Dear Client,
Thank you for Purchasing our HTFDK-300V/100A
Voltage Battery Discharge Tester. Please read the manual in detail
prior to first use, which will help you use the equipment skillfully.
products continually, so there may be slight
differences between your purchase equipment and its
instruction manual. You can find the changes in the appendix.
Sorry for the inconvenience. If you have further questions,
welcome to contact with our service department.
may bring voltage, when you plug/draw the test wire
or power outlet, they will cause electric spark. PLEASE CAUTION
RISK OF ELECTRICAL SHOCK!
Our aim is to improve and perfect the company's
The input/output terminals and the test column
1
Wide

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HTFDK-300V/100A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Wuhan Guide HTFDK-300V/100A

  • Page 1 Dear Client, Thank you for Purchasing our HTFDK-300V/100A Wide Voltage Battery Discharge Tester. Please read the manual in detail prior to first use, which will help you use the equipment skillfully. Our aim is to improve and perfect the company's...
  • Page 2  SERIOUS COMMITMENT All products of our company carry one year limited warranty from the date of shipment. If any such product proves defective during this warranty period we will maintain it for free. Meanwhile we implement lifetime service. Except otherwise agreed by contract. ...
  • Page 3 shock, the grounding conductor must be connected to the ground. Make sure the product has been grounded correctly before connecting with the input/output port. Pay Attention to the Ratings of All Terminals To prevent the fire hazard or electric shock, please be care of all ratings and labels/marks of this product.
  • Page 4: Security Terms

    -Security Terms Warning: indicates that death or severe personal injury may result if proper precautions are not taken Caution: indicates that property damage may result if proper precautions are not taken.
  • Page 5: Table Of Contents

    Contents I. An overview ..................6 II. Performance characteristics ............7 III. Technical indicators ................ 9 IV. Instrument appearance ..............10 V. Operation Setting Method ............. 11 VI.This section describes the system management interface ..18 VII. Maintenance and after-sales service ........20...
  • Page 6: An Overview

    I. An overview This product is a professional test instrument designed according to the national DL/T 1397.2-2014 power DC power supply system test equipment general technical conditions Part Battery capacity discharge tester test and maintenance regulations. Applicable to substation, converter station, power plant and other power engineering, DC power supply, DC power supply equipment equipped with battery pack capacity testing.
  • Page 7: Performance Characteristics

    battery load tester, etc. II. Performance characteristics Large screen: The instrument is operated by a 7-inch high-definition 1024*600 capacitor touch screen, and the interface can be operated directly by fingers. 2 Storage: Data can be stored in 8GB internal storage or external USB flash drive.
  • Page 8 real-time current, battery capacity, single battery voltage, discharge time and other data; 6 Real-time protection: During the test, if the whole group or single battery is abnormal or the tester works abnormally, the tester will automatically terminate the test to protect the battery. 7 strong anti-interference ability: under severe interference conditions, the last bit of the LCD screen data can be stable in the range of ±1 word, stable reading, good repeatability.
  • Page 9: Technical Indicators

    PC control, micro printer, Beidou GPS positioning. III. Technical indicators Applicable to battery 10V-300V string specifications The whole range of 0~300V voltage measurement Whole group voltage 0.01V resolution Voltage test accuracy 0.5% 10-19V:0~50A Constant current range 19-180V:0~100A 180-300V:0-50A Constant current 10-300V voltage range Discharge current...
  • Page 10: Instrument Appearance

    Input-enclosure: 2200Vdc 1min; Input-output: Withstand voltage test 2200Vdc 1min; Output - Enclosure: 700Vdc 1min security EN610950 The weight of the about45KG size 620x360x1050 IV. Instrument appearance Different current, voltage, appearance volume slightly different...
  • Page 11: Operation Setting Method

    V. Operation Setting Method 1 Cable Connection Safety 5.1.1 Locate the positive and negative battery string terminals onsite, and turn off the battery string output switch. 5.1.2 Wiring before test should be done in the order of "instrument first, then battery", that is, connecting the connection of the instrument end first, then the connection of the battery end.
  • Page 12 built-in buzzer will sound) 5.2.2 Connect the "whole voltage" of the tester to the total positive and negative terminals of the battery string with the whole voltage collection line. Note: The "positive" (red clip) of the whole battery line is connected to the positive terminal of the battery string, and the "negative"...
  • Page 13 5.3.1 Parameter Settings (Default 48-V System sample) Rear power button Power on to enter the main screen, the main setting screen device Figure 5.3.1 Main Parameter setting interface ※Group type:Set this parameter based on the battery string voltage. (Multiple voltage types of test instruments, must be strictly according to the battery input selection) ※Single type:Nominal voltage of a single battery。...
  • Page 14 battery。 ※Sort NO1:The limit switch is disabled by default ※Consistent:The limit switch defaults to constant current。 ※To number:The limit switch cannot be activated ※Single switch:The restriction function is disabled by default Termination of the set ※Group limit : After discharge, the battery pack voltage lower limit terminates。...
  • Page 15 5.3.2Start test screen Figure 5.3.2 Preparing the test data interface After setting field parameters, check whether the cable connection is complete. Close the air switch and click the start button. The internal cooling fan starts to run. At this point, the pause button can be moved, and the end button can be moved.
  • Page 16 ※When the whole set of lower limit value reaches the set value, the machine will stop automatically. 5.3.3Stop discharge state ※ Manual termination, section number or reach the termination condition, the tester to stop discharge (instrument fan for 20S heat dissipation, at this time do not turn off the power supply of the instrument, so as not to cause damage to the instrument)! The data view and return screen is displayed.
  • Page 17 Figure 5.3.3 Entering the page for viewing Data 5.3.4 Demolition of wiring ※ Test completed, the first step air switch, turn off the main engine. Turn off the power supply of the tester and remove the cable connection. When removing the cable,...
  • Page 18: Vi.this Section Describes The System Management Interface

    first remove the cable connection with the battery and then remove the cable connection with the instrument. ※ Field device recovery。 5.3.5Data export interface and desktop software Before the test is shut down, if you need the software of the upper computer on the desktop of the computer to export the report, insert the standard USB disk, click data management to select the desired file or select all, and click the USB disk to export。...
  • Page 19 2.Parameter protectection Over voltage:Generally, the device does not work beyond this voltage value by default。 Over current:Generally, it is the upper limit of current stabilization that is 10% higher than the sensor specifications in the device。 Storage interval:The storage interval of real-time discharge data is generally 1 minute。...
  • Page 20: Maintenance And After-Sales Service

    acquisition box。 Monomer number: Change the wireless acquisition box frequency band. (If the wireless single collection box is configured, it can be used in emergency situations but not in general) 6.5.About: type: Voltage refers to a description of the range of voltage values available to the machine。...
  • Page 21 Check whether the discharge switch is closed. ※ The discharge current is normal during discharge, but the voltage does not drop. The battery is not separated from the UPS charging system. The total voltage of the total voltage collection line is not connected, or is connected in reverse, or there is a broken line in the middle of the collection line.
  • Page 22 In case of failure or damage caused by force majeure (such as fire, flood, natural disaster, etc.). Failure or damage caused by random connection of other equipment not according to the instructions. 7 Faulty products without product warranty card and unable to confirm that the instrument is within the warranty period.