VESDA-E 19" Sub-Rack Remote Unit Installation Instructions
These installation instructions provide essential information for installing the VESDA-E Sub-Rack Remote Unit in accordance with the system design. Additional installation and product documentation are listed below
in the Reference Documents section.
System Components
The VESDA-E Sub-Rack Remote Unit is shipped with the following components:
1 VESDA-E 19" Sub-Rack (VEK-0000)
1 VESDA-E Sub-Rack Remote Box (VEK-)
1 installation instruction sheet
1 VESDA Device Safety Instruction Sheet
Prerequisites
Completed VESDA network design.
24V DC Power Supply, compliant with local codes and standards.
Type A to Type B USB Interface Lead for initial configuration of this device.
Conduit should be used in a way that is suitable to cable glands that are compliant with the IP rating of
this device.
Cable termination for Screw terminal blocks (0.2-1.5 sq mm, 24-16 AWG)
PC or laptop installed with Xtralis VSC for initial configuration.
Standard connection instructions for where the VESDA-E Sub-Rack Remote Unit is to be added to a
corporate network.
Standards Compliance
UL and ULC
Please refer to the Regional Regulatory Requirements and Notices section in the VESDA-E Remote
Accessories Product Guide (Doc. 37188).
Power Consumption
Supply Voltage
VEK-A10-0
VEK-A10-7 VEK-A10-12
Max Power
2.112 W
3.35 W
(with Alarm)
Peak Current
0.09 A
0.14 A
(with Alarm)
Relays
Programmable to latch or not latch alarm or fault states
19" Sub-Rack
current
Environmental Requirements
Temperature
Ambient: 0°C to 39°C (32°F to 102°F)
Humidity: 5 to 95% RH, non-condensing
Reference Documents
Additional installation and product information are contained in the following documents, which are
available for download at www.xtralis.com.
37188 - VESDA-E Remote Accessories Product Guide
48996 - VESDA-E Remote Accessories Quick Start Guide
To visit the product's web page, please scan this QR code:
Installation Instructions
Notes
18 - 30 VDC
VEK-A30
VEK-A40-7 VEK-A40-12
4.14 W
0.74 W
1.93 W
0.17 A
0.03 A
0.08 A
Contacts rated 2A @ 30 VDC (Resistive)
2A Max
The VESDA-E 19" Sub-Rack Remote Unit is an array of 4
Sub-Rack Remote Box Models and can be mounted on a 19"
Sub-Rack.
Note: It cannot operate without a fully loaded sub-rack.
Once unboxed, please ensure the Relay plugs are plugged
in on the rear side of the device as shown to avoid any static
charges while handling.
Note: Connections are made following the legend shown in
Figure 2 Socket Locations.
The 19" Sub-Rack can be stacked in a vertical array using
Din Rails or server rack mounts system.
Ensure the assembled VESDA-E 19" Sub-Rack
Remote Unit mount holes align with the 19" server
rack / Din Rail mount holes, position for continuous
repetition stack with minimum gap i.e. 1U hole
position.
www.acornfiresecurity.com
Assembling VESDA-E Sub-Rack Remote Box to the 19" Sub-Rack
Assembling a VESDA-E 19" Sub-Rack Remote Unit
VESDA-E Sub-Rack Remote Box is designed to be flexible in its configuration option in mounting on a
Ensure sufficient access to the rear side of the 19" Sub-Rack.
19" Sub-Rack.
1. The VESDA-E Sub-Rack Remote Box (A) is rested on the base metal platform of the 19" Sub-Rack
(C) provided.
2. Match the locater pin (D) shown on th 19" Sub-Rack (B) to the slot feature (i) provided on the
VESDA-E Sub-Rack Remote Box (A) and slide-in gently.
3. Push the VESDA-E Sub-Rack Remote Box (A) gently till the rear standoff (E) bottoms to the 19"
2.77 W
Sub-Rack (B) inside rear face (F).
4. Secure each VESDA-E Sub-Rack Remote Box (A) from the rear side of 19" Sub-Rack (B) using four
