General and safety information ......................8 1.4.1 Safety symbology......................... 8 1.4.2 General symbology ........................8 1.4.3 Recommended minimum profile for SDV operator and maintainer ..........9 1.4.4 Environmental and voltage conditions required for installation and operation ......9 1.4.5 Testing and installation instructions ....................10 1.4.6 Cleaning and decontamination instructions ................11...
Page 3
Self-diagnosis ..........................173 Alarms ............................180 Alarm and self-diagnosis memories ....................183 Commissioning for entry into service ................. 184 General commissioning guidelines ....................184 Commissioning guidelines for regulation functionality ..............184 [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 4
Technical data and type tests ..................186 Technical data..........................186 Type tests ............................. 188 Order specification ....................190 Accessories ......................192 11.1 Required accessories ........................192 11.2 Recommended accessories ......................196 [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 5
Figure 6 – Application example of the Smart Device for Voltage Regulation - SDV ..........30 Figure 7 - Application example of the Smart Device for Voltage Regulation – SDV with fiber optics....31 Figure 8 - Application example of the Smart Device for Voltage Regulation – SDV with RS-485 ......32 Figure 9 - System Composition of the Smart Device for Voltage Regulation - SDV ..........33...
9,610/98. 1.1.1 Disclaimer Treetech Sistemas Digitais reserves the right to make changes without prior notice to all products, circuits and functionalities described herein in order to improve their reliability, function or design. Treetech Sistemas Digitais does not assume any responsibility resulting from the application or use of any product or circuit described herein, nor does it transmit any licenses or patents under its rights, nor the rights of third parties.
1.4 General and safety information In this section, relevant aspects of safety, installation and maintenance of the SDV will be presented. 1.4.1 Safety symbology This manual uses three types of risk classification, as shown below: Warning This symbol is used to alert the user to a potentially dangerous operating or maintenance procedure, which demands greater care in its execution.
To handle the SDV, the professional must: Be trained and authorized to operate, ground, turn on and off the SDV, following the maintenance procedures in accordance with established safety practices, which are under the sole responsibility of the operator and maintainer of the SDV;...
3. Special attention must be given to the installation of the SDV, including the type and gauge of the cables and terminals used, as well as the procedures for putting into service, including the correct parameterization of the equipment.
These inspections are not mandatory. Opening the SDV at any time will result in loss of the product's warranty. In cases of improper opening of the equipment, Treetech cannot guarantee its correct functioning, regardless of whether the warranty period has expired or not.
All parts of this equipment must be provided by Treetech, or one of its accredited suppliers, according to their specifications. If the user wishes to purchase them in any other way, Treetech specifications for this must be strictly followed. Thus, the performance and safety for the user and the equipment will not be compromised.
1.6 Warranty term The Smart Device for Voltage Regulation - SDV will be guaranteed by Treetech for a period of 2 (two) years, counted from the date of purchase, exclusively against any manufacturing defects or quality defects that make it unfit for regular use.
During its operation, the SDV aims to maintain the quality of the voltage in the load, that is, within a given range of values, programmed by the user. For this, in addition to performing the ANSI 90 function, the SDV presents a series of applications to meet the most demanding regulations of the electricity sector.
High brightness, readable under any LOCAL COOLING CONTROL lighting and temperature conditions. Two options for performing this function: automatic or manual - via front keyboard, and remote - via communication port. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Shutdown contacts with adjustable timing from 0 to 20 minutes, with countdown indication on the display and via serial communications; Output contact for signaling the countdown to shutdown in progress; [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
1 ms accuracy. * Customer must choose only one of the 3 configurations. In case the user chooses the range options with negative values, mA outputs 3 and 4 will be unavailable. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
SDV, making it an Through the web interface, the firmware extremely safe and stable product while update process becomes extremely simple remaining easy to operate. and intuitive. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
SUPERVISION It is possible to supervise the communication status and error statistics of the SDV. Access to the details of the IED allows tracking of measurement values in real time. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
2.4 Optional functions According to the order, the SDV can be provided with one or more of the optional functions listed below: MMEM - Mass storage Non-volatile memory for storing measurements and events of alarms, shutdowns and others, with a capacity greater than 10 months recording every 15 minutes. Programming of the interval between recordings and temperature and voltage variation for recording is customized by the user.
Page 21
Two digital inputs for switching the OLTC command mode between manual/automatic and local/remote. They can also be used to command raise tap/decrease tap if the TAPP option is enabled or enable/disable the parallelism concentrator if the CONC option is enabled. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 22
Ethernet; Limitation of the OLTC excursion range (minimum and maximum taps allowed) and memorization of the minimum and maximum positions reached by the SDV since the last reset; Protection against improper tap changer operations: tap changer block in case of operations not initiated by the SDV.
OLCK - Verification of successful tap changing Enabled, this function allows the SDV to verify the tap changing success by means of voltage changes after the regulation command (increase/decrease voltage), without the need to measure the tap position. The algorithm applied to this verification method performs the comparison between the initial voltage levels and the one presented after the command for tap changing.
