Copeland ZXDI Quick Installation Manual

Indoor refrigeration units

Advertisement

Quick Links

TI_Unit_ZXDI_03_EN_Rev01
Copeland ZXDI
indoor refrigeration units
Quick installation guide
1. Install the refrigeration unit according to Application Guidelines AGL_Unit_ZXDI_EN "Copeland refrigeration units
for indoor applications – ZXDI range".
2. Prefill the unit with refrigerant and set all valves into operating position.
3. Set up the unit controller (XCM25D) for the required application.
The XCM25D controller provides 2 programming levels:
▪ Pr1 with direct access
▪ Pr2 protected with a password (intended for experts)
Explanation of LED functionalities:
LED
Mode
Function
On
Compressor 1 enabled
Flashing
Anti-short cycle delay enabled
On
Condensing fans enabled
On
Bar display
Flashing
Programming mode
On
PSI display
Flashing
Programming mode
On
When browsing the service menu
Flashing
In fast access menu
How to program the "Pr1" parameters:
Access pre-
program level
Access
or
program level
Access Pr1
Select item
or
Show value
Modify
or
Confirm and
store
EXIT
When entering the programming level for the first time the display will show the rtC (real time clock) label.
▪ Press
to access parameters N01(Min)/02(Hr)/03(MdY)/04(Mon)/05(YEr) and adjust time & date. For further
details see the refrigeration unit application guidelines, section 2.13 "Parameters level 1 – Required settings".
▪ Press
or
to move from the rtC label to the Par label, in order to access programming level 1.
▪ Press
: the parameters in programming level 1 can be changed.
Application Engineering Europe
Press simultaneously for about 3 seconds to access the pre-programming
level. The message rtC (real time clock) is displayed.
Press the Up or Down key until the message Par is displayed.
Press the SET button to enter the program level. First parameter C01 is
displayed.
Select the parameter or submenu using the arrows.
Press the SET button.
Use the arrows to modify the value.
Press the SET button: the value will blink for 3 seconds, then the display
will show the next parameter.
Press simultaneously to exit the programming mode or wait for 30 seconds
without pressing any key.
1/4
TECHNICAL INFORMATION
LED
Mode
Function
On
When browsing the alarm menu
Flashing
A new alarm occurred
On
An alarm is occurring
On
Digital unloader solenoid On
On
In defrost
Evaporator fans - Liquid line
On
solenoid valve On

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZXDI and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Copeland ZXDI

  • Page 1 Copeland ZXDI indoor refrigeration units Quick installation guide 1. Install the refrigeration unit according to Application Guidelines AGL_Unit_ZXDI_EN "Copeland refrigeration units for indoor applications – ZXDI range". 2. Prefill the unit with refrigerant and set all valves into operating position.
  • Page 2 The following "Pr1" parameters must be verified before commissioning: Parameter Factory Description Unit Comments settings ZX*E ZXDI R22, R407A, R407F, R507, Refrigerant selection for regulation R404A R448A, R449A, R450A, R134a, R407C, R513A Digital compressor setpoint bar* Proportional band for compressor...
  • Page 3 Code Description Cause Action Reset Automatically: lost phase recovered and Power supply phase H08 delay elapsed. If all three phases are Lost phase error loss The compressor will trip present but the controller still shows the (3-phase units) error message, set parameters H06 and H25 to "No".
  • Page 4 DISCLAIMER: Copeland Europe GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifications, assumptions, designs and technical data contained in this document are subject to modification by us without prior notice.