OPERATING MANUAL
STATYS
200 - 1800A Cabinet and Integrable Frame
Socomec Resources Center
To download, brochures, catalogues
and technical manuals
EN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the STATYS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for socomec STATYS

  • Page 1 OPERATING MANUAL STATYS 200 - 1800A Cabinet and Integrable Frame Socomec Resources Center To download, brochures, catalogues and technical manuals...
  • Page 3 WARRANTY CERTIFICATE SAFETY PROCEDURES 2. 1. oreword 2. 2. recautions 2. 3. lectrical risk 2. 4. isk oF Power cut THE ROLE OF STATYS OPERATING PRINCIPLE OPERATING MODES 5. 1. anual transFer 5. 2. utoMatic transFer 5. 3. (atsM) dvance...
  • Page 4: Warranty Certificate

    The warranty terms and conditions are stipulated in the offer, by default the following clauses apply. The SOCOMEC warranty is strictly limited to the product(s) and does not extend to equipment which may be integrated with this/these product(s), nor the performance of such equipment.
  • Page 5: Safety Procedures

    2. 1. F oreword Thank you for choosing the STATYS Static Transfer System from SOCOMEC. This equipment complies with the IEC 62310-2 product standard concerning Static Transfer Systems (STS). This equipment conforms to the EC directives applicable to this type of product. This conformity is indicated by the CE mark: 2.
  • Page 6: Operating Principle

    3. THE ROLE OF STATYS The role of STATYS is to monitor the alternate source, to detect any failure of the preferred source and, if this should occur, to ensure that the load is automatically transferred to the alternate source.
  • Page 7: Operating Modes

    If the alternate source is unavailable (or if the voltage exceeds the preset tolerances), the transfer function is inhibited. STATYS raises an alarm to warn the operator that the transfer is no longer possible. Automatic return from the alternate source back to the preferred source may also occur following a manual transfer.
  • Page 8 However if a significant part of the load is composed by magnetic elements (typicaly when there is a transformer between STATYS and the loads) there is a risk of inrush in case of transfer. In this case ATSM fonction must be ac- tivated (ATSM fonction see 5.3).
  • Page 9: Functional Diagrams

    STATYS Q50-1** Q50-2** STATYS Load Load * = optional ** = Q51 and Q52 for STATYS 800/1000A LEGENDS: Source 1 input switch*, Source 2 input switch*, Output switch*, Inverter, for source 1 or 2 maintenance bypasses*, Static Switch 1, Static Switch 2,...
  • Page 10: Mimic Panel

    • programming of the device (in PROG mode) – 13 LEDS indicating: • the different operating states • the mimic panel showing the power flow • the system's current mode – 6 keys used for system management. STATYS 200-1800A - 552184A_EN...
  • Page 11: M Eaning Of Leds

    ImIC pANel 7. 2. M eaning oF leds BLINKING Load supplied by STATYS Output shutdown imminent Output not supplied by STATYS Output supplied directly by source 1 Output supplied directly by source 2 General Alarm Critical alarm No alarm active...
  • Page 12 In CONTROL mode, activates source 2 conduction Modifies the blinking value In TEST mode, launches a full display test (LEDs, screen, buzzer) Modifies the blinking value Acknowledges alarm Validate or store The buzzer emits a short beep whenever a key is pressed STATYS 200-1800A - 552184A_EN...
  • Page 13 An alarm message may appear if an alarm is raised (see "alarm" chapter) This standard display may be temporarily fixed on one page using the buttons The display goes into standby mode (backlight OFF) after 5 minutes of keypad inactivity. STATYS 200-1800A - 552184A_EN...
  • Page 14: Automatic Mode

    4 modes: – automatic (AUT) – control (CONTROL) – test (TEST) Whatever the mode selected, STATYS operation remains prioritised. – programming (PROG) Press the key to select the next mode (the corresponding LED will blink), press the key to enter the se- lected mode.
  • Page 15 To exit this mode, press the key for the source in conduction state once more. The message "esc" then appears. Validate it using the key or cancel it using the key. Stop automatic switchback when the device is waiting for phase synchronisation, press the key for the alternate source ( The message "end asb" appears STATYS 200-1800A - 552184A_EN...
  • Page 16: Test Mode

    – Switching on all LEDs, – Displaying all LCD segments, – Operating the buzzer. This mode does not interrupt the normal operation of STATYS 7. 6.4. Programming mode This mode is accessed by entering a password: If the "user" password is inputted, only "user" parameters may be configured.
  • Page 17 Default value: nominal value measured by the equipment Possible choice: 100V to 499V Nominal frequency (System access) Display: fn (F) Default value: nominal value measured by the equipment Possible choice: 50 or 60 Hz Values used to calculated upper and lower limits. STATYS 200-1800A - 552184A_EN...
  • Page 18 Use of automatic switchback Display: aut sb (automatic switchback) Default value: no Possible choice: yes or no Delay before automatic switchback Display: dly (delay) Default value: 3 seconds Possible choice: 0 to 65535 (if aut sb = yes) STATYS 200-1800A - 552184A_EN...
  • Page 19: Alarm Management