CTs (required accessory, supplied separately). 2.5.1.2 Forced cooling control The SDV can command up to 2 groups of forced cooling, in manual or automatic mode. In automatic mode, the forced cooling groups are controlled based on the highest measured value among the temperatures of windings 1, 2 and 3 or based on the oil temperature, depending on the parameterization.
Page 25
2.5.1.3 Multigradient function The SDV has a multigradient function, as the thermal behavior of a transformer varies according to the activation of its cooling stages. This functionality allows the equipment to vary the thermal parameters according to the active cooling stage. The winding temperature is calculated with greater precision, according to the operation of the transformer, ensuring greater reliability in the thermal management of the asset.
Its monitoring makes it possible to detect trends in the evolution of the differential that indicate permanent defects of small intensity, although with a longer detection time. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Smart Device for Voltage Regulation. 2.5.2 Voltage regulation During its operation, the SDV aims to maintain the load voltage within a range of values determined by the parameters programmed by the user. The SDV measures the voltage at the transformer’s output and the load current and uses them together with the programmed line voltage drop parameters to calculate the voltage [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
*Treetech auxiliary PT: 138.580.01 Figure 5 - Smart Device for Voltage Regulation - SDV For more detailed information on how the SDV acts during voltage regulation, see chapter 5.5. In addition to the basic voltage regulation function, the SDV also performs protection...
The SDV can act as a parallelism concentrator if the CONC option is enabled, managing the parallelism of the SPS, thus replacing the COMM-04 communication module.
COOLING GROUPS OLTC PROTECTION AND CONTROL THERMAL MANAGEMENT PARALLELISM IMPROVEMENT OF OPTIMIZED ASSET VOLTAGE QUALITY MANAGEMENT Figure 6 – Application example of the Smart Device for Voltage Regulation - SDV [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
RS-485 USER LEVEL FIBER OPTICS RS-485 CONVERTER Figure 8 - Application example of the Smart Device for Voltage Regulation – SDV with RS-485 [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
This item must be specified in the purchase order when the SDV model has regulation; External PT for measuring the system voltage that is required by the SDV. This is an item that must appear in the purchase order;...
(1 or 3 windings) and must be included in the purchase order; RTD type Pt100 Ω at 0 °C for temperature measurement by the SDV. The quantity can vary between 1 and 2 and must be included in the purchase order according to the quantity of temperatures to be measured;...
In either case, there must be an anti-condensation system. The SDV is suitable for flush-mounted installation and can be fixed, for example, on doors or front plates of panels. Fastening clips are supplied with the equipment.
A circuit breaker must be used immediately before the power input (universal power supply - 85 to 265 Vac/Vdc, ≤ 13 W, 50/60 Hz), which corresponds to pins 33 and 34 of the SDV. This circuit breaker must have the number of poles corresponding to the number of phases used in the supply - the poles must only interrupt the phases, and never the neutral or ground - and provide thermal and electrical protection to the conductors that supply the equipment.
, according to IEC 61010-1. These values are related to the intrinsic insulation of the devices connected to the SDV. Cases where this value does not apply to equipment or devices connected to the SDV will be explicitly informed in this manual.
5.9. Since the SDV offers a wide variety of warnings, alarms and commands, it will also be necessary to choose the use of the outputs according to the priorities of the application.
57 - VM temperature required by the application, the Smart Device for Voltage common Regulation - SDV has two inputs for Pt100 Ω at 0 °C type sensors. 58 - VM RTD 2 59 - VR RTD 2 CURRENT INPUTS...
DRY CONTACT INPUTS If the DIGI option is enabled, the SDV will be able to receive information through two dry contacts to be connected to terminals 50 and 54 with pin 52 in common. These contacts are especially useful for the device's regulation functions, allowing it to receive the following instructions and information from a remote source: ...
The automatic resistance compensation of the connection cables is made from the potentiometric transmitter to the SDV, and for this the three wires must have the same length and gauge, with the maximum allowable resistance for each wire being 8 Ω.
MOVING CONTACT FIXED CONTACTS START POSITION CURSOR START END POSITION POSITION END POSITION CURSOR Figure 16 - Configuration of the potentiometric transmitter resistors in the intermediate positions of the OLTC [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
The SDV assumes that the resistance per step of the potentiometric transmitter is in the range from 4.7 to 20 Ω, and the total resistance of the transmitter from 4.7 to 1400 Ω. The value of each individual resistor is shown in Figure 17, at the RS value. The moving contact (cursor) of the potentiometric transmitter can be either “close before open”...
Figure 18 - Central tap indication TEMPERATURE SENSORS The SDV has two inputs for RTD Pt100 Ω at 0 °C type temperature sensors. One of them must be used to measure the temperature of the top of the transformer oil; the other can be used to measure ambient temperature, transformer oil temperature redundancy, tap changer oil temperature, or to another desired temperature.
The temperature sensor must be connected to the SDV through shielded cables, without interrupting the mesh, which must be grounded only at the end connected to the SDV, as close as possible to it. If there is a need for intermediate terminals for interconnecting the RTD sensor, the cable shield must pass through the terminal, preventing its interruption.
CT of the equipment is short-circuited and grounded in the panel terminals. If the SDV has the regulation functionality, the input where the external CT for regulation is located must be informed in the configuration. This external CT is a window type with a non- sectionable core, unlike the clip-on CT that is normally used for thermal imaging.
