Assembly and operating instructions geba Fire Dampers EAV as of EN 15650 as insertion fire damper for use in ventilation and air-conditioning systems of buildings Tested according to EN 1366, Part 2 As of: 12/2022...
Assembly and operating instructions geba fire dampers EAV Table of Content General Information ............................................... Safety and Proper Use ............................................Transport and Storage ............................................Product description ..............................................General Installation Instructions ........................................Clearance to Load-bearing Components................................Important information ......................................Distances - Installation in wall ..........................................
Assembly and operating instructions geba fire dampers EAV General Instructions This assembly and operating manual describes the fire damper of the EAV variant. To ensure the complete functionality of the fire damper, it is absolutely necessary to read the supplied assembly and operating manual before any use and to follow the instructions listed therein. At the time of delivery, the manual is to be handed over to the system operator.
Residual Risks Fire dampers from geba undergo strict quality controls during production. In addition, a functional test is carried out before delivery. Damage during transport or installation may impair the function. The proper, undamaged condition of the fire damper must be checked before installation and during commissioning.
Product description Fire dampers of the EAV series are used as safety components within the ventilation system. The fire damper is used to prevent the spread of fire and smoke through the air duct. During operation, at normal temperature, the fire damper is open to ensure air flow in the ventilation system.
Assembly and operating instructions geba fire dampers EAV Distance to be maintained from load-bearing components ≥ 75 mm Ceiling ≥ 75 mm Wall Important Information Warning! Malfunction of the fire damper due to dirt or damage. Before installation, clean any dirt from the fire damper. Protect the fire damper from dirt and damage during installation.
Assembly and operating instructions geba fire dampers EAV Installation in solid wall Basics/Data ■ Performance class EI 90 (ve i ↔ o) S ■ Distance between dampers ≥ 200 mm ■ Distance between the fire damper and load-bearing components ≥ 75 mm Steps 1.
Assembly and operating instructions geba fire dampers EAV Commissioning/Functional testing The EAV fire damper is delivered with closed closure caps. Before inserting the EAV, these caps must be placed in the open position. Steps: 1 . Release the lock. 2 . Open the closure gap 3 .