-05 5.00Hz...
Page 23
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table P2 group-vector parameters Function Name Setting range Property Leave factory code address value Speed ring 0.01s 〜10.00s ☆ P2-04 integral time 2 1.00s 61956 Shift frequency P2-02 ~ The max ☆...
Page 24
MR-HPHD-1C High Performance Vector Control Frequency Converter Function Name Setting range Property Leave factory address code value 0:function code P2-10 setting l:AI1 2: AI2 3:keyboard electric Torque up limit source under potential ☆ P2-09 61961 speed control 4:PULSE pulse setting method 5:communication setting 6: MIN (Al012)
Page 25
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Function Name Setting range Property Leave factory code address value Torque 0 〜60000 ☆ P2-15 adjustment ratio 2000 61967 gain Torque 0 〜60000 ☆ P2-16 adjustment 1300 61968 integral gain Speed ring...
Page 26
MR-HPHD-1C High Performance Vector Control Frequency Converter P3 group-V/F control parameters Function Name Setting range Property Leave factory address code value 0:line\^F 1:multiply points V/F 2:square V/F 3:1.2 power VF curve ★ P3-00 62208 setting V/F 4:1.4 power V/F 6:1.6 power V/F 8:1.8 power V/F 9~ll:remain 0.0%: (automatic torque Model...
Page 27
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Function Name Setting range Property Leave factory address code value Multi points VF ★ P3-08 0.0% ~ 100.0% 100.0% 62216 voltage point 3 speed difference 0.0% 〜200.0% ☆...
Page 28
MR-HPHD-1C High Performance Vector Control Frequency Converter P4 group-input terminal Leave Function Name Setting range Property factory address code value 0:no function l:forward running (FWD) 2:reverse running (REV) 3:three line type running control terminal ★ P4-00 62464 4:forward crawl (FJOG) function 5:reverse crawl (RJOG) 6:terminal select...
Page 29
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory address code value 30:HDI pulse frequency input(X5) 31:Remain 33:Outer failure normally close X4 terminal input ★ function 34:Frequency modification enable P4-03 62467 select...
Page 30
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value Terminal 0.001Hz/s 〜65.535Hz/s ☆ UP/DOWNN P4-12 1.00Hz/s 62476 change ratio Min in put of ☆ P4-13 0.00V-P4-15 O.OOv 62477 AI curve 1 Min input corresponding -100.0% 〜+100.0% ☆...
Page 31
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory code address value Min input corresponding -100.0% 〜+100.0% ☆ P4-19 0.0% 62483 setting of AI curve 2 Max input of P4-18 〜+10.00V ☆...
Page 32
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value Max input of P4-23 〜+10.00V ☆ P4-25 10.00V 62484 AI curve3 Max input corresponding ☆ P4-26 -100.0%— +100.0% 100.0% 62485 setting of AI curve3 AI3 filter 0.00s 〜10.00s...
Page 33
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory address code value Max input -100.0% 〜100.0% ☆ setting of HDI P4-31 100.0% 62495 pulse HDI pulse 0.00s 〜10.00s ☆ filter wave P4-32 0.10s...
Page 34
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value 0:high electric level valid 1:low electric level valid Terminal X The unit:Xl ☆ P4-35 valid mode 00000 62498 Decade: X2 select 1 Hundreds: X3 Kilobit: X4 Myriabit: X5 Al input...
Page 35
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table P5 group-output terminal Leave Function Name Setting range Property factory code address value 0:high speed pulse output HDO terminal (HD0) ☆ output mode P5-00 62720 l:terminal switch quantity select output (FMR) 0:no output l:frequency...
Page 36
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value 19:lack voltage status output 20:communication setting 23:zerospeed running2 (also output when stop machine) 24:accumulate power on time Electric relay arrived RY2 function ☆ P5-03 25:frequency level tested FDT2 62723...
Page 37
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory code address value HDO high 0:running frequency l:setting speed pulse frequency 2:output current ☆ output P5-06 62726 3:output torque 4:output power function 5:output voltage 6:HDI pulse select...
Page 38
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value RY1 delay 0.0s 〜6553.5s ☆ P5-18 0.0s 62738 close time RY2 delay ☆ P5-19 0.0s ~ 6553.5s 0.0s 62739 close time Y1 delay 0.0s 〜6553.5s ☆...