Page 51
41 - NO The SDV has three reversible output relays being NO or NC. 42 - NC 43 - common R1 - Self-diagnostic signaling relay 38 - NO R2 - Forced ventilation group 1 activation relay 39 - NC R3 - Forced ventilation group 2 activation relay...
A, without interruption. SIMPLE CONTACT RELAYS There are eleven of these relays on the SDV, R4 through R14. Relays 6 to 10 can be configured to work in normal (NO) or inverted (NC) mode while the others have fixed NO operation.
Page 53
The relay will operate for Red classification alarms Tap Reading Error The relay will operate tap reading error Automatic Mode The relay will operate when the SDV is in Automatic mode Manual Mode The relay will operate when the SDV is in Manual mode Local Mode...
ANALOG OUTPUTS IN CURRENT LOOP The SDV has four analog current loop outputs (mA), which can be programmed by the user to remotely indicate the measured voltage, current or tap position value. The output current range is also user selectable from 0 to 1, -1 to +1, 0 to 5, -5 to +5, 0 to 10, -10 to +10, 0 to 20, - 20 to +20 or 4 to 20 mA.
71 - (-) Two of them, located at terminals 71 and 72, and 74 and 75, 72 - (+) are intended to allow the connection between the SDV and User some supervision or monitoring system owned by the user. 74 - (-)
3.4.3.1 Cautions when installing the RS-485 network 3.4.3.1.1 Communication with the data acquisition system The SDV can be connected to a data acquisition system (supervisory or monitoring system) via the RS-485 serial communication ports located on terminals 71 and 72, and 74 and 75.
Figure 26 - RS-485 serial communication shield connection and grounding 3.4.3.1.2 Parallelism communication For the SDV to act as a parallelism concentrator, the SDV and all SPSs that participate in parallelism must be interconnected by connecting their RS-485 ports in parallel, as shown in Figure 27.
4 Operation All operations on the Smart Device for Voltage Regulation - SDV can be performed through the keyboard on its front panel. The voltages, currents and other measured quantities are indicated on the display, and the alarm conditions, by the signaling LEDs.
Press the key to save the new setting and the key to return to the indication screens. Contrast Adjustment Figure 29 - SDV contrast adjustment [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
4.3 Query screens The Smart Device for Voltage Regulation - SDV display presents some screens just for reference. Information such as date, time, time zone and measurements. Use the arrows to navigate through the screens shown below: Status: 0.0°C Normal...
Page 61
Operation Mode Default Remote/Automat. ACTIVE REGULATION SET: Indicates OPERATION MODE: Indicates the which regulation set is currently SDV operation mode (automatic or active. manual) and the command mode (local or remote). [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 62
Current TAP Pos Previous TAP TAP POSITION: Indicates the position PREVIOUS TAP: Indicates the last tap the tap is presently in. position before the present one. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 63
Temperature Regulation ---> ---> TEMPERATURE MENU: Press the key REGULATION MENU: Press the key and access the advanced query and access the advanced query screens for temperature. screens for regulation. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
At any time, press the key return. To reset the maximums shown in the following menus, press the key the measurement you want to reset for approximately 3 seconds. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 65
1 of through winding 2 of gradient between oil the transformer. the transformer. and winding 3 will be if the present loading is maintained. It also shows the active cooling stage. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 66
Pt100 sensor #1 since since the last time this menu related to the the last time this marker was reset. tap changer marker was reset. temperature differential. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 67
To navigate through the tap changer temperature differential advanced query screens, use the keys. At any time, press the key to return. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 69
See information on the insulation aging of each Winding 1 winding (1, 2 or 3) individually. Use ---> to find the desired winding and press select. Then, navigate through the menus described below: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
PT. In average of daily the frequency and the lower row, it operations. capacitive power shows the current in factor (c) or inductive the secondary of the power factor(i). measuring CT. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
REMAINING DAYS: Indicates the number of days left for the alarm due to I² or due to operations, considering the I² accumulation trends or the daily present switching average, respectively. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
IP address and Network Settings subnet mask of the SDV primary and ---> secondary network, gateway, preferred and alternate DNS. Use the keys navigate through information. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
SDV secondary IP. 4.4 Regulation command modes The SDV allows the user to select a series of characteristics of the regulation's operation. To access this menu, press the key . To navigate through the options and confirm the selection, use the keys , respectively .
Table 10 - Command conditions - Part II Choose the command mode between automatic and manual: Front External Contact SDV Regulation Serial Local Remote Caption: Allowed Not allowed Not applicable [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
As seen in the tables in the previous section, it will only be possible to do this if the SDV is configured in local and manual mode. 4.6 Commands to cooling groups The SDV has two contacts for commanding ventilation or cooling groups in general.
When such irregularities are detected, 0001 0004 0800 warning texts automatically appear on the equipment screen, as in the example on the right - in this case, the SDV has detected a self-diagnosis and displays the self-diagnosis code for identification. Autodiagnostic...