    Problem with the settings and parameters Control Panel alarm hmi alm Communication with screen lost Electronic Electronic problem Custom input alarm cus in Custom alarm Maintenance alarm mnt alm Maintenance alarm General Alarm gen alm General Alarm STATYS 200-1800A - 552184A_EN...
  • Page 20: Touch Screen

    Handle the control panel with care. It is made of metal, glass and plastic and contains delicate electronic components. The control panel may be damaged if dropped, pierced or broken or comes into contact with liquids. Do not use the control panel with a cracked screen, as it may cause injury. STATYS 200-1800A - 552184A_EN...
  • Page 21: Display Description

    A dedicated pop-up appears and can be cleared. Clock Maintenance alert Synoptic area Help message area “Press Key to wake up” appears when the display goes on standby. Touch the display to wake it up. Measures report STATYS 200-1800A - 552184A_EN...
  • Page 22: Monitoring ▶ Alarms

    ▶ SWITCH LOAD OFF ▶ MAINTENANCE ▶ ALARMS RESET ▶ LED TEST CONFIGURATIONS ▶ CLOCK ▶ COM-SLOTS ▶ COM-SLOT 1 ▶ REFERENCE ▶ SOCOMEC REFERENCE ▶ SERIAL NUMBER ▶ REMOTE ▶ REMOTE ON ▶ REMOTE OFF STATYS 200-1800A - 552184A_EN...
  • Page 23 ▶ NETWORK PARAMETERS (Only for service) ▶ MAINTENANCE CODE 8. 3. F unctioning Mode Service 8. 4. s tatus 8. 4.1. Status page Filtering List all active status List all status List all status not active STATYS 200-1800A - 552184A_EN...
  • Page 24: Alarm Popup

    List all active alarms List all active preventive alarms List all active critical alarms oPuP alarM For Preventive alarM In USER PARAMETERS menu, USER PREFERENCES item gives the possibility to enable popup alarm also with preventive alarms. STATYS 200-1800A - 552184A_EN...
  • Page 25 Instantaneous value. displayed if value > 0 Load on Maintenance bypass 2 Present maintenance bypass voltage voltage Out of Input source 2 absent presence tolerance Normal Preventive Critical alarm Access to Static status alarm Static Switch 2 Switch page STATYS 200-1800A - 552184A_EN...
  • Page 26: Additional Icons

    8. T OUChsCreeN 8. 6.1. Additional icons Transfer impossible Transfer locked Maintenance alarm. Preventive maintenance is requested. 8. 7. e vent log Page Show STATUS events Show ALARMS events Show CONTROLS STATYS 200-1800A - 552184A_EN...
  • Page 27: Monitoring Menu

    This menu displays all STS measurements relating to the input stages, output stage. The pins on the bottom of the screen indicate whether or not there are more pages. Sliding to the right or left changes measurements page. STATYS 200-1800A - 552184A_EN...
  • Page 28 • CLOCK: this function sets the date and time. • COM-SLOTS: this function configures the RS485 modbus serial link. • REFERENCE: STATYS identification and serial number. • REMOTE: this function enables controls from remote devices through MODBUS protocol. 8. 8.7. USER PARAMETERS menu This menu contains the different functions for users such as language, password, buzzer, display, preferences, touchscreen calibration.
  • Page 29 Phase 2 Dark blue Purple Phase 1 Brown Light grey Dark grey Black The popup alarm appears in case of critical alarms. This function can be extended to preventive alarms by switching “Preventive Popup Alarm” to ON. STATYS 200-1800A - 552184A_EN...
  • Page 30 8. T OUChsCreeN 8. 10. sts settings please see § 7.6.4 Programming mode STATYS 200-1800A - 552184A_EN...
  • Page 31: S Tart Conditions

    Maintenance byPass STATYS is equipped with two bypasses (except the “Integrable” model) which enable it to directly supply the load from source 1 or 2 without interrupting your application’s power supply. This function is entirely secure, the switches are equipped with mechanical and electronic locks to minimise the risk of human error.
  • Page 32: Maintenance Bypass

    – 1 to 4 alarm relay modules (each module providing 3 inputs and 4 outputs). 11. ADVANCED DIAGNOSTICS AND PARAMETERS STATYS is equipped with a diagnostic card for connection to a maintenance computer. This link can be used for ad- justing the advanced parameters and other settings according to specific operational needs. Maintenance personnel...