Page 39
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table P6 group-start and stop control Leave Function Name Setting range Property factory code address value 0:directly start l:speed tracing ☆ P6-00 Start method 62976 and restart 2:pre-excitation start (AC asynchronous motor) 0:startfrom stop machine Speed tracing...
Page 40
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value 0:line accelerate and moderate l:Curve S accelerate and Accelerate and moderate A ★ moderate P6-07 62983 2:Curve S accelerate and method moderate B Curves start ★...
Page 41
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table P7 group-keyboard and display Leave Function Name Setting range Property factory code address value 0:MFK invalid l:operate panel order passageway and remote order passageway (terminal order passageway or communication MFKkey order passageway) shift function...
Page 42
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value 0000 〜FFFF BitOO:PID feedback BitOkPLC stage Bit02:HDI input pulse frequency (kHz) Bit03:running frequency 2 (Hz) Bit04:rest running time Bit05:voltage before All correct Bit06:voltage before AI2 correct LED running Bit07:Voltage before correction of ☆...
Page 43
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory address code value 0000 〜FFFF BitOO:setting frequency (Hz) BitOkbus line voltage(V) BitO2:X in put status BitO3:Y output status BitO4:All voltage (V) LED stop Bit05:AI2voltage(V) machine...
Page 44
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value Accumulate 0 〜65535h P7-13 63245 power time Accumulate power 0 〜65535kW P7-14 63246 consumption quantity Digit tube 2 stop 00 〜75 ☆ P7-17 machine monitor 63249 select...
Page 45
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table P8 group-assist function Function Leave factory Name Setting range Property code value address Crawl 0.00Hz 〜The max ☆ P8-00 2.00Hz 63488 running frequency frequency Crawl ☆ P8-01 accelerate 0.0s—...
Page 46
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value Jump frequency ☆ 0.00Hz ~ The max frequency 0.00Hz P8-09 63497 0.00Hz 〜The max Jump frequency ☆ P8-10 0.00Hz 63498 frequency Running mode 0:runningatdown limit when setting ☆...
Page 47
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory code address value Frequency 0.0% 〜100.0% ☆ P8-21 arrived test 0.0% 63509 (The maxfre-quency) out width Accelerate time lan accelerate 0.00Hz 〜The max frequency ☆...
Page 48
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value Any arrived 0.0% 〜100.0% (The frequency test ☆ P8-31 0.0% 63519 out width 1 max frequency) Any arrived 0.00Hz 〜The max frequency ☆ P8-32 frequency test 50.00Hz...
Page 49
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory code address value Any arrived current 1 0.0% 〜300.0% ☆ P8-39 0.0% 63527 width (motor rated current) 0.0% 〜300.0% Any arrived ☆...
Page 50
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value All input voltage P8-45 〜11.00V ☆ P8-46 6.80V 63534 protection value up limit Module ☆ temperature P8-47 (TC~100°C) 75° C 63535 arrived Fan control 0:fan rotating when running ☆...
Page 51
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table P9 group-failure and protection Function Leave factory Name Setting range Property code value address Motor overload ☆ P9-00 0:forbid hallow 63744 protection select Motor overload 0.20 〜10.00 ☆...
Page 52
MR-HPHD-1C High Performance Vector Control Frequency Converter Function Leave factory Name Setting range Property code value address Fault auto reset ☆ P9-09 0~20 63753 times Fault auto reset 0: No action ☆ P9-10 63754 FAULT DO selection 1: action Fault auto reset ☆...
Page 53
MR-HPHD-1C High Performance Vector Control Frequency Converter P9 group-assist function Function Leave factory Name Setting range Property address code value Frequency converter P9-42 63786 status at first time failure Power on time at first P9-43 63787 time failure Running time at first time P9-44 63788...
Page 54
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory code address value 0.0% 〜100.0% Abnormal reserve (100.0%corresponding the max P9-55 100.0% 63799 frequency frequency P0-10) Action select 0:invalid l:moderate 2: mode when moment P9-59 rate to stop machine...
Page 55
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value Loss load 0:invalid ☆ protection P9-63 63807 1:valid select Loss load test 0.0 〜100.0% ☆ P9-64 10.0% 63808 level Loss load test 0.0 〜60.0s ☆...