Page 77
(in days). SDV that the maintenance has been carried out, press simultaneously , the message “OLTC Maintenance carried out?” will appear on the screen, then press the key and then confirm. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 78
3 reaches the winding 2 reaches the programmed level. programmed level. This screen indicates This screen indicates the time, in minutes, the time, in minutes, for this action. for this action. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
5 Parameterization To guarantee its correct operation, several parameters must be adjusted in the SDV that will provide the equipment with the necessary information for its operation. Programmable parameters are organized in menus with password-protected access. In the main menu, the user will have access to the programming submenus, where it is possible to navigate and adjust the values according to the characteristics of the transformer and users' needs.
DEFAULT VALUE: Portugues. 5.2 Set clock To access the date and time setting menu, navigate with the arrow keys until the “Set Clock” line is highlighted, then press Idioma/Language Set Clock [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Clock Sync. Mode Internal Clock CLOCK SYNCHRONIZATION MODE: Select whether the SDV date and time will be based on the NTP/SNTP protocol or the internal clock. If the first option is chosen, by pressing the key the clock will be set by the network according to NTP/SNTP and the menu will return to the previous level.
SETTING RANGE: 1 to 15 min. DEFAULT VALUE: 5 min. New Password NEW PASSWORD: Choose a new password to access the parameterization menu. SETTING RANGE: 0 to 8191. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
If active but not assigned to any function, it will measure ambient temperature. SETTING RANGE: 1X3, OFF. DEFAULT VALUE: 1X3. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Set the largest tolerable difference between the temperatures measured by the redundant sensors. A difference greater than the one defined here will generate the self- diagnosis “Max Difference Error”. SETTING RANGE: 1.0 to 6.0 °C. DEFAULT VALUE: 4.0 °C. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Simulator SIMULATOR: In case of any test or experiment that involves connecting a temperature sensor simulator to the SDV, indicate here which input will be used for this purpose. SETTING RANGE: PT1, PT2, OFF. DEFAULT VALUE: OFF. 5.4.2 Alarms The alarm configuration submenu is subdivided into two other submenus.
Page 88
1 °C or more below the trigger value. It can also be used as a second level alarm if automatic transformer shutdown is not desirable. SETTING RANGE: -55 to 200 °C. DEFAULT VALUE: 120 °C. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 89
Allows a delay to be entered between the moment when the winding 2 temperature reaches the shutdown value and the time the shutdown signal and associated output relays are actually activated. SETTING RANGE: 0.0 to 20.0 min. DEFAULT VALUE: 20.0 min. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 90
Instantaneous temperature differential between transformer and tap changer above which the “Instantaneous Temperature Differential Alarm” (alarm panel 2, code 0001) must be activated. SETTING RANGE: -40.0 to 40.0 °C. DEFAULT VALUE: 10.0 °C. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 91
Low Lifetime 1.0 years LOW REMAINING LIFETIME: Based on the load and wear history, the SDV calculates the remaining lifetime for the transformer. If the projected remaining lifetime is less than what is set here, an alarm will be activated.
Page 92
ALARM DUE TO TEMPERATURE OF WINDING 1: Classify this alarm into one of the categories listed in the setting range or disable the alarm classification. SETTING RANGE: Red, Yellow, Blue and Disabled. DEFAULT VALUE: Red. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 93
SHUTDOWN DUE TO TEMPERATURE OF WINDING 2: Classify this alarm into one of the categories listed in the setting range or disable the alarm classification. SETTING RANGE: Red, Yellow, Blue and Disabled. DEFAULT VALUE: Red. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 94
DELAY OF SHUTDOWN DUE TO TEMPERATURE OF WINDING 3: Classify this alarm into one of the categories listed in the setting range or disable the alarm classification. SETTING RANGE: Red, Yellow, Blue and Disabled. DEFAULT VALUE: Red. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 95
LOW REMAINING LIFETIME IN WINDING 1: Classify this alarm into one of the categories listed in the setting range or disable the alarm classification. SETTING RANGE: Red, Yellow, Blue and Disabled. DEFAULT VALUE: Red. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 96
HIGH LOSS OF LIFESPAN IN WINDING 2: Classify this alarm into one of the categories listed in the setting range or disable the alarm classification. SETTING RANGE: Red, Yellow, Blue and Disabled. DEFAULT VALUE: Red. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
In the Transformer second submenu, for each active cooling stage, the parameters related to the calculation of the temperature of the windings and the hotspot are configured. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 98
In case it is not possible to obtain it by one of these two ways, the typical value of 300 s can be adopted. SETTING RANGE: 72 to 999 s. DEFAULT VALUE: 300 s. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 99
It must be used when there are no differences in temperature rises due to the operation of the cooling groups. Then configure each of the calculation parameters listed below: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 100
Número Descrição Transformers cooled by natural or forced oil circulation (ONAN, ONAF, OFAF, OFWF) Transformers cooled by oil directed circulation (ODAF, ODWF) SETTING RANGE: 0.0 to 4.0. DEFAULT VALUE: 1.6. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
