Vacumat Eco G4 1. Liability 2. Warranty All technical specifications, data and instructions for executable actions and actions You can find the corresponding specifications in our General Terms and Conditions. that must be executed contained herein are correct at time of publication. This information is the result of our current findings and experience to the best of our knowledge.
Vacumat Eco G4 3. Copyright 4. General safety instructions This manual must be used confidentially. It may be circulated among authorized Disregard or lack of attention to the information and measures in this manual may pose personnel only. It must not be given to third parties. All documentation is protected a hazard to people, animals, the environment and tangible assets.
Vacumat Eco G4 4.2. Purpose and use of this manual Electrical installation Electrical engineering Specialist in electrical engineering/ installation The following pages list the information, specifications, measures and technical data Initial and re-inspection of Qualified person (QP) with that allow the relevant personnel to use this product safely and for the intended electrical systems certification in Electrical purpose.
Vacumat Eco G4 4.6. Incoming goods The items delivered must be compared against the items listed on the shipping note Access for unqualified and untrained persons must be restricted or forbidden. and inspected for conformity. Unpacking, installation and commissioning may be started only once the product has been checked to conform with the intended use The set-up location of the Vacuum degasser must ensure that operation, service, as stated in the order process and contract.
Vacumat Eco G4 4.11. Personal protective equipment (PPE) 4.14. Safeguards PPE must be used when carrying out potentially dangerous work and other activities The equipment supplied is equipped with the required safety devices. To test their (e.g. welding), in order to prevent or minimise the risk of personal injury if other effectiveness or restore the set-up conditions, the equipment must first be taken out measures cannot be taken.
Vacumat Eco G4 4.16. Inspection prior to commissioning, maintenance and 4.19. Maintenance and repairs re-inspection These services may only be carried out when the system is shut down or if the Vacuum degasser is not required. The Vacuum degasser must be taken out of service and These checks guarantee operational safety and its continued presence in line with guarded against unintentional re-starting until the maintenance work is finished.
For installation instructions and further documentation in various languages, visit www.flamco.aalberts.com. Further product information can be obtained from the 1. Creating a vacuum 2. Dearation 3. Topping up...
Vacumat Eco G4 5.2. System diagram 5.3. Component parts, vessels and connection assembly Pvac Psys NFE x.x A From system: Supply to Vacumat Eco G4 with gas-rich medium B to system: Return from Vacumat Eco G4 to system circulation with degassed medium C Top-up connection point (NFE x.2 - variable, optional wiring) Ball valve Pump with frequency converter...
Vacumat Eco G4 5.4. Mode of operation 5.5. Top-up The Vacumat Eco G4 works as an active degassing device with automatic top-up. Both pressure-controlled and level-controlled topping-up can be performed. Topping-up occurs when the motor ball valve (6) switches; medium then passes into Degassing is performed by removing system medium from the system circulation the Vacumat Eco G4 through the top-up opening (C) and is fed to the system by the through a bypass.
Vacumat Eco G4 5.12. Vacuum test However, if air is discharged from the vessel in the check degassing discharge phase, Requires the supply connection to be shut off when the vessel is full (coming from check degassing is followed by normal degassing; a lower negative pressure is built the system return).
Vacumat Eco G4 5.13. Connectivity options 5.15. Control unit Connectivity Designated use options Ethernet port To connect Vacumat Eco G4 to a Building Management System (BMS) via modbus or bacnet. Standard USB For saving the offline log and the configuration parameters. (aka USB-A) The second option for this port is to update the firmware of the controller (to download a new control SW)
Page 14
Vacumat Eco G4 Screen on/off hold 5 sec for FC fault 1. NO powerdown Standby input 1. NO RJ45 connector used for Modbus/ Pressure analogue out 1. 0-10V Bacnet over TCP/IP 2. GND USB-A software update Fault contact, Pot free 1 1.
Vacumat Eco G4 6.3. Connecting the electrical supply 6. Assembly The power supply connection must be created by the customer between the mains supply and the Powerbox. The mains supply, earthing system and cable protection must be provided in compliance with the requirements of the responsible power supply 6.1.
Vacumat Eco G4 Close the cover and fasten the four screws of the Powerbox again. 7. Commissioning For more detailed instructions regarding the top-up function check additional instructions at www.flamco.aalberts-hfc.com. 7.1. Initial commissioning • Document the commissioning procedure (actions and settings) •...
Vacumat Eco G4 recommendations and explanations in this manual lead to the degasser being ready for operation. For the Vacumat Eco G4 to function correctly, it is essential that the temperature sensor (Pos. 9 in the system diagram) has a reliable, fixed contact with the pump body through the tensioning strap that attaches it to the pump body.
Vacumat Eco G4 For the Vacumat Eco G4 to function correctly, it is essential that the 8. Maintenance temperature sensor (Pos. 9 in the system diagram) has a reliable, fixed contact with the pump body through the tensioning strap that attaches it to the pump body.
Page 19
Vacumat Eco G4 Warning # Action System pressure sensor The system pressure sensor is not no signal connected or defective. Check wiring from Maintenance 1 is due A periodic maintenance is due. Contact your P15 to the sensor. Top-up/degassing is local service engineer.
Vacumat Eco G4 9. Appendix 1: Technical data, general Temperature of the The temperature of the medium at the medium too low automat inlet is lower than 3°C. Top-up/ specifications degassing is disabled until resolved. Temperature of the The temperature of the medium at the medium too high automat inlet is higher than 90°C.
Vacumat Eco G4 ≥1m From system To system • Install connections at the side of the pipe – do not install at the bottom of the pipe, this will contaminate the Vacumat! • Regard the pipe length in correlation with the diameter and the number of bends. From System: To System: <...
Vacumat Eco G4 Interfaces: 10. Appendix 2: technical data and Expansion slot for specifications hardware modules of which: module slot for SD card Vacumat Eco G4 Terminal connection port Fully automatic stationary degassing and top-up machines for heating and cooling water systems. Dimensions and weights: Hydraulic connection data: Width x depth x height;...
We take your data very seriously, so we have a host of security measures in place to Remote Portal. More information can be found at https://flamco.aalberts-hfc.com/nl/ ensure your data stays safe. Below is a small subset of these measures to give an idea page/services/flamconnect-remote.
Vacumat Eco G4 12. Appendix 4: Optional accessories and their 13. Appendix 5: MeiFlow L MF Connector kit integration The MeiFlow L MF Connector kit is used to easily connect the large distribution Optional accessories and their integration Otherwise, the unit is fully set up. systems with pressure maintenance/degassing machines by means of a BigFixLock adapter plate DN150 with 2 threaded connections (1 1/4”...
Vacumat Eco G4 14. Appendix 6: Declaration of Conformity Manufacturer Aalberts hydronic flow control Hersteller Fort Blauwkapel 1, 1358 DB Almere, The Netherlands Product description Degassing and top-up devices Produktbezeichnung Entgasungs- und Nachspeiseautomaten Product type Vacumat Eco 300 (17003) Produkttyp...