Page 56
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table PA group -PID function Function Leave factory Name Setting range Property address code value 0:PA-01 setting l:All 2:AI2 3:keyboard electric potential ☆ 4:HDI input pulse PA-00 PID setting source 64000 setting(X5) 5:communication...
Page 57
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value Differential 0.000 〜10.000s ☆ PA-07 0.000s 64007 timeTdl PID return ☆ PA-08 0.00 ~ The max frequency 0.00Hz 64008 stop frequency PID tolerance 0.0 〜100.0% ☆...
Page 58
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory code address value 0:not shift l:shiftthrough terminal X PID parameter ☆ PA-18 64018 shift condition 2:automatically shift according to tolerance PID parameter ☆...
Page 59
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value The unit: integral separate 0:invalid l:valid PID integral Decade: whether stop integral ☆ PA-25 64025 property after output arrived limit value Oxontinue integral l:stop integral 0.0%:not judge the feedback PID feedback...
Page 60
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Pb group-swing frequency, fix length and counting Function Leave factory Name Setting range Property address code value 0:oppositetothe Swing frequency center frequency Pb-00 setting method l:oppositetothe max frequency Swing frequency ☆...
Page 61
MR-HPHD-1C High Performance Vector Control Frequency Converter Pc group-multi section order and simple and easy PLC Function Leave factory Name Setting range Property address code value Multi section -100.0% 〜100.0% ☆ PC-00 0.0% 64512 order 0 Multi section -100.0% 〜100.0% ☆...
Page 62
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory code address value Single digit: power down memory selection 0:no power Simple PLC power down ☆ PC-17 64529 memory down memory selection l:powerdown memory Ten digits: stop memory selection...
Page 63
MR-HPHD-1C High Performance Vector Control Frequency Converter Leave Function Name Setting range Property factory address code value 3 section accelerate ☆ and moderate time of PC-25 0〜3 64537 simple and easy PLC 4 section running time ☆ PC-26 of simple and easy 0.0s (h)〜6553.5s (h) 0.0s(h) 64538 4section accelerate...
Page 64
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Leave Function Name Setting range Property factory address code value Selection of acceleration and deceleration time of ☆ PC-33 0〜3 64545 the 7th section of simple Run time unit of simple 0:s (second) ☆...
Page 65
MR-HPHD-1C High Performance Vector Control Frequency Converter Pd group-communication parameters Leave Function Name Setting range Property factory address code value 0:300BPS 5: 9600BPS 1: 600BPS 6:19200BPS 2:1200BPS ☆ Pd-00 Baud rate 7:38400BPS 64768 3:2400BPS 4:4800BPS 8: 57600BPS ☆ Pd-01 Data format 64769 This machine ☆...
Page 66
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table PP group-function code management Function Leave factory Name Setting range Property address code value ☆ PP-00 User password 0~ 65535 00000 7936 0:no operation 01:recover leave factory parameters, ★...
Page 67
MR-HPHD-1C High Performance Vector Control Frequency Converter A5 group-control optimize parameters Function Leave factory Name Setting range Property address code value 5.00Hz 〜The max DPWM shift up ☆ A5-00 8.00Hz 42240 limit frequency frequency O:asynchronous PWM modulate ☆ A5-01 42241 modulate l:syn method modulate...
Page 68
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table UO group-monitor parameters table Function Leave factory Name Setting range Property code value address U0-00 Running frequency (Hz) 0.01Hz 28672 U0-01 Setting frequency (Hz) 0.01Hz 28673 U0-02 Bus line voltage (V) 0.1V 28674...
Page 69
MR-HPHD-1C High Performance Vector Control Frequency Converter Function Leave factory Name Setting range Property address code value U0-13 Length value 28685 U0-14 Load speed display 28686 U0-15 PI D setting 28687 U0-16 RID feedback 28688 U0-17 PLC stage 28689 HDI input pulse frequency U0-18 0.01kHz 28690...
Page 70
MR-HPHD-1C High Performance Vector Control Frequency Converter 4.1 Basic function parameters simple table Function Leave factory Name Setting range Property code value address U0-27 28699 HDI input pulse frequency Communication setting U0-28 0.01% 28700 value U0-30 0.01Hz 28702 Main frequency X display Assist frequency Y U0-31 0.01Hz...