As long as the functionality for monitoring the temperature of 3 windings is active and the corresponding number of windings is parameterized in the item “N. Windings”, all configuration items in this section will be repeated for windings 2 and 3 of the transformer. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Temperature reduction value, below the starting temperature of the cooling stage, to turn off the fans/pumps, to prevent them from being turned on and off successively with small temperature variations. SETTING RANGE: 0 to 9 °C. DEFAULT VALUE: 5 °C. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 103
This parameter will only be displayed if one of the cooling groups has pumps. SETTING RANGE: -55 to 200 °C. DEFAULT VALUE: -25 °C. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 104
This parameter will only be displayed if the FEXC option is enabled. SETTING RANGE: 0 to 999 min. DEFAULT VALUE: 45 min. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 105
“Cooling Group 1” and “Cooling Group 2” will be on, prioritizing the activation of the group with the shortest operating time. SETTING RANGE: -55 to 200 °C. DEFAULT VALUE: 65 °C. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 106
Selects whether or not cooling group 1 is enrolled in stage “N” of forced cooling, that is, whether it can be used by the cooling stage when its temperature or activation load percentage is reached. SETTING RANGE: YES, NO. DEFAULT VALUE: YES. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Water content in the winding 2 insulating paper in % of dry mass. It is possible to define the moisture in the paper based on oil samples according to NBR 5356:2017. SETTING RANGE: 0.0 to 10.0 %. DEFAULT VALUE: 0.0 %. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 108
The standard NBR 5356:2017 can be used as a reference, which establishes the limits of 2.0% for transformers below 230 kV and 1.5% for transformers of 230 kV and above. SETTING RANGE: 0.0 to 3.0 %. DEFAULT VALUE: 1.5 %. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 110
LOSS OF LIFESPAN RESET: Reset of loss of lifespan stored in non-volatile memory. Especially useful when the device has just been put into operation on a transformer. SETTING RANGE: YES, NO. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
180 min. Timing for Alarms 20 min TIMING FOR ALARMS: Timing for issuing alarms by temperature differential of tap changers. SETTING RANGE: 1 to 240 min. DEFAULT VALUE: 20 min. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 112
When selecting YES, the time countdown for automatic adjustment will start, as programmed in the parameter above. SETTING RANGE: YES, NO. DEFAULT VALUE: YES. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
ENABLE REGULATION: This parameter allows enabling or disabling the regulation function, due to maintenance, temporary non-use or any other applicable reasons, when the SDV is purchased in the model with regulation. When disabled, the equipment does not perform any function related to voltage regulation, remaining only as a temperature monitor.
Desired voltage on load = 13200 V 13800 V PT transformation ratio = = 120 115 V 13200 V Rated voltage = = 110 V SETTING RANGE: 10.0 to 240.0 V. DEFAULT VALUE: 115.0 V. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 115
It is used for faster voltage regulation in case of large voltage deviations. The timing effectively applied by the SDV after detecting a voltage deviation greater than the insensitivity will be given by: Adjusted deviation Effective time = Adjusted time ∙...
Page 116
“Timing Step”. If a single tap changer operation is not enough for the voltage to return to the set limits, the SDV will use the subsequent time setting as an interval for the other commands to the on-load tap changer.
Page 117
It is the line voltage drop as a percentage of the transformer output voltage, adjusted to the rated current of the SDV (5 A). The Z Compensation adjustment can be obtained experimentally, if the transformer output voltage, the load voltage and the load current are measured simultaneously, then applying the formula below: Transformer Output Voltage −...
Page 118
1) 10.0 % COMPENSATION LIMIT: During line drop compensation operation, the SDV will cause the transformer output voltage to rise in order to keep the load voltage within limits. This voltage rise will be proportional to the load current, so very high load currents could cause a large voltage rise at the transformer output.
Page 119
PT Ratio = = 120 115 V 13200 V Rated voltage = = 110V 172.5 V Deviation 1 > 50 ∙ 110 V ∙ 120 Deviation 1 > 0.65 % [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 120
Note that the three timing steps will only be effective if the Type of Timing parameter is selected for linear timing. Otherwise, when inverse timing is selected, only timing step 1 settings will be effectively used for SDV operation.
0° PHASE DIFFERENCE BETWEEN CT AND PT: There are several possible combinations for connecting the PT and CT to the SDV, and each combination produces an angular phase difference between the voltage and current signals. In this parameter, the phase difference angle between the voltage measured by the PT and the current measured by the CT is adjusted.
Page 122
115 V, we get the value of the PT voltage ratio: 138000 V PT Ratio = = 1200 115 V SETTING RANGE: 1 to 9999. DEFAULT VALUE: 100. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 123
DEFAULT VALUE: YES. OLTC Limit Check OLTC LIMIT CHECK: Select the number of times the SDV should check the OLTC before generating an alarm. This parameter will only be displayed if the OLCK option is enabled. SETTING RANGE: 1 to 99.
10% of the rated voltage. To prevent the SDV from triggering the on-load tap changer to try to raise the voltage during a short circuit, the user can select the alarm of U< as a condition for tap changer blocking in the OLTC Blocking parameter.
Page 125
This condition can be harmful to loads connected to the transformer. When overvoltage occurs, the SDV can immediately operate the on-load tap changer in order to lower the voltage, disregarding timing adjustments. If this quick operation is to be avoided, the user can select the U> alarm as a condition for tap changer blocking in the OLTC Blocking parameter.