screws (G) provided.
0.12 A
VE Sub-Rack Remote Box Single Device
Provided is a scenario where less than 4 units of Sub-Rack Remote Boxes are used, then the
subsequent empty slots in 19" Sub-Rack should be installed with a VEK-0 blank box to bridge the
VESDAnet communication.
Warning:
Make sure that there are Jumper card PCB installed (i) to all VEK-0 Sub-Rack Blank Box
Position, otherwise the device will raise open loop fault.
Avertissement : Assurez-vous qu'un circuit imprimé de carte de couplage est installé (i) à tous les
emplacements de boîtier vide de casier VEK-0. Dans le cas contraire, l'appareil
déclenchera un défaut de boucle ouverte.
Field Wiring Assembled VESDA-E 19" Sub-Rack Remote Unit
2
2
The VESDA-E 19" Sub-Rack Remote Unit provides rear access for Power, VESDAnet, Relays and
Ethernet connections while the backplane interconnects the power and VESDAnet connections between
various VESDA-E Sub-Rack Remote Box models stacked/assembled in a 19" Sub-Rack.
Power:
The VESDA-E 19" Sub-Rack Remote Unit can be powered with an external 24 VDC Power Supply
(compliant with local codes and standards) / VESDA-E detector via designated PWR IN socket at
rear side.
Note: The VESDA-E 19" Sub-Rack Remote Unit will not operate if the power supply polarity is
reversed.
Use the designated PWR OUT socket to connect up to three VESDA-E 19" Sub-Rack Remote Units
in a daisy chained manner for vertical stack mounting to the PWR IN socket on each subsequent
VESDA-E 19" Sub-Rack Remote Unit connected from the same power supply.
Connection to VESDAnet:
The VESDAnet A & B connector at the rear side is used for loop-in/loop-out connection as below.
Shield
Shield
A-
A-
A+
A+
Shield
Shield
B-
B-
B+
B+
Module 1
Module 2
Shield
A-
A+
Shield
B-
B+
Module 5
Note:
For the chassis grounding requirement, use the Ring Terminal Grounding Lug (symbol 1)
with a maximum outer diameter of 9 mm at any chassis grounding points (marked with
ground symbol 2).
www.acornfiresecurity.com
1
2
D
B
E
C
A
C
G
E
i
G
F
i
BACKPLANE
BACKPLANE
EXTERNAL PWR
RJ45 PORT
EXTERNAL PWR
IN/OUT
FOR
VESDAnet
PORT
CONNECTORS
VEK -A30 BOX
CONNECTORS
Will be closed with RJ45 Blank cap when not used
+
-
+
-
+
-
+
-
PWR IN PWR OUT
VESDANET A
VESDANET B
VEK-0
VEK- A30
VEK- A10-7
The diagram shows an example of the wiring for a
Shield
A-
closed VESDAnet loop, which is the recommended
A+
configuration. It is recommended that 120 Ohm
Shield
twisted pair cables (e.g. Belden 9841) be used
B-
B+
for including the devices in the network, with a
Module 3
maximum length between devices of 1.2 km. The
polarity of the data wires must be maintained
Shield
throughout the network.
A-
A+
Shield
B-
B+
Module 4
3
D
E
F
4
1
2
2
VEK- A10-12

Advertisement

loading
Need help?

Need help?

Do you have a question about the VESDA-E and is the answer not in the manual?

Questions and answers

Summary of Contents for Xtralis VESDA-E

  • Page 1 VESDA-E 19” Sub-Rack Remote Unit Installation Instructions www.acornfiresecurity.com These installation instructions provide essential information for installing the VESDA-E Sub-Rack Remote Unit in accordance with the system design. Additional installation and product documentation are listed below in the Reference Documents section.
  • Page 2 This document is subject to copyright owned by Xtralis. You agree not to copy, communicate to the public, adapt, distribute, transfer, sell, modify or publish any contents of this document without the express prior written consent of Xtralis.

This manual is also suitable for:

Vek-a10-0Vek-a10-7Vek-a10-12Vek-a30Vek-a40-7Vek-a40-12