Safetec SDS-72 Manual

Safetec SDS-72 Manual

Smoke detection system
Table of Contents

Advertisement

Quick Links

safetec
Smoke Detection System
SDS-72
according to:
FSS Code Chapter 10
EN 54-2: 1997/A1:2006
IEC 60092-504
SMOKE DETECTION SYSTEM SDS-72
safetec
i
<
>
ALARMS
POWER
DISABLED
FIRE
FAULT
SYSTEM
DIM
SILENCE
ACK
MENU
Manual
Art. No. DOK02.140

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SDS-72 and is the answer not in the manual?

Questions and answers

Summary of Contents for Safetec SDS-72

  • Page 1 Smoke Detection System SDS-72 according to: FSS Code Chapter 10 EN 54-2: 1997/A1:2006 IEC 60092-504 SMOKE DETECTION SYSTEM SDS-72 safetec  < > ALARMS POWER DISABLED FIRE FAULT SYSTEM SILENCE MENU Manual Art. No. DOK02.140...
  • Page 2 Brandes und Niehoff GmbH Arenskule 7-9 21339 Lüneburg Germany Tel.: +49 4131 7670200 Fax.: +49 4131 7670201 E-Mail: mail@safetec-online.de Internet: www.safetec-online.de Revisions Date Author Check Release Remark 19.08.2016 dt, kb tr, dt initial issue 02.09.2016 data sheets added, small corrections 06.04.2017...
  • Page 3: Table Of Contents

    Manual for Smoke Detection System SDS-72 Table of Content Terms and definitions............................6 3/2-way valve..............................6 Airflow detector...............................6 Block valve..............................6 CO2 section valve............................6 Control panel..............................6 Exhaust ventilation duct detector........................6 Extension panel...............................6 module..............................6 unit................................6 1.10 Galvanic isolator............................7 1.11 Indicating panel.............................7 1.12 Loop isolator..............................7...
  • Page 4 Manual for Smoke Detection System SDS-72 5.6.2 Smoke detector loop no. 2........................23 5.6.3 Restrictions when planning smoke detector loops................23 Select a fan module / fan unit........................24 Smoke detection valves and flexible hoses....................25 5.8.1 Flexible hoses for conveying hazardous atmosphere................25 5.8.2...
  • Page 5 Manual for Smoke Detection System SDS-72 10.3.2 control............................40 10.3.3 Disable function..........................40 10.3.4 Test functions............................41 10.3.5 Diagnosis functions..........................41 10.3.6 Configuration data..........................42 10.3.7 function............................43 10.3.8 RTC - Real Time Clock ........................43 10.4 Menu structure (access level 2)........................44 11 Configuration..............................45 11.1 General................................45 11.2...
  • Page 6: Terms And Definitions

    1.8 Fan module A fan module in the context of the SDS-72 smoke detection system is a single fan to draw air from the protected spaces to the smoke detection panel, extension panel(s) or smoke detection unit. At least two fan modules are required for one smoke detection system.
  • Page 7: Galvanic Isolator

    Manual for Smoke Detection System SDS-72 1 Terms and definitions 1.10 Galvanic isolator The galvanic isolator is a device which restricts the available electrical and thermal energy in an intrinsically safe circuit so that ignition of a hazardous (explosive) atmosphere cannot occur.
  • Page 8: Smoke Detection Valve

    1.21 Smoke detector loop for exhaust ventilation ducts The smoke detector loop for exhaust ventilation ducts is an option of the smoke detection system SDS-72, which allows electrical connection of smoke detectors for monitoring of exhaust ventilation ducts as required by FSS-...
  • Page 9: General

    2 General 2.1 Introduction The smoke detection system SDS-72 is a sample extraction smoke detection system for up to 72 detection lines for cargo holds onboard ships. It is complying fully with all requirements of the relevant international standards and norms.
  • Page 10: Main Variants Of System Layout