Page 126
Operating the on-load tap changer with high currents can be harmful to its contacts. To prevent the SDV from triggering the on-load tap changer to try to raise the voltage during a short circuit, the user can select the alarm of I> as a condition for tap changer blocking in the OLTC Blocking parameter.
Page 127
RPF: Blocking by reverse power flow. When one or more conditions programmed in these parameters occur, the SDV will not issue any command to the OLTC, blocking the action of increasing or decreasing the voltage. The...
Page 128
Allows the user to sort the alarm priority level of OLTC check events according to the color code described in section 7.2. This parameter will only be available if the OLCK option is enabled. SETTING RANGE: Red, Yellow, Blue e Disabled. DEFAULT VALUE: Red. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Allows the user to classify the priority level of the switched current integral alarm, according to the color code described in section 7.2. SETTING RANGE: Red, Yellow, Blue e Disabled. DEFAULT VALUE: Blue. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 130
ENABLE TAP CHANGER MAINTENANCE FUNCTION: Enables the tap changer maintenance function. This parameter will only be available if the OLMT option is enabled. SETTING RANGE: YES, NO. DEFAULT VALUE: YES. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 131
Defines the total number of operations of the tap changer since the start of its operation. It allows the present number of tap changer operations to be adjusted so that the SDV count matches the mechanical counter on most OLTCs.
Page 132
Defines the number of operations for OLTC maintenance, as indicated by its manufacturer. When the counter of No. Op. Last Maint. reaches the configured value, the SDV issues a warning indicating that maintenance on the tap changer must be carried out. The warning can be signaled on a programmable output relay.
Page 133
OLTC maintenance, as indicated by its manufacturer. When the I after Maint. recorder reaches the configured value, the SDV issues a warning indicating that maintenance on the tap changer must be carried out. The maintenance warning indication remains active in the SDV and programmed warning contacts will remain on until the user manually acknowledges the warnings.
Average Reset AVERAGE RESET: Resets the average number of tap changer operations and switched current. SETTING RANGE: YES, NO. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
DEFAULT VALUE: YES. ID Concentrator CONCENTRATOR IDENTIFICATION: Number that identifies the SDV in the SCADA system. Used to identify which SDV is enabled as a parallelism concentrator. This parameter will only be available if the CONC option is enabled. SETTING RANGE: 1 to 65535.
Normal, Simple Cal., Advanced Cal. DEFAULT VALUE: Normal. Number of TAPS OLTC NUMBER OF TAPS: Select the number of OLTC taps that the SDV should monitor. SETTING RANGE: 1 to 49. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 137
Choose the value of the final step of the transmitter resistance, proportional to the parameter “Resistance”, that is, Final Resistance = Final Offset * Resistance. SETTING RANGE: 0 to 5. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 138
Enter the minimum tap number to be allowed. SETTING RANGE: 1 to 49. DEFAULT VALUE: Max. TAP Allowed MAXIMUM TAP ALLOWED: Enter the maximum tap number to be allowed. SETTING RANGE: 1 to 49. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 139
Cursor Res. Alm 20 Ohms CURSOR RESISTANCE FOR ALARM: If the SDV identifies that the resistance of the cursor is greater than the value defined in this parameter, the equipment will issue an alarm of high resistance of the cursor. SETTING RANGE: 5 to 20 Ω.
Page 140
Definition of the multiplier factor of the integral of the squared switched current (I²). This parameter can only be filled in if the OLTC option is enabled. SETTING RANGE: 1 to 5. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Input Contact 1 INPUT CONTACTS 1 AND 2: The SDV can receive different types of commands from external sources, such as control panels and buttons installed in remote locations from the device. For this, SDV input contacts 1 and 2 can be configured to receive different types of commands if the DIGI option is enabled.
There is also the “Factory” menu, for exclusive use by Treetech. When trying to access the factory menu with the wrong password, the SDV will show the message VOID on its display for a few seconds. The indication time of this message increases as retries are made with an incorrect password.
60 min. RECORDING INTERVAL: Selects the time between times when recordings will be made. The SDV has 23,000 positions for recording variables. Depending on the interval chosen between recordings, the mass storage may take more or less time to fill up. To know how long the memory will take to be completely occupied, just do: Total time = Positions [ rec.
Indicate the present tap position for the calibration. This parameter will only be displayed if the parameter “Measurement Method” in the menu “On-Load Tap Changer” is set to “Simple Cal.” or “Advanced Cal.”. SETTING RANGE: 1 to 49. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
(terminals 62 and 51 of the SDV), select the “Calibrate” option so that the SDV performs the calibration. This parameter will only be displayed if the parameter “Measurement Method” in the menu “On-Load Tap Changer” is set to “Simple Cal.”...
The first step in this submenu is to select the relay you want to configure. The General submenu allows the selection of five relays. SETTING RANGE: 06 to 10. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 148
Mode Normal MODE: Relays 06 to 10 are always NO, by hardware definition. However, the SDV allows the electrical assembly logic to be inverted by firmware such that all relays can operate in NO and NC modes. SETTING RANGE: Normal, Inverse.
