Page 1
Installation Instructions Compressor Sealant Kit KIT09237 Model Numbers: CDHF CDHG, CVHE, CVHF, CVHG This document applies to service offering applications only. SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Introduction Read this manual thoroughly before operating or servicing this unit. WARNING Proper Field Wiring and Grounding Warnings, Cautions, and Notices Required! Safety advisories appear throughout this manual as required. Failure to follow code could result in death or serious Your personal safety and the proper operation of this machine injury.
Introduction WARNING Follow EHS Policies! Failure to follow instructions below could result in death or serious injury. • All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc.
General Information This kit contains the sealant and corresponding instructions to be used when reassembling a compressor with or without O-rings. Table 1. KIT contents Part Number Quantity Description CHM00210 Loctite® Chisel SEL00376 Loctite® 515™, 300 mL tube SO-SVN011*-EN Installation Instructions SO-SVN011A-EN...
Installation Sealing of Chiller flanges with the extrude or seep into undesirable areas, making removal of additional components difficult. use of O-rings 3. Wipe the O-ring grooves and flange surfaces clean with alcohol wipes. Avoid touching the cleaned surfaces with bare hands as body oils can affect the adhesion of the WARNING sealant.
Installation Figure 1. Loctite® 515™ application, with O-ring groove O-ring with Loctite® 515™: Apply a bead 1/8-in. above and below the O-ring Side View Loctite® 515™ *Additional 1/16-in. maximum bead of Loctite® 515™ on flange face *Additional 1/16-in. maximum bead of Loctite® 515™ Top View O-ring SO-SVN011A-EN...
Page 7
Installation Sealing of Chiller flanges without 2. Remove all high spots or burrs that may have occurred on the flange faces because of the use of the jack bolt holes. the use of O-rings File the high spots and burrs to obtain a flat surface. If a flange surface does get extremely smooth (mirror-like), use some 80- to 120-grit sandpaper on a hand-sanding WARNING...
Page 8
Installation elapse between mating of the flanges and applying the Table 2. Loctite® 515™ bead size when no O-ring is final bolt torque. applied Typical effective cure times for Loctite® 515™ will range Flange Face Width (in.) Sealant Bead Size (in.) from 1 to 12 hours depending on surrounding temperatures and flange gaps.
Page 12
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.