    Following the development of the regulations for smoke detection systems and CO extinguishing systems, the smoke detection system SDS-72 is available in three main variants: 3.1 Variant A The system layout is similar to the well-known pipe net layout used for the SDS-48 system. It is recommended for sampling pipe diameters of max.
  • Page 11: Variant B

    Power A Power B to / from cargo spaces Typical Arrangement of Smoke Detection System SDS-72 in CO Room, Layout Variant B 1 CO section valve 7 smoke detection panel SDS-3000 2 smoke detection valve...
  • Page 12: Variant C

    Power A Power B from cylinders Typical Arrangement of Smoke Detection System SDS-72 in Passage Way, Layout Variant C 1 junction box with loop isolator and safety barrier 8 CO section valve 2 flexible hose 9 3/2-way flap SDS-3800...
  • Page 13: Additional Smoke Detector Loop No.2 For Exhaust Ventilation Ducts

    Manual for Smoke Detection System SDS-72 3 Main variants of system layout 3.4 Additional smoke detector loop no.2 for exhaust ventilation ducts The smoke detection panels with two smoke detector loops offer the feature of connecting exhaust ventilation duct detectors directly to the smoke detection panel without the need of installing a separate fire alarm panel.
  • Page 14 Manual for Smoke Detection System SDS-72 3 Main variants of system layout In variant C the smoke detectors for the exhaust ventilation ducts can be connected to the same junction box as the smoke detection unit SDU. If you have a combination of cargo holds with hazardous area and cargo holds without...
  • Page 15: Comparison Of Variants A, B And C

    Manual for Smoke Detection System SDS-72 3 Main variants of system layout 3.5 Comparison of variants A, B and C variant A variant B variant C smoke detection devices smoke detection panel smoke detection panel smoke detection panel SDS-31xx and extension...
  • Page 16: System Components

    Manual for Smoke Detection System SDS-72 4 System components 4 System components 4.1 Main components Type Name Typical Location Remark ADP-3500 adapter module near remote panel required for remote panel SDS-3000 smoke detection panel room or passage way without integrated detection lines...
  • Page 17: Smoke Detection Unit Sds-3300 (Sdu)

    Manual for Smoke Detection System SDS-72 4 System components 4.3 Smoke detection unit SDS-3300 (SDU) The smoke detection unit SDU allows smoke detection in conjunction with large pipe diameters of up to 150 mm diameter. To prevent smoke detector pollution ahead of time, a large dust filter for different particle sizes is integrated.
  • Page 18: Planning The System

    5 Planning the system 5 Planning the system Before planning a smoke detection system SDS-72, the layout of the CO2 extinguishing system must be available. At least the following information is required for a correct planning: number of sampling pipes, •...
  • Page 19: Variant A: Select A Combination Of Smoke Detection Panel And Extension Panel(S)

    Manual for Smoke Detection System SDS-72 5 Planning the system 5.2.1 Variant A: Select a combination of smoke detection panel and extension panel(s) 1 pipe 2 pipes 3 pipes 4 pipes 5 pipes 6 pipes 7 pipes 8 pipes...
  • Page 20: Select One Or More Remote Panels

    Manual for Smoke Detection System SDS-72 5 Planning the system 18 pipes 19 pipes 20 pipes 21 pipes 22 pipes 23 pipes 24 pipes 25 pipes 26 pipes 27 pipes 28 pipes 29 pipes Standard arrangement for system variant A with 18 – 29 sampling pipes For details to smoke detection panels and extension panels see data sheets SDS-3100.01 and SDS-3200.01 in the...
  • Page 21: Locations Of Smoke Accumulators

    Manual for Smoke Detection System SDS-72 5 Planning the system see data sheets SDS-3500.01 in the appendix of this manual. 5.4 Locations of smoke accumulators „The smoke accumulators shall be located on the overhead or as high as possible in the protected space, and shall be spaced so that no part of the overhead deck area is more than 12 m, measured horizontally, from an accumulator“...
  • Page 22: Example No. 2B