To read all alarms individually at a distance, an interesting option is to acquire a monitoring system such as Treetech's SIGMA ECM®, which also integrates other substation equipment and allows more advanced engineering calculations.
Page 150
Manual Mode MANUAL MODE SIGNALING: Activates the relay when the SDV operating mode is in manual. SETTING RANGE: NO, YES. DEFAULT VALUE: Local Mode LOCAL MODE SIGNALING: Activates the relay when the SDV command mode is in local. SETTING RANGE: NO, YES.
Page 151
NO, YES. DEFAULT VALUE: Inst. Differential INSTANTANEOUS DIFFERENTIAL: Activates relays when there is an alarm due to temperature instantaneous differential between transformer and tap changer. SETTING RANGE: NO, YES. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 152
DEFAULT VALUE: 5.9.2.3 Regulation The regulation submenu is divided into two categories. In the first, configure the relays for general functions In the second, configure the relays for advanced regulation functions. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 153
Activates relay when there is an overcurrent alarm. SETTING RANGE: NO, YES. DEFAULT VALUE: OLTC Block OLTC BLOCKING: Activates relay when there is an OLTC blocking condition. SETTING RANGE: NO, YES. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 154
Activates the relay when the sum of the squares of the currents at the time of the OLTC operation has reached the value for maintenance for switched current, defined in the parameter “Warning Maint. Ipu²”, indicating contact wear. SETTING RANGE: NO, YES. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 155
OLTC squared (Ipu²), considering the counter “I after Maint.” the daily average of switched current squared and the number of days for warning with advance for maintenance. SETTING RANGE: NO, YES. DEFAULT VALUE: [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Figure 30 - Illustration of the SDV front displaying the IP for website access 6.1 General navigation In order to facilitate navigation, the SDV website has a general symbology, which is repeated on several pages. Depending on user profile permissions, some fields will not be available.
Clicking on the “Create” button will open an empty form with the necessary fields to create a dataset. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 158
The highlighted panel shows the time in local format and the date. This panel is responsive so the user can access local time and UTC information by hovering the cursor over the panel. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
4. Output groups In the central part of the screen, the user can consult and interact with the expandable blocks that represent the SDV output connections and their information as well as the status and history of the communication. 5. Language In the lower right corner of the homepage, the user can select the language.
In addition, when interacting with the buttons below the screen, the user has access to some “Parameters” and “Changelog” information. Figure 33 - System information screen [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
“Login” button to access the system. 2. Wrong username and/or password If the username and/or password are not correct, a message will be displayed inside a red text box, alerting you to the error. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
In the final thirty seconds, a countdown window alerts the user to the end of the session. 6.5 Editing the profile Figure 35 - Editing the profile on the SDV website 1. Access If the user wants to make changes to their profile, changing their password or their login, just click on the username, available in the upper right corner of the screen.
Page 163
In the lower left part of the screen, a table is displayed that indicates the permissions of the current user in each of the functionalities. Just below the table is a checkbox that enables or disables a set of optional advanced settings for some screens. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Figure 37 - “System” tab of the SDV website 6.6.1 Date and time In this screen the user can modify the date and time of the SDV. Figure 38 - System tab > Date and time of the SDV website 1.
It may be necessary to configure an IP address in the “Gateway” field of the IP configuration in order for the SDV to have access to the NTP IP. If the source is RTC, the user, in addition to selecting a time zone, must manually adjust the equipment's date and time.
Below the search box, a list of found processes is shown. They can be organized according to the name of the columns presented in the table header: processes or connection. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
IP (192.168.10.87). 3. System restore As well as allowing the user to restart the IED, the SDV website guarantees the possibility to restore all the product's factory settings. To do this, click on the orange “System Restore”...
Figure 43 - Access configuration screen 6.6.7 Restart The SDV website allows the user to remotely restart the equipment. To do this, simply click on “Restart” on the “System” tab. 6.7 User registration On this page, you can check which users are registered to use the system, as well as make changes to them and register new ones.
The “System Log” page, accessed through the “Download” tab, allows the user to download, in a text file, the communication log of all ports and protocols used. It is also possible to [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
3. Download system log Another log available for download is the system log. To download it, just click on the third blue button. Although the user can download it, access to this log is restricted to Treetech technical support. 4. Download configuration report The last type of log available for download is the configuration log.
2. Table filters and navigation The table header allows the user to sort abstracts by “Name”, “Value”, “Unit”, “Written”, “Description” and “Date/Time”. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Figure 48 – ”Mapping” Menu > SDV website ”Definitions” page 6.10.2 Modbus / DNP3 / IEC 61850 In this section it is possible to configure the points to be distributed in the SDV output connections, available in the Modbus®, DNP3 and IEC 61850 protocols.
B for example, alarms 1, 2 and 8 are currently active, as in hexadecimal numbers B=1+2+8. The tables below present all the SDV self-diagnostic codes and the recommended procedures for each case. Table 12 – Self-diagnosis Self-diagnosis panel 1...
