Meteo Control 592.722 User Manual

Meteo Control 592.722 User Manual

Control cabinets

Advertisement

Quick Links

meteocontrol Control Cabinets
User manual
For item numbers
592.722 – 592.734
592.850 – 592.854
Version 20241025

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 592.722 and is the answer not in the manual?

Questions and answers

Summary of Contents for Meteo Control 592.722

  • Page 1 Control Cabinets User manual For item numbers 592.722 – 592.734 592.850 – 592.854 Version 20241025...
  • Page 2 Copyright and protection rights Copyright for this manual remains with the manufacturer. No part of this manual may be reproduced or edited, duplicated or distributed using electronic systems without written permission from meteocontrol GmbH. Compensation shall be payable in the event of any copyright infringements. All brand names mentioned in this manual are the property of their respective manufac- turers and are hereby acknowledged.
  • Page 3: Release Notes

    Release notes Date Changes 20241024 Added information about "Residual Current Device" Adjusted footer Added links to the declaration of conformity and RoHS statement on meteocontrol website 20240822 Specific item numbers of stations added. 20240730 Note added regarding functional earthing for sensor cables. 20230301 Format and safety instructions updated.
  • Page 4: Table Of Contents

    Contents General notes ........................ 3 Safety instructions ....................3 Warning notices ..................... 3 Additional information..................... 3 Advice on using the user manual ................4 Purpose of this user manual................... 4 Target group and qualification ................4 Warranty and liability ....................5 Additional documentation ..................
  • Page 5: General Notes

    General notes Safety instructions Safety instructions warn of dangers when using the devices and explain how they can be avoided. The safety instructions are classified according to the severity of the risk and are subdivided into four groups: DANGER Imminent danger Failure to comply with the warning notice will lead to an imminent risk of death or serious physical injury! WARNING...
  • Page 6: Advice On Using The User Manual

    Advice on using the user manual Purpose of this user manual This user manual is an essential aid for the proper operation of the meteocontrol stations (here- inafter referred to as "control cabinets"). It will help to avoid dangers, to reduce repair costs and downtimes, and to increase the reliability and service life of the control cabinets and their built-in components.
  • Page 7: Warranty And Liability

    Warranty and liability The scope, period and form of the warranty are specified in the general terms and conditions of meteocontrol GmbH. meteocontrol rejects any liability for damage arising from the non-observance of the user manual. This applies, in particular, for damage from: •...
  • Page 8: Product Description

    Product description The meteocontrol switch cabinets contain measurement technology devices for the central col- lection and processing of all system data ("Data Stations") and, depending on the version, for the implementation of grid feed-in management ("Power Control Stations") in photovoltaic power plants.
  • Page 9: Transportation

    Transportation Every product leaves our factory in perfect electrical and mechanical condition. On delivery, un- pack the control cabinet and all accessories and check them for any damage. WARNING A damaged control cabinet must not be put into operation! Transport the control cabinet using a forklift or pallet truck. During transport, ensure the control cabinet is sufficiently secured in place in order to prevent overturning or movement.
  • Page 10 The following illustrations show possible options for transport of the control cabinet. Fig. 3: Transportation lying on the rear panel Fig. 2: Transportation lying on the side Fig. 4: Transport without a pallet Fig. 5: Do not transport by crane Fig.
  • Page 11: Safety

    Safety This chapter contains general safety regulations that must be followed during installation, opera- tion, and maintenance of the control cabinet. Failure to do so can result in injury or death and/or damage the control cabinet. Read these safety regulations before working on the control cabinet. Intended use The connections for the control cabinets and modules used here may only be loaded with the signals and signal strengths permitted for this purpose.
  • Page 12 • Turn off all possible power sources. • All other possible live parts must be protected from contact. • Special precautionary measures are required when working close to bare conductors. • Ensure that the control cabinet is disconnected from the power supply. Always perform measurements to ensure the control cabinet is in a de-energized state.
  • Page 13: Mounting And Installation

    Mounting and installation Safety instructions for installation DANGER Electric shock hazard! Danger to life and limb! Fatal injuries or death from contact with lines and terminals. • Only connect or disconnect lines while they are de-energized. Take measures to prevent the power line from being reactivated. CAUTION Hazard with a risk of personal injury •...
  • Page 14 NOTICE Damage due to overvoltage! Overvoltage or voltage peaks damage or destroy the device. • Protect the power supply against electrical surges. Voltages of more than 10 V DC and currents of more than 50 mA on the analog inputs can destroy the respective measuring inputs. •...
  • Page 15: Workflow For Mounting, Installation, And Commissioning

    Workflow for mounting, installation, and commissioning Step Action Comment Unpack the control cabinet and check it for damage. For more information, see Chapter 4 Transportation. Check whether all necessary modules and devices are provided Only devices in perfect condition may and in perfect condition.
  • Page 16: Mounting The Control Cabinet

    Mounting the control cabinet The control cabinet is generally suitable for installation in indoor and outdoor areas, depending on the model. Observe the following instructions for wall installation: • Ensure that the mounting surface is horizontal and as level as possible to prevent leakage due to warping of the enclosure.
  • Page 17: Installing The Network Cable

    Installing the network cable To install a network cable in the control cabinet, there are two cable glands in the enclosure with a split sealing insert. Fig. 9: Cable gland with split sealing insert Step Action To lay the network cable, first remove the cable gland from the control cabinet. Remove the dummy plug from the cable gland of the control cabinet.
  • Page 18: Installation

    6.5 Installation 6.5.1 Cables and wires Recommended wire and cable types for wiring the individual system components are given below. Wiring restrictions are also listed. Type Product designation Item number Max. permissi- ble length Bus cabling (inverter) UNITRONIC Li2YCYv (TP) data cable 200.116 2) 1) 2x2x0.5 mm²...
  • Page 19: Commissioning

    Commissioning This chapter describes the commissioning procedure for the control cabinet. Installation, commissioning and maintenance of the control cabinet may only be performed by a qualified electrician. RISK OF ELECTRIC SHOCK Electric shock hazard! Danger to life and limb! • Observe the safety instructions during installation and commissioning! See Chapter 5 Safety.
  • Page 20: Care And Maintenance

    Care and maintenance The control cabinet only requires minimal maintenance when installed in a proper environment. meteocontrol recommends an annual inspection of the control cabinet to ensure optimal opera- tion. Furthermore, a periodic verification must be carried out in accordance with IEC 60364-6 – "Low voltage electrical installations –...
  • Page 21: Technical Data

    CAUTION Hazard due to moving rotors There is a risk of injury if the fan wheel of the control cabinet cooler moves during maintenance! • Secure the fan by mechanically blocking the rotors. For this, the fan must be secured by means of a pencil or similar tool; this is to prevent the fan from being set in motion at a high rotational speed by compressed air or water.
  • Page 23 Text and illustrations represent state-of-the-art technology at time of printing  Subject to technical modifications  We assume no liability for printing errors. Further information: www.meteocontrol.com Visit the mc Help Center: https://help-center.meteocontrol.com/blue-log-xm-xc/ Item number: 832069 Version 20241025...

This manual is also suitable for:

592.734592.850592.854

Table of Contents