MODEL LUT-SHUNT-A-TD-5 INSTALLATION INSTRUCTIONS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS
SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. This product can be used with LED, ballast, tungsten, and general use loads.
2. Make sure all connections are in accordance with the National Electrical Code and local regulations.
3. To reduce the risk of electric shock, disconnect both normal and emergency power supplies before servicing.
4. This product is intended to be used to control indoor and outdoor located loads.
5. An unswitched AC power source is required (120-240VAC/277VAC).
6. Do not install near gas or electric heaters.
7. Do not attempt to service a sealed Emergency Power Control. When malfunctioning, return to the
manufacturer: LVS, LLC. 15007 Wicks Blvd, San Leandro, CA 94577.
8. The use of untested accessory equipment is not recommended by the manufacturer and may cause unsafe
condition.
9. Do not use this product for other than its intended use.
10. Servicing should be performed by qualified service personnel.
11. Equipment should be mounted in locations and at heights where it will not readily be subjected to
tampering by unauthorized personnel.
LVS, LLC warrants to the original purchaser/user for the published warranty period from the date of shipment that
should LVS instruments or equipment prove defective by reason of improper workmanship or material, LVS will repair or
replace the same equipment without charge. The warranty does not cover defects or malfunctions arising from improper
installation, operation or repair, neglect, accident, or abuse. LVS will honor its warranty provided the equipment has not
been physically damaged, improperly installed or connected. To obtain warranty/repair, the defective product should be
shipped freight prepaid within the warranty period to the address below. To the extent permitted by applicable law, all
warranties extending beyond repair or replacement as described above are disclaimed, including the implied warranties
of merchantability and fitness for a particular purpose. Where applicable law prohibits disclaimers or the implied
warranties of merchantability and fitness; those warranties are limited to 12 months from the date of shipment. LVS
provides a 90-day money back guarantee if equipment does not perform in accordance with LVS published
specifications. The liability of LVS and its agents under all warranties is limited to repair and replacement as described
herein and under no circumstances shall there be liability for any other kind of loss, damage, or labor, either
consequential or for injury to person or property or otherwise.
Electrical Specfications
120-240/277V Sensing Input
120-277V Load Ratings:
16 Amp Electronic Ballast/LED/General Use
5 Amp Magnetic Ballast
1800W(120V)/3000W(277V) Incandescent
Normally Closed Output Contact
UL924 Listed (usUL/cUL)
! IMPORTANT SAFEGUARDS !
SAVE THESE INSTRUCTIONS
5-Year Limited Warranty
LVS, LLC. 15007 Wicks Blvd., San Leandro, CA 94577-4216
Phone: 510-352-9600
Web: WWW.LVSCONTROLS.COM
Mechanical Specifications
Hub mount to 1/2" K.O.
Suitable for installation in the plenum
Tested to UL2043 (Plenum Rated)
Shipping Weight: 8 oz Color : Black
Temperature: 0°C-60°C (32°F - 140°F)
Body Size: 3-5/8" x 1-5/8" x 1-3/8" (With Hub/Ears)
Mounted Size: 2-1/2" x 1-5/8" x 1-3/8"
(Without Hub/Ears)
1-800-982-4587
1
Need help?
Do you have a question about the LUT-SHUNT-A-TD-5 and is the answer not in the manual?
Questions and answers