    Manual for Smoke Detection System SDS-72 5 Planning the system 5.5.3 Example No. 2b 3 x 3 Smoke Accumulators Example no. 2 b is similar to example No. 2 a. It fits for longer cargo spaces, where 2 rows of smoke accumulators are not sufficient.
  • Page 23: Smoke Detector Loop No. 1

    5.6 Smoke detector loops The smoke detection panel of the smoke detection system SDS-72 can be delivered with 1 or 2 electrical smoke detector loops. Smoke detector loop no. 2 is optional. It allows a very economic monitoring of the exhaust ventilation ducts because it does not need neither a separate smoke detection panel nor separate sampling pipes.
  • Page 24: Select A Fan Module / Fan Unit

    Manual for Smoke Detection System SDS-72 5 Planning the system 5.7 Select a fan module / fan unit For selection of a fan unit /fan modules it is essential to know the number of sampling pipes and the length and diameter of each sampling pipe.
  • Page 25: Smoke Detection Valves And Flexible Hoses

    As a consequence for applications with hazardous area in the pipe net between smoke detection valve and air out, safetec recommends to use mainly steel pipes. Flexible hoses shall be used as transitions from valves, smoke detection units/panels and fan modules to the steel pipes and vice versa. If dust or water droplets...
  • Page 26: Flexible Hoses For System Variant A, Non Conductive

    Manual for Smoke Detection System SDS-72 5 Planning the system 5.8.2 Flexible Hoses for System Variant A, non conductive Article Name Diameter, Outline Remark number inner/ outer Z02.002 flexible 12,5/17,5 From 3/2-way-valve to smoke detection panel. hose Z01.403 clamp Z02.315...
  • Page 27: Flexible Hoses For System Variant A, Conductive

    Manual for Smoke Detection System SDS-72 5 Planning the system 5.8.3 Flexible Hoses for System Variant A, conductive Article Name Diameter, Outline Remark number inner/ outer Z02.400 flexible 25/32 mm From 3/2-way-valve to smoke detection panel. For hose earth connection, strip off the supporting spiral at the both ends of the hose and connect to earth.
  • Page 28: Flexible Hoses For System Variant B And C, Conductive

    Manual for Smoke Detection System SDS-72 5 Planning the system 5.8.4 Flexible Hoses for System Variant B and C, conductive Article Name Diameter, Outline Remark number inner/ outer Z02.402 flexible 60/67 mm For connection of smoke detection unit SDU. The hose hose can be cut for the required length.
  • Page 29: Transitions From Conductive Flexible Hose To Steel Pipe

    Manual for Smoke Detection System SDS-72 5 Planning the system 5.8.5 Transitions from conductive flexible hose to steel pipe For connection of flexible hose Z02.465 to 6” steel pipe, use steel extension adapters MET04.125. The steel extension adapter must be welded to the 6” pipe. Fix the flexible hose will be with a suitable clamp on the steel extension adapter.
  • Page 30: Explosion Protection

    Manual for Smoke Detection System SDS-72 6 Explosion protection 6 Explosion protection 6.1 General The areas in the smoke detection panel, in the extension panel(s), in the smoke detection unit and in the fan units, where air from the monitored cargo holds passes through, are designed to safeguard against explosion.
  • Page 31: Fan Module Sds-M0440 And Sds-M0441

    Manual for Smoke Detection System SDS-72 6 Explosion protection 6.5.1 Fan module SDS-M0440 and SDS-M0441 Information about the safeguarding against explosion of the fan units is given in the additional operation manual DOK02.055, together with useful instructions how to maintain safety.
  • Page 32: Can-Bus

    The CAN bus is a serial data bus, which serves as a connection of the smoke detection panel with the remote panel(s). The CAN bus used in the smoke detection system SDS-72 additionally includes a 24 V power supply for the connected devices.
  • Page 33: Termination Resistors For The Can Buses