Page 71
MR-HPHD-1C High Performance Vector Control Frequency Converter Function Leave factory Name Setting range Property address code value U0-45 Failure information 28717 U0-59 Setting frequenc (%) 0.01% 28731 U0-60 Runningfrequen (%) 0.01% 28732 Frequency converter U0-61 28733 status U0-62 Current failure code 28734 U0-65 Torque up limit...
Chapters Failure diagnose and policies 5.1 Failure alarm and policies MR-HPHD-1C Series frequency converter total has 32 items warning information and protection function, protection function act once happen failure, frequency converter stop output, frequency converter failure electric relay contact act and indicate failure code on the frequency converter display panel.
Page 73
MR-HPHD-1C High Performance Vector Control Frequency Converter Failure Failure reason one by one Failure name Failure treatment policies code check 1. Frequency converter output circuit existing grounding or l.Solve outer failure short circuit 2. Process motor parameter 2. Control method is vector identification and not process parameter 3.
Page 74
MR-HPHD-1C High Performance Vector Control Frequency Converter 5.1 Failure alarm and policies Failure Failure reason one by one Failure name Failure treatment policies code check 1. Frequency converter output circuit existing grounding or short circuit l.Solve outer failure 2. Control method is vector 2.
Page 75
MR-HPHD-1C High Performance Vector Control Frequency Converter Failure Failure reason one by one Failure name Failure treatment policies code check 1. Adjust the voltage to normal 1. Higher input voltage range Constant speed 2. Existing outer force drive 2. Cancel this outer power or Err07 over voltage motor to run during running...
Page 76
MR-HPHD-1C High Performance Vector Control Frequency Converter 5.1 Failure alarm and policies Failure Failure reason one by one Failure name Failure treatment policies code check Abnormal three phase l.Check and solve the existing input power supply problems in outer circuit 2.Seeking Abnormal drive board Input lack for technical support 3.Seeking for...
Page 77
MR-HPHD-1C High Performance Vector Control Frequency Converter Failure Failure reason one by one Failure name Failure treatment policies code check 1. Abnormal host computer Check host computer working wiring 2. Abnormal communication 2. Checkcommunication wiring Communication wire 3. Correctly set communication Err16 failure 3.
Page 78
MR-HPHD-1C High Performance Vector Control Frequency Converter 5.1 Failure alarm and policies Failure Failure reason one by one Failure name Failure treatment policies code check Grounding Err23 l.Motor grounding short circuit 1.Renewal cable or motor short circuit failure Accumulated l.Use parameter initialize l.Accumulated running time runningtime Err26...
Page 79
MR-HPHD-1C High Performance Vector Control Frequency Converter Failure Failure reason one by one Failure name Failure treatment policies code check l.Whether too big load or l.Reduce load and check the motor Wave tracing happen motor blocked and mechanical situation and limit Err40 2.Smaller frequency converter 2,Select more bigger power grade...
Page 80
MR-HPHD-1C High Performance Vector Control Frequency Converter 5.2 Common failure and solve methods The frequency converter maybe meeting the below failure situation during use, please process simple failure analyse refer to the below methods. Failure Possible reason Solve method appearance No power grid voltage or too low;...
Page 81
MR-HPHD-1C High Performance Vector Control Frequency Converter Failure Possible reason Solve method appearance Power on indication normal, Fan damaged or blocked; Renewal fan; indicate after Outer control terminal wiring Solve the outer short circuit failure; running and short circuit; Seeking factory service; stop machine immediately Too high carriage frequency...
5. The Product Warranty Card is not re-issued. Please keep the card and present it to the maintenance personnel when asking for maintenance. 6. If there is any problem during the service, contact Mactrol-Refu Pvt. Ltd.’s agent or Mactrol-Refu Pvt. Ltd. directly.
Page 83
MR-HPHD-1C High Performance Vector Control Frequency Converter Thanks for choosing MACTROL product. Any technique support, please feel free to contact our support team Tel: 0120-4557924-30, Fax: 0120-4155384, Mobile: 9811078752, 9871124663 URL: www.mactrol.org Email: hsb@mactrol.org sales@mactrol.org...