TABLE OF CONTENTS TABLE OF CONTENTS Overview ................................3 Sequence of Operation ............................3 Design and Installation Guidelines ........................3 ZP4-ESP-FAV Panel Layout ..........................4 System Wiring ..............................5-9 Warning! ..............................5 Caution! ..............................5 Mounting the Panel ..........................5 System Power ............................5 HVAC System ............................
OVERVIEW The ZP4-ESP-FAV is a residential and light commercial forced air zone control system that allows a single HVAC unit to have up to 4 separate zones. The panel can be used with single stage or multi- stage heat/cool equipment as well as heat pump and dual fuel systems having up to 3 stages of heating and 2 stages of cooling.
ZP4-ESP-FAV PANEL LAYOUT 3 AMP FUSE PROTECTS CIRCUIT POWER BOARD POWER 3 AMP 3 AMP 24 VOLT POWER ZONE 1 THERMOSTAT ZONE 1 DAMPER W1-AUX W1-AUX W2-O/B W2-O/B GRAPHIC ZONE PROGRAMMING ZONE 2 DAMPER DAMPER DISPLAY MODULE POSITION LEDs (ON WHEN ZONE 3 DAMPER OPEN) ZONE 2 THERMOSTAT...
SYSTEM WIRING WARNING! 1. Turn power off to HVAC equipment and control panel during installation to prevent serious injury from electrical shock and/or damage to the system. 2. Use extreme care when making duct openings and handling sheet metal to avoid injury. 3.
SYSTEM WIRING DH Terminals The ZP4-ESP-FAV has a set of terminals marked DH that are a normally open dry contact input designed for an optional dehumidistat. When the HVAC system is in the cooling mode and the humidity is above the dedhumidistat setpoint, the cooling setpoint will be overridden and the equipment will continue to run until either the dehumidistat setpoint is reached or the equipment is shut off...
SYSTEM WIRING SENSORS The SENSOR terminals provide inputs for Discharge Air (DAS), Return Air (RAS) and Outdoor Temperature (OTS) sensors. All sensors are NTC Type III thermistors rated at 10K Ohms @ 77° F. Discharge Air Sensor Mount the discharge air sensor in the main supply duct out of the line of sight of the heat exchanger or cooling coil and upstream of any duct transitions or zone dampers.
SYSTEM WIRING SPS Terminals The SPS terminals wire to the ZPA-SPS Static Pressure Sensor. The sensor should be installed on a flat surface so that the diaphragm is in the vertical position. Use the 1/4” x 36” tubing provided and connect one end to the (P1+) high pressure fitting on the sensor.
SYSTEM WIRING Using a conventional electronic bypass damper A conventional electronic bypass damper can be used in place of the ESP feature. When selected, the bypass damper wires to the BYPASS terminals on the panel which is then controlled by the ZPA- SPS static pressure control.
SYSTEM WIRING FAD (Fresh Air Damper) The ZP4-ESP-FAV has a fresh air damper terminal designed to be used with a 24VAC Power Open / Spring Close, 2-wire damper. The fresh air damper can be used for both timed fresh air ventilation and/or CO2 ventilation.
PANEL SETUP Switch Configurations The ZP4-ESP-FAV panel has a row of slide switches that are used to configure the panel for the specific equipment application. The switches also provide other control options. System Configuration Switch 1 selects the type of system. Heat Pump or Heat / Cool Switch 2 selects the type of Heat Pump.
PANEL SETUP GDM (Graphic Display Module) The GDM is designed to provide real-time display of discharge air, return air and outdoor air temperatures when the appropriate sensors are wired to the panel. The GDM is also used to set Low Limit, High Limit, Low Balance Point, and High Balance Point setpoints as well as initiation of the automatic upstage timer.
PANEL SETUP Setting High Balance Point High Balance Point only functions in heat pump and dual fuel configuration. It is designed to prevent the auxiliary heat from coming on if the outdoor air High BP temperature is above the High Balance Point setpoint. Press the SELECT 60 °F button to display the High BP.
PANEL SETUP Ventilation Timer The Ventilation Timer is designed to improve residential indoor air quality. This is accomplished by introducing fresh, outside air through a fresh air damper controlled by a logic panel. The panel controls the amount of fresh air required each hour based on the ASHRAE 62.2 - 2013 Ventilation and Indoor Air Quality Vent Timer Standard.
PANEL SETUP Ventilation Timer Hi Limit When an outdoor sensor is wired to the panel and Timed Ventilation is being used, the fresh air damper will remain closed if the temperature exceeds the Hi Vent Hi Limit Limit setting which is adjustable from 60° F to 90° F in 1 degree increments. The factory default is Disable.
PANEL LED DEFINITIONS AND FUNCTIONS SPEED UP Blinks when panel is in speed up mode. 3 seconds = 1 minute in speed up mode. Pushing the Speed Up button manually turns Speed Up on and off. If left on, Speed Up mode drops out in 10 minutes.
OPTIONAL NIGHT STAT SETUP AND SCHEDULING HOW IT WORKS: The UT32-NS does not control the HVAC equipment and only uses the ‘G’ fan relay to set the panel in either the occupied or unoccupied mode. This is accomplished by using the Programmable Fan option so that the fan relay is energized during occupied mode (Always On) and de-energized during unoccupied mode (Automatic).
OPTIONAL NIGHT STAT SETUP AND SCHEDULING PROGRAMMING EVENTS: When the thermostat is configured to provide 2 schedules per day (Occupied/Unoccupied), 7 days per week, each event is displayed on the LCD as DAY (Occupied) and NIGHT (Unoccupied). 1. Touch and hold Program until Mon (Monday) flashes. 2.
Page 19
www.iohvaccontrols.com For Technical Support Call Toll Free: 866-225-5032 iO-06-1376-031224...
Page 20
New HVAC equipment using A2L refrigerants (R-32, R-454B, etc.) may incorporate a Refrigerant Leak Detection System (RDS) as an added safety measure. iO HVAC Controls ESP series zone panels can accept a signal from the RDS in order to drive open all dampers when a leak is detected.
Need help?
Do you have a question about the ZP4-ESP-FAV-KIT and is the answer not in the manual?
Questions and answers