    Manual for Smoke Detection System SDS-72 7 CAN-Bus 7.4 Termination resistors for the CAN buses For a correct function, each CAN bus A and CAN bus B require termination resistors 120Ω at both ends of the bus cables. Please note, that at the smoke detection panel as one end of the CAN buses termination resistors are already integrated.
  • Page 34: User Interface

    Manual for Smoke Detection System SDS-72 8 User interface 8 User interface 8.1 General The user interface of the smoke detection panel and the remote panel consists of a display (LCD), 5 indicator LEDs and 7 buttons. The image below shows the surface of the user interface with all operating elements.
  • Page 35: Soft Keys

    Manual for Smoke Detection System SDS-72 8 User interface 8.3 Soft keys The soft keys are located directly below the display. Each key has a default function, which is active if no other label is designated in the display.
  • Page 36: Indicator Led

    Manual for Smoke Detection System SDS-72 8 User interface Indicator Color State of Description LEDs Indicator LED detected. flashing At least one not acknowledged internal fault in the smoke detection or remote panel(s). Internal faults of the smoke detection panel can be: internal memory faults (RAM,EEPROM) or an automatic software reset (watchdog).
  • Page 37: Operation

    Manual for Smoke Detection System SDS-72 9 Operation 9 Operation 9.1 Start-up notification During start-up after power on or reset of the system, the display shows software name and software version of the device: Software: CM3100A Version: 01.01.000 After a short time the display shows the configuration (project) name: <Project name max.
  • Page 38: If A Detector Name Is Not Configured

    Manual for Smoke Detection System SDS-72 9 Operation 9.3.2 If a detector name is not configured If a detector name is not configured, the display shows: FIRE Detector XX/Y 1 of 1 Here is the detector address and y is the loop number.
  • Page 39: Silence-Button („Silence")

    Manual for Smoke Detection System SDS-72 9 Operation If there is at least one not acknowledged fire alarm, the label of the soft key ALARMS will be flashing. If a fault occurs, which is critical for the system function, the “SYSTEM” LED will be activated additionally to the “FAULT”...
  • Page 40: Menu (Access Level 2)

    Manual for Smoke Detection System SDS-72 10 Menu (access level 2) 10 Menu (access level 2) 10.1 General This chapter describes the menu, which is accessible during the normal operation of the smoke detection system (access level 2). A further configuration menu with restricted access (access level 3) is available in the configuration mode (see chapter „Configuration“).
  • Page 41: Test Functions

    Manual for Smoke Detection System SDS-72 10 Menu (access level 2) Please note that this menu has effect only on the control panel. If you want to enter this sub-menu on other panels the following warning will be shown: Only possible on control panel! 10.3.4 Test functions...
  • Page 42: Configuration Data

    Manual for Smoke Detection System SDS-72 10 Menu (access level 2) 10.3.5.3 Device This function is only available on the smoke detection panel. For each detector the following values will be shown: actual analog value from last polling and •...
  • Page 43: Log Function

    Manual for Smoke Detection System SDS-72 10 Menu (access level 2) 10.3.6.3 Panel configuration The sub-menu provides the following information: software name and version, • whether the panel is an control panel or not (control and indication master according EN-54).
  • Page 44: Menu Structure (Access Level 2)

    Manual for Smoke Detection System SDS-72 10 Menu (access level 2) 10.4 Menu structure (access level 2) Menu in access level 2 (to enter this menu, press SILENCE button for more than 6 seconds) │ ├── [RESET] (→ reset-dialog) │...
  • Page 45: Configuration

    The configuration of a smoke detection system can be adapted easily to different project requirements. Normally safetec delivers the smoke detection systems readily configured according the customer requirements. However a trained technician can modify certain configuration values after delivery, if required. Furthermore a trained technician can carry out the complete configuration.
  • Page 46: Required Parameters For Configuration

