VESDA-E 19" Sub-Rack Remote Unit Installation Instructions
These installation instructions provide essential information for installing the VESDA-E Sub-Rack Remote Unit in accordance with the system design. Additional installation and product documentation are listed below
in the Reference Documents section.
System Components
The VESDA-E Sub-Rack Remote Unit is shipped with the following components:
•
1 VESDA-E 19" Sub-Rack (VEK-0000)
•
1 VESDA-E Sub-Rack Remote Box (VEK-)
•
1 installation instruction sheet
•
1 VESDA Device Safety Instruction Sheet
Prerequisites
•
Completed VESDA network design.
•
24V DC Power Supply, compliant with local codes and standards.
Type A to Type B USB Interface Lead for initial configuration of this device.
•
•
Conduit should be used in a way that is suitable to cable glands that are compliant with the IP rating of
this device.
•
Cable termination for Screw terminal blocks (0.2-1.5 sq mm, 24-16 AWG)
PC or laptop installed with Xtralis VSC for initial configuration.
•
•
Standard connection instructions for where the VESDA-E Sub-Rack Remote Unit is to be added to a
corporate network.
Standards Compliance
UL and ULC
Please refer to the Regional Regulatory Requirements and Notices section in the VESDA-E Remote
Accessories Product Guide (Doc. 37188).
Power Consumption
Supply Voltage
VEK-A10-0
VEK-A10-7 VEK-A10-12
Max Power
2.112 W
3.35 W
(with Alarm)
Peak Current
0.09 A
0.14 A
(with Alarm)
Relays
Programmable to latch or not latch alarm or fault states
19" Sub-Rack
current
Environmental Requirements
•
Temperature
•
Ambient: 0°C to 39°C (32°F to 102°F)
•
Humidity: 5 to 95% RH, non-condensing
Reference Documents
Additional installation and product information are contained in the following documents, which are
available for download at www.xtralis.com.
•
37188 - VESDA-E Remote Accessories Product Guide
•
48996 - VESDA-E Remote Accessories Quick Start Guide
To visit the product's web page, please scan this QR code:
Installation Instructions
Notes
18 - 30 VDC
VEK-A30
VEK-A40-7 VEK-A40-12
4.14 W
0.74 W
1.93 W
0.17 A
0.03 A
0.08 A
Contacts rated 2A @ 30 VDC (Resistive)
2A Max
The VESDA-E 19" Sub-Rack Remote Unit is an array of 4
Sub-Rack Remote Box Models and can be mounted on a 19"
Sub-Rack.
Note: It cannot operate without a fully loaded sub-rack.
Once unboxed, please ensure the Relay plugs are plugged
in on the rear side of the device as shown to avoid any static
charges while handling.
Note: Connections are made following the legend shown in
Figure 2 Socket Locations.
The 19" Sub-Rack can be stacked in a vertical array using
Din Rails or server rack mounts system.
•
Ensure the assembled VESDA-E 19" Sub-Rack
Remote Unit mount holes align with the 19" server
rack / Din Rail mount holes, position for continuous
repetition stack with minimum gap i.e. 1U hole
position.
www.acornfiresecurity.com
Assembling VESDA-E Sub-Rack Remote Box to the 19" Sub-Rack
Assembling a VESDA-E 19" Sub-Rack Remote Unit
VESDA-E Sub-Rack Remote Box is designed to be flexible in its configuration option in mounting on a
Ensure sufficient access to the rear side of the 19" Sub-Rack.
19" Sub-Rack.
1. The VESDA-E Sub-Rack Remote Box (A) is rested on the base metal platform of the 19" Sub-Rack
(C) provided.
2. Match the locater pin (D) shown on th 19" Sub-Rack (B) to the slot feature (i) provided on the
VESDA-E Sub-Rack Remote Box (A) and slide-in gently.
3. Push the VESDA-E Sub-Rack Remote Box (A) gently till the rear standoff (E) bottoms to the 19"
2.77 W
Sub-Rack (B) inside rear face (F).
4. Secure each VESDA-E Sub-Rack Remote Box (A) from the rear side of 19" Sub-Rack (B) using four
screws (G) provided.
0.12 A
VE Sub-Rack Remote Box Single Device
Provided is a scenario where less than 4 units of Sub-Rack Remote Boxes are used, then the
subsequent empty slots in 19" Sub-Rack should be installed with a VEK-0 blank box to bridge the
VESDAnet communication.
Warning:
Make sure that there are Jumper card PCB installed (i) to all VEK-0 Sub-Rack Blank Box
Position, otherwise the device will raise open loop fault.
Avertissement : Assurez-vous qu'un circuit imprimé de carte de couplage est installé (i) à tous les
emplacements de boîtier vide de casier VEK-0. Dans le cas contraire, l'appareil
déclenchera un défaut de boucle ouverte.
Field Wiring Assembled VESDA-E 19" Sub-Rack Remote Unit
2
2
The VESDA-E 19" Sub-Rack Remote Unit provides rear access for Power, VESDAnet, Relays and
Ethernet connections while the backplane interconnects the power and VESDAnet connections between
various VESDA-E Sub-Rack Remote Box models stacked/assembled in a 19" Sub-Rack.
Power:
•
The VESDA-E 19" Sub-Rack Remote Unit can be powered with an external 24 VDC Power Supply
(compliant with local codes and standards) / VESDA-E detector via designated PWR IN socket at
rear side.
Note: The VESDA-E 19" Sub-Rack Remote Unit will not operate if the power supply polarity is
reversed.
•
Use the designated PWR OUT socket to connect up to three VESDA-E 19" Sub-Rack Remote Units
in a daisy chained manner for vertical stack mounting to the PWR IN socket on each subsequent
VESDA-E 19" Sub-Rack Remote Unit connected from the same power supply.
Connection to VESDAnet:
•
The VESDAnet A & B connector at the rear side is used for loop-in/loop-out connection as below.
Shield
Shield
A-
A-
A+
A+
Shield
Shield
B-
B-
B+
B+
Module 1
Module 2
Shield
A-
A+
Shield
B-
B+
Module 5
Note:
For the chassis grounding requirement, use the Ring Terminal Grounding Lug (symbol 1)
with a maximum outer diameter of 9 mm at any chassis grounding points (marked with
ground symbol 2).
www.acornfiresecurity.com
1
2
D
B
E
C
A
C
G
E
i
G
F
i
BACKPLANE
BACKPLANE
EXTERNAL PWR
RJ45 PORT
EXTERNAL PWR
IN/OUT
FOR
VESDAnet
PORT
CONNECTORS
VEK -A30 BOX
CONNECTORS
Will be closed with RJ45 Blank cap when not used
+
-
+
-
+
-
+
-
PWR IN PWR OUT
VESDANET A
VESDANET B
VEK-0
VEK- A30
VEK- A10-7
The diagram shows an example of the wiring for a
Shield
A-
closed VESDAnet loop, which is the recommended
A+
configuration. It is recommended that 120 Ohm
Shield
twisted pair cables (e.g. Belden 9841) be used
B-
B+
for including the devices in the network, with a
Module 3
maximum length between devices of 1.2 km. The
polarity of the data wires must be maintained
Shield
throughout the network.
A-
A+
Shield
B-
B+
Module 4
3
D
E
F
4
1
2
2
VEK- A10-12