Power Meter Installation for 60 Hz PowerTAP
Scope
Follow the instructions below to install and configure the 60 Hz Power Meter Acuvim II Series for the
PowerTAP system.
Safety
Safety and Preparations
Follow all standard shop practices and safety procedures.
Safety Compliance
Before beginning any procedure, ensure appropriate training, safety equipment, Lock-Out Tag-
Out (LOTO), and any other applicable policies and procedures are identified and adhered to. A
Job Safety Analysis (JSA) must be completed daily and signed by all personnel who are to be
working in the area and to this procedure.
Safety Considerations and PPE
SAFETY
INSTRUCTIONS
RIGLINE 24/7™ Support: 866.433.4345 | International: +1 281.774.5649 | E-mail:
Document ID 23-041 Rev 1 | Copyright © 2023 Nabors Drilling Technologies USA, Inc. All rights reserved.
All work tasks require the use of standard Personal Protective
Equipment (PPE) which includes Hard Hats, Flame-Resistant
Coveralls, Impact Gloves, Steel-Toed Footwear, and Safety Glasses.
Lock Out Tag Out
Step Off Hazard
Slippery Floor
Pinch Points
Electrocution Risk
1 of 24
CANRIG CONFIDENTIAL - DO NOT DISTRIBUTE
Model: 60 Hz Power Meter
Acuvim II Series
Serial #: NA
Service Bulletin # 23-041 Rev 1
CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE
support@rigcloud.com
Oct. 12, 2023

Advertisement

loading
Need help?

Need help?

Do you have a question about the PowerTAP and is the answer not in the manual?

Questions and answers

Summary of Contents for Canrig PowerTAP

  • Page 1 Serial #: NA Service Bulletin # 23-041 Rev 1 CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Power Meter Installation for 60 Hz PowerTAP Scope Follow the instructions below to install and configure the 60 Hz Power Meter Acuvim II Series for the PowerTAP system.
  • Page 2 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Installing the Current Transformers (CTs) SHOCK HAZARD – Ensure power has been removed from the DANGER transfer panel and LOTO has been applied before starting this procedure.
  • Page 3 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Installing the Current Transformers 1. Remove the covers from the transfer panel to expose the transfer switch bus bars. 2. Install the CTs on the transfer switch bus bars, as shown in Figure 2.
  • Page 4 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Wiring the Power Meter and CTs 1. Wire the power meter and the CTs in 3LL-3CT configuration, as shown in Figure 3. Figure 3: Wiring the power meter and Rogowski Coils (3LL-3CT) RIGLINE 24/7™...
  • Page 5 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Setting up the Power Meter Acuvim II For the Initial meter setup, you must set the wire mode, PT and CT ratios. Follow the steps below to do this from the meter’s display.
  • Page 6: Entering The Password

    Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Entering the Password 1. The display will show PASSWORD as shown in Figure 5. Leave the default password as 0000 and press V/A to enter the parameter selection mode. The screen will be directed to the parameter settings main menu.
  • Page 7 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Parameter Settings Main Menu 1. This screen displays options for System (SYS), Input/Output (I/O), Network (NET), and Alarm (ALM). While the cursor is in SYS, press V/A to enter the System settings menu. In this mode, you will see screens for various parameter settings.
  • Page 8 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 4. The screen displays S04: Voltage Wiring Mode (WIRE MODE U 3LL), meaning the mode is 3-Phase 3-Wire Delta. Setting...
  • Page 9 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 6. The screen displays S05: Current Wiring Mode (WIRE MODE I 3CT), meaning the current wiring mode is 3 CTs. Setting...
  • Page 10 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 8. The screen displays S06: PT1 400, meaning no potential transformer (PT) is used. Keep this setting as the default 400. Setting...
  • Page 11 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 10. The screen displays S07: PT2 400, meaning no potential transformer (PT) is used. Keep this setting as the default 400. Setting...
  • Page 12 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 12. The screen displays S08: CT1 5000, meaning the primary rating of CT is 5000. Change this value if it is different. Setting...
  • Page 13 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 14. The screen displays S09:CT2 120 60, meaning the secondary value of the CT is 120/60. Setting Load Figure 13: S09: CT2 screen To change the setting: a.
  • Page 14 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Setting up the NET settings 1. Follow steps “Entering Setting Mode” on page 5. and “Entering the Password” on page 6. to get to the Parameter Settings Main Menu. Enter the SYS parameter screen. See Figure 6 on page 7.
  • Page 15 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 5. Change the DHCP setting to “MANU”. a. Press V/A to edit the setting b. Press P or E to change the setting to “MANU”...
  • Page 16 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 7. Change the Ethernet IP address to 192.168.1.81 a. Press V/A to configure the IP address b. Press H to scroll through the digits c.
  • Page 17 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 9. Change the Subnet Mask to 255.255.255.0 a. Press V/A to configure the Subnet Mask b. Press H to scroll through the digits c.
  • Page 18 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 11. Change the Gateway address to 192.168.1.1 a. Press V/A to configure the Gateway b. Press H to scroll through the digits c.
  • Page 19 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 13. Change the DNS Primary Server to 8.8.8.8 a. Press V/A to configure the DNS Primary Server b. Press H to scroll through the digits c.
  • Page 20 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 15. Change the DNS Secondary Server to 8.8.4.4 a. Press V/A to configure the DNS Secondary Server b. Press H to scroll through the digits c.
  • Page 21 Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 17. After making any changes to the NET settings, the Ethernet module must be rebooted. a. Press V/A to reboot the module, the cursor will begin to flash b.
  • Page 22 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE Configuring Web2 Module and Time To connect to the meter and WEB2 Module, the computer’s IP address needs to be on the same network at the meter (i.e., 192.168.1.20).
  • Page 23 Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE 4. After sign-in, you will be directed to the “Dashboard” page. Click on settings. Figure 24: Settings 5. Click on Communications. Then click on Time/Date Settings. Enter the current date and time in the Device Clock field.
  • Page 24 Model: 60 Hz Power Meter Acuvim II Series Oct. 12, 2023 Serial #: NA CANRIG CONFIDENTIAL – DO NOT DISTRIBUTE References Acuvim II Series Manual • How to Program Acuvim II YouTube video: • https://www.youtube.com/watch?v=6CjgxG9pmfw&t=2s AXM-WEB2 User Manual • AXM-WEB2 Configuration Videos: •...