    Do not switch the panels into normal operation mode before the configuration process is completed! If you do so accidentally, re-configure the panel. 11.7 Required parameters for configuration The following parameters are required for configuration of the Smoke Detection System SDS-72: Menu Subject...
  • Page 47 Manual for Smoke Detection System SDS-72 11 Configuration Menu Subject Limitation Remark DEVICE → DETECTOR Fan(s) controlling by airflow ON/OFF If all detectors with the <X>/<Y> → FAN detectors setting configured reports the air flow fault, the fans will be switched over.
  • Page 48: Configuration Menu Structure (Access Level 3)

    Manual for Smoke Detection System SDS-72 11 Configuration 11.8 Configuration menu structure (access level 3) Menu in access level 3 (set configuration jumper to position “ON”) │ ├── [GENERAL] │ │ │ ├── [EDIT] (→ this module address) │...
  • Page 49: Interfaces To External Systems

    12 Interfaces to External Systems 12.1 Relay Contacts The smoke detection system SDS-72 offers voltage free relay contacts for signal transmission to external alarm monitoring systems. The relay contacts are located on the main board in the smoke detection panel and on the adapter module in the remote panel.
  • Page 50: Detector State

    Manual for Smoke Detection System SDS-72 12 Interfaces to External Systems 12.2.3 Detector state A message of this type will be sent by each change of the detector state and by the system status transmission. A typical sequence for this message is:...
  • Page 51: Fans Status And Disablement

    FANS DISABLED – state description 12.2.6 Status information Every 5 minutes SDS-72 sends the complete status information about each fault and fire alarm. The status information is preceded with this message: - $FRFIR,S,<time>,FS,01,,<total number of alarms>,,,STATUS TRANSMISSION BEGIN,*xx After that separate messages for each detector in activated or fault state and for activated faults according section „Detector state“...
  • Page 52: Fault Finding

    13 Fault finding 13 Fault finding 13.1 Table of faults All possible faults of the smoke detection system SDS-72 will be indicated on the displays of all connected panels simultaneously. Please find hereafter a description of all possible fault indications. Important Notice! Only one fault can be shown on the display at the same time.
  • Page 53 Manual for Smoke Detection System SDS-72 13 Fault finding Fault Indication Possible Cause Action Possible Values Config Memory The configuration data 1. Repeat the configuration <ADDR>: 1 - 4 Address <ADDR> saved in smoke detection process of the smoke panel are not consistent.
  • Page 54: Fault: Flow Detector X/Y

    Manual for Smoke Detection System SDS-72 13 Fault finding Fault Indication Possible Cause Action Possible Values Missing DETECTOR The detector <DET> on 1. Check the loop cable (voltage <DET>: 1 - 72 <DET> /<LOOP> loop <LOOP> is not at detector).
  • Page 55: Fans Faults

    Manual for Smoke Detection System SDS-72 13 Fault finding the block valve, smoke detection valve or 3/2-way valve is closed, or • the airflow detector of this sampling pipe is defective. • For fault finding please proceed as follows: Remove the flexible hose of the appropriate sampling pipe at the smoke detection panel resp.
  • Page 56: Fault: Short Circuit On Port A Or B

    Manual for Smoke Detection System SDS-72 13 Fault finding Important Notice! Because of the nature of the fault the system has not full redundancy in emergency addressing mode. The fault cause is to be located and removed as soon as possible.
  • Page 57: Fault Finding In Can-Bus A Or Can-Bus B

    Manual for Smoke Detection System SDS-72 13 Fault finding 13.5 Fault finding in CAN-Bus A or CAN-Bus B This type of fault can be caused by: Interrupted connections of CAN-H or CAN-L wiring • short circuit between CAN-H and CAN-L wiring •...
  • Page 58: Locate A Data Transmission Problem

    Manual for Smoke Detection System SDS-72 13 Fault finding instruction continues with the previous cable segment at the next lower address until the fault is located. The following instruction assumes a system with 3 addresses: 13.5.2.3 Localization procedure Precondition is the information about ...
  • Page 59: Contact Service For Additional Support