Page 174
Use of unshielded cable to Check if shielded cable is connect the Pt100 sensor to being used to connect the the SDV. temperature sensor to the SDV. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 175
“Sensor Pt1” and changing the parameter “Sensor Pt2” parameters. “Sensor Pt1” and “Sensor Pt2”. Internal failure of the temperature sensor. Replace defective temperature sensor. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 176
Internal failure of the temperature sensor. Replace defective temperature sensor. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 177
3. potentiometric transmitter to the SDV is grounded at Ground the shield of the more than one point, not cables connecting the [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 178
1%. Restart the equipment by disconnecting the SDV from Transmitter A/D 0002 Internal failure. the power supply and self-diagnosis. reconnecting immediately. If this action does not have [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 179
SPS. potentiometric transmitters. Cables connecting the potentiometric transmitter Replace the cables to the SPS with resistance connecting the greater than 8 ohms per potentiometric transmitters wire - very low gauge [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
B for example, alarms 1, 2 and 8 are currently active, as in hexadecimal numbers B=1+2+8. In addition, alarms are color-coded in ascending order of urgency. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Code Blue Maintenance warning Yellow Minor alarm. Check occurrence. Severe alarm. Immediate attention required. The table below describes all alarms available in the SDV: Table 14 - SDV alarm table Alarm panel 1 Code Alarm description 0001 Alarm due to high oil temperature.
Page 182
Alarm due to OLTC maintenance for switched current squared. Alarm due to advance warning of OLTC maintenance for number of operations or 0080 switched current squared. 4000 Alarm due to high transmitter cursor resistance. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Reconnect the ground cables to the SDV terminals, if they have been disconnected for applied voltage tests; Power the SDV with any voltage in the range of 85 to 265 Vac/Vdc, 50/60 Hz; Check that the current loop output has the correct value in relation to the associated variable;...
If necessary, isolate all command, alarm and shutdown contacts; Connect temperature calibrator, decade resistance or check the temperature of the Pt100 connected to each SDV measurement input, checking if the measurements are correct; Inject AC current into the SDV current measurement inputs, verifying that the indications are correct on the equipment query screens;...
Current loop analog outputs Up to 4 unipolar or 2 bipolar, with common positive Maximum error of analog outputs 0.5% of full scale Selectable options and maximum load 0...1 mA, 10 kΩ [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 187
GOOSE publisher * Customer must choose only one of the 3 configurations. The .icd file can be created from any .icd generator software and later imported through the SDV web interface. The .icd file can be created from any .icd generator software and later imported through the SDV web interface.
9.2 Type tests The SDV is an equipment built on the SmartSensor 3 platform, on which the type tests presented were carried out: Surge immunity (IEC 60255-22-5 and IEC 61000-4-5) Waveform, intensity, amount of surges 1.2/50 µs ±2 kV common mode ±1 kV differential mode...
Page 189
Amplitude and frequency range 0.075 mm, 10...59 Hz 9.8 m/s (1 gn), 59...150 Hz Duration 8 min/axis Vibration durability (IEC 60255-21-1) Application method Sinusoidal Amplitude and frequency range 19.6 m/s (2 gn), 10...150 Hz Duration 160 min/axis [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
SDV FOFO - 2x Ethernet F.O. (10/100BASE-FX; MM 1310 nm SC connector; MM 1310 nm SC connector). SDV FOSR - 1x Ethernet F.O. (10/100BASE-FX; MM 1310 nm SC connector) + 1x Serial F.O. (MM 850 nm SC connector).
Page 191
MMEM PCOL FEXC INAG OLTD DIGI TAPP OLMT OLCK CONC Caption: Available Oil temperature redundancy is restricted, as it requires a Pt100 for OLTC temperature Not available [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
11 Accessories There are additional accessories to the SDV, and depending on the functions chosen, some are required for its operation, while others are optional. 11.1 Required accessories 1. External split-core window type CTs (clip-on) The use of external split-core window type CTs is required to read the transformer load currents.
Page 193
Maximum phase error ≤ 1° at 300 Ω load Power ≤ 0.5 VA (measurement only) Operating temperature -40...+85 °C Secondary with protection against load Protection disconnection and external electrical transients [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 194
3. Regulation PT The use of SDV in voltage regulation of transformers requires the installation of an auxiliary PT. This item is supplied in the quantity required for the type of application desired, and must be requested in the purchase order, with the characteristics listed in the table below.
Page 195
The sensors used must be of the Pt100 Ω at 0 °C type. If necessary, Treetech has a sensor suitable for installation in a thermowell, according to the drawing below (special dimensions on request), supplied as an accessory.
In cases where this is not convenient, as for example, in retrofitting old transformers, the SDV can be supplied in an easy-to-install weatherproof cabinet.
Page 197
The wells are made of 304 stainless steel, a very corrosion resistant material and widely used as protection at temperatures up to 900 °C. Characteristics Range/description Internal thread (Pt100) 3/4” BSP External thread (process) 3/4” NPT or 1/2” NPT [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Page 198
The computer with the software can be located in the substation control room or in a remote location, allowing access to all information to others connected to the intranet network. [Manual - SDV | MAN-008 | 18/11/2024 | Revisão: 1.10]...
Need help?
Do you have a question about the SDV and is the answer not in the manual?
Questions and answers