    Manual for Smoke Detection System SDS-72 13 Fault finding what to do ... result ... Enter the service mode (Menu → Test → Service Mode) The service mode allows acknowledging alarms at each panel. Disconnect data bus A and B connection at module address 1 If the original fault is not longer •...
  • Page 60: Commissioning And Maintenance

    Manual for Smoke Detection System SDS-72 14 Commissioning and maintenance 14 Commissioning and maintenance 14.1 General Observe MSC.1/Circ. 1318 and the rules of the responsible flag states / authorities regarding sample extraction smoke detection systems and the piping of gas extinguishing systems using CO2.
  • Page 61: Commissioning And Maintenance Checklist

    Manual for Smoke Detection System SDS-72 14 Commissioning and maintenance 14.3 Commissioning and Maintenance Checklist Steps o.k. o.k. 1 Smoke accumulators Check for location and secure mounting of the smoke collectors in the monitored areas. 2 Sampling pipe and hose connections Check all pipe and hose connections for secure fastening and support.
  • Page 62: Power Supply

    Manual for Smoke Detection System SDS-72 14 Commissioning and maintenance Steps o.k. o.k. Press SILENCE button not longer than 6 seconds. All lamps, the background light for the display and the buzzer must be on while the button is pressed.
  • Page 63: Commissioning And Maintenance Checklist For Fans

    Check the motor bearings and the complete fan unit for irregular vibrations and unusual running noise. For more details please refer to ISO 14694:2003. safetec recommends to measure vibrations on a regular base with a vibration meter (Art. No. B06.970).
  • Page 64 "XP95 I.S." Junction Box with Loop Isolator Suction Fan SDS- and Galvanic Isolator SDS-M0460 3700 Refer to protection notice ISO 16016. Rev.4 04.11.2016 Smoke Detection System SDS-72, Variant A safetec Overview-Variant-A Check 07.11.2016 AB Overview Plan for Electric Installation Approv. 09.11.2016...
  • Page 65 Junction Box with Loop Isolator Suction Fan Flap SDS- and Galvanic Isolator SDS-M0460 SDS-3800 3700 Refer to protection notice ISO 16016. Rev.3 09.11.2016 Smoke Detection System SDS-72, Variant B safetec SDS-72-B Check 07.11.2016 AB Overview Plan for Electric Installation Approv. 03.03.2016...
  • Page 66 Junction Box with Loop Isolator Suction Fan Flap SDS- and Galvanic Isolator SDS-M0460 SDS-3800 3700 Refer to protection notice ISO 16016. Rev.4 09.11.2016 Smoke Detection System SDS-72, Variant C safetec SDS-72-C Check 07.11.2016 AB Overview Plan for Electric Installation Approv. 03.03.2016...
  • Page 67 < NEXT ALARM > POWER DISABLED FIRE FAULT SYSTEM SILENCE RESET Main Board (Terminal Module) for Smoke Detection System SDS-72 (Art. No. BG03.501) Terminals Terminal Terminal Terminal X5 / X4 Power Power CAN Bus A CAN Bus B RS422 /...
  • Page 68 All resistors 0,6W 1% if not otherwise stated. Refer to protection notice ISO 16016. Rev. KUNDE 19.12.2016 Smoke Detection Panel SDS-3104 (Part: Detection Box) safetec SDS-72-3104 Check PROJEKT 23.01.2017 Intrinsically Safe Circuits in Detection Box for max. 4 Sampling Pipes Approv. AUFTRAGSNR...
  • Page 69 All resistors 0,6W 1% if not otherwise stated. evaluation box Refer to protection notice ISO 16016. Rev. KUNDE 23.01.2017 Smoke Detection Panel SDS-3108 / Extension Panel SDS-3208 safetec SDS-72-3108 Check PROJEKT 23.01.2017 Part: Detection Box with Intrinsically Safe Circuits for max. 8 Sampling Pipes Approv. AUFTRAGSNR 23.01.2017...
  • Page 70 Refer to protection notice ISO 16016. Rev. KUNDE 23.01.2017 Smoke Detection Panel SDS-3112 / Extension Panel SDS-3212 safetec SDS-72-3112 Check PROJEKT 23.01.2017 Part: Detect. Boxes with Intrinsically Safe Circuits for max. 12 Sampling Pipes Approv. AUFTRAGSNR 23.01.2017...
  • Page 71 All resistors 0,6W 1% if not otherwise stated. isolators in evaluation box Refer to protection notice ISO 16016. Rev. KUNDE 23.01.2017 Extension Panel SDS-3216 safetec SDS-72-3216 Check PROJEKT 23.01.2017 Part: Detect. Boxes with Intrinsically Safe Circuits for max. 16 Sampling Pipes Approv. AUFTRAGSNR 23.01.2017...
  • Page 72 Ausgabe: 29.09.2017 SDS-72 FIRE ALARM PANEL CP-3100 safetec < NEXT ALARM > POWER DISABLED FIRE FAULT SYSTEM SILENCE RESET Adapter ADP-3500 for Remote Panel SDS-3500 CAN Bus A CAN Bus B NMEA Fire Fire Alarm Fault Disabled Open Remarks (RS422 /...
  • Page 73 Pre Fuse Pre Fuse 16 A 16 A All resistors 0,6W 1% if not otherwise stated. Refer to protection notice ISO 16016. Rev. KUNDE 02.12.2015 Junction Box SDS-3600 with Fan Motors SDS-M0460 safetec SDS-72-3600 Check PROJEKT 01.09.2016 Approv. AUFTRAGSNR 02.09.2016...
  • Page 74 All resistors 0,6W 1% if not otherwise stated. Refer to protection notice ISO 16016. Rev. customer 30.01.2018 Detector Loop 2: Junction Box SDS-3700 with Smoke Detection Unit SDS- safetec SDS-72-3700-3300-XP95-IS Check project 06.02.2018 3300 (SDU) and Smoke Detectors XP95 I.S. for Exhaust Ventilation Ducts Approv. order no.
  • Page 75 All resistors 0,6W 1% if not otherwise stated. Refer to protection notice ISO 16016. Rev. customer 30.01.2018 Detector Loop 2: Junction Box SDS-3700 with Air Exhaust Duct Detectors safetec SDS-72-3700-XP95-IS Check project 06.02.2018 for one Cargo Hold (hazardous atmosphere) Approv. order no.
  • Page 76 Refer to protection notice ISO 16016. Rev. customer 30.01.2018 Detector Loop 2 for Exhaust Duct Detectors safetec SDS-72-3700-XP95-Discovery Check project 06.02.2018 Variant A and B Approv. order no. 06.02.2018...
  • Page 77 SDS-72 FIRE ALARM PANEL CP-3100 safetec < > NEXT ALARM POWER DISABLED FIRE FAULT SYSTEM SILENCE RESET Description The Smoke Detection Panel SDS-3000 is normally located in the CO2 room of a vessel. The operation interface allows monitoring of the system state (alarm, fault and status messages) as well as manually switching the fans and reseting alarms.
  • Page 78 SDS - 72 FI RE AL ARM P ANEL CP - 3100 safetec SDS - 72 FI RE AL ARM P ANEL CP - 3100 safetec SDS - 72 FI RE AL ARM P ANEL CP - 3100 safetec <...
  • Page 79 SDS-3216 SDS03.213 1270 mm 380 x 1200 x 210 mm 57 kg SDS03.214 58 kg SDS03.215 59 kg SDS03.216 60 kg Refer to protection notice ISO 16016. Rev.0 21.01.2016 Extension Panels safetec SDS-3200.01 Check 26.08.2016 Tal Type: SDS-32xx Approv. 26.08.2016...
  • Page 80: Alarm Threshold

    Alarm Threshold SDS03.340 10 - 60 m³/h 4 - 24 m³/h SDS03.342 30 - 180 m³/h 12 - 72 m³/h Refer to protection notice ISO 16016. safetec Smoke Detection Unit SDU Rev.7 27.02.2018 SDS-3300.01 Check 27.02.2018 kb Type: SDS-3300 Approv. 27.02.2018...
  • Page 81 SDS-72 FIRE ALARM PANEL CP-3100 safetec SDS-72 FIRE ALARM PANEL CP-3100 safetec < NEXT ALARM > < NEXT ALARM > POWER DISABLED FIRE FAULT SYSTEM POWER DISABLED FIRE FAULT SYSTEM SILENCE SILENCE MENU MENU Desk Panel Mounting Instruction Countersunk Head Screws...
  • Page 82: Article Numbers

    Instruction 4 x screws M3 4 x distance bolts M3 x 10 mm 4 x threads M3 safetec 4 x D = 3,5 mm Adapter Module ADP-3500 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70...
  • Page 83 Junction Box for 2 Suction Fans 230V 3~ SDS03.621 Junction Box for 2 Suction Fans 110V 3~ Refer to protection notice ISO 16016. Rev.1 23.12.2015 Junction Box for 2 Suction Fans safetec SDS-3600.01 Check 23.12.2015 Tal Type: SDS-3600 Approv. 23.12.2015...
  • Page 84 1 output with loop isolator and galvanic isolator SDS03.704 4x M20 or M25 2 outputs with loop isolator and galvanic isolators Refer to protection notice ISO 16016. Rev.1 30.01.2018 Junction Box with Loop Isolator and Safety Barrier(s) safetec SDS-3700.01 Check 06.02.2018 kb Type: SDS-3700 Approv. 06.02.2018...
  • Page 85 3,9 kg Stainless steel 1.4301 SDS03.805 174,3 137,5 112,5 337,5 151,2 251,2 2,3 kg Stainless steel 1.4301 Refer to protection notice ISO 16016. Rev.3 20.04.2018 3/2-Way Flap for Fan Module SDS-M0460 safetec SDS-3800.01 Check 20.04.2018 JP Type: SDS-3800 Approv. 20.04.2018...
  • Page 86 230V: 2,3A (50Hz), 2,7A (60Hz) Method of installation: upright on shock mounts clearance: 300mm above and 50mm beside Article number: SDS02.440 Refer to protection notice ISO 16016 Rev.12 28.02.2018 Fan Unit SDS-M0440 safetec SDS-M0440.01 Check 28.02.2018 JP 220 V / 230 V Approv. 28.02.2018...
  • Page 87 Rated current: Method of installation: upright on shock mounts clearance: 300mm above and 50mm beside Article number: SDS02.441 Refer to protection notice ISO 16016 Rev.6 26.02.2018 Fan Unit SDS-M0441 safetec SDS02.441.01 Check 26.02.2018 eng 110 V / 115 V Approv. 26.02.2018...
  • Page 88 2. The dotted lines are already wired by manufactorer 3. Motor is rotating clockwise 4. The wiring diagram for fan no. 2 is correspondend 5. Adjust the overcurrent protection to 6A. safetec Art.Nos.: Motor type Hanning 277940387: FAN02.131 Motor circuit breaker (without housing): F05.015...
  • Page 89 60 Hz 150 mm SDS03.469 Fan Module 50 Hz 150 mm FAN06.235 Vibration Damper; set of 6 pcs. for 1 Fan Module Refer to protection notice ISO 16016 safetec Fan Module Rev.1 18.04.2018 SDS-M0460.01 Check 18.04.2018 JP Type: SDS-M0460 Approv.
  • Page 90 Fastening Points mounting base to free air distance piece from cargo holds from cargo holds 2495 Refer to protection notice ISO 16016 safetec Fan Modules and 3/2-Way Flap Rev.1 26.04.2018 SDS-M0460.03 Check 26.04.2018 HZ Typical Arrangement and Fastening Points Approv.