Table of Contents

Advertisement

Quick Links

Operation manual
CoolOut7

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CoolOut7 and is the answer not in the manual?

Questions and answers

Summary of Contents for Conteg CoolOut7

  • Page 1 Operation manual CoolOut7...
  • Page 2 Regardless of the fact that this User Guide has been created and checked for correctness with maximum care, CONTEG, spol. s r. o. does not assume any liability for any mistakes in this documentation. CONTEG, spol. s r. o. reserves the right to modify the content. Neither are we liable for any indirect damages which may occur in relation to the delivery of the device or the use of this documentation within the limits laid down by the relevant law.
  • Page 3: Table Of Contents

    Obsah SAFETY INSTRUCTIONS ................5 ........................5 MPORTANT SAFETY INSTRUCTIONS ..........................6 EFRIGERANT HANDLING ....................7 NVIRONMENTAL AND SAFETY REQUIREMENTS ..............................7 IRST AID PRODUCT IDENTIFICATION ..............8 BASIC DESCRIPTION OF THE DEVICE ............9 ......................9 ENERAL DESCRIPTION OF UT UNIT ............................
  • Page 4 ........................36 LEANING THE HEAT EXCHANGER ALARM LIST .................... 37 DISCONNECTION AND DISPOSAL OF THE UNIT ........38 10 TECHNICAL DATA ..................39 10.1 7............................39 10.2 ......................... 40 EFAULT PARAMETER SETTINGS...
  • Page 5 Conteg, spol. s r. o. reserves the right to modify the product as well as the relevant User Guide without prior notice to the users of the preceding version of the product.
  • Page 6: Safety Instructions

    1.1 Important safety instructions • Work with this device may only be performed by duly trained personnel with the relevant Conteg, spol. s r. o. certificate. • Please observe local safety instructions! •...
  • Page 7: Refrigerant Handling

    The device may not be modified in any way without the approval of Conteg, spol. s r.o. If any part of the unit must be replaced, use only original spare parts approved by Conteg, spol. s r. o. to ensure the safety and functionality of the system.
  • Page 8: Environmental And Safety Requirements

    1.3 Environmental and safety requirements In accordance with the certificate of compliance, Conteg spol. s r. o., as the manufacturer of the device, declares that CoolOut cooling units have been manufactured and tested in accordance with the following directives: Directive 2014/35/EU – low voltage technical requirements EN 60204-1 Electrical apparatus for machines.
  • Page 9: Product Identification

    Product identification Product plate The unit may be identified by product plate, which contains basic product information. The technical specifications on the label are related to the rated conditions of operation the cooling equipment. Production label is located at the rear side of the unit. picture: 2.1...
  • Page 10: Basic Description Of The Device

    Basic description of the device The CoolOut condensing unit is basically an air / refrigerant heat exchanger that removes the heat load (thermal energy) that is taken from the indoor unit as efficiently as possible. The CoolOut unit is optimized for placement on the wall or roof of a building.
  • Page 11: Correct Usage

    3.2 Correct usage CoolOut units are designed to be connected to the Conteg indoor unit. The assembly of these units provides cooling of cabinets with technological equipment (especially IT). CoolOut units must not be used beyond the safety limits. Operating limits: Standard design of CoolOut units.
  • Page 12: Unpacking And Inspection On Receipt Of The Product

    In accordance with the company's terms of delivery, the deliverer is the sole person responsible for damage caused during the transportation of the goods. CONTEG is not liable for any damage caused by the deliverer; however, CONTEG does its best to help its customers in such a situation.
  • Page 13: Lifting And Transportation

    4.2 Lifting and transportation Danger of heavy load falling The capacity of the lifting device must be adapted to the weight of the condensing unit. The load must be placed evenly to prevent tilting. Avoid negligent and dangerous handling. Do not place any other objects on the air-conditioning unit. Check the dimensions of the unit.
  • Page 14: Installation

    • Select a location that allows easy wiring and access to the ductwork. • Avoid locations where flammable gases may escape, produce, flow or accumulate. • Unit must be secured with anchor bolts. • Maintain minimum clearances from walls. 5.2 Basic dimensions Figure 5.1 - CoolOut7 unit...
  • Page 15: Minimum Space For Installation

    5.3 Minimum space for installation Figure 5.2 – Minimum spare for installation...
  • Page 16: Recommended Layout

    5.4 Recommended layout • Observe the air flow, see arrows in the picture below. • Units must not draw heated air from another unit or other heat source. • The figure below shows the minimum distances with respect to maximum area utilization.
  • Page 17: Dimensions Of Coolout7 Mounting Points

    5.5 Dimensions of CoolOut7 mounting points • The mounting holes are dimensioned for the use of M10 screws. Figure 5.4 – dimensions of CoolOut7 mounting Figure 5.5 – detail of the mounting hole...
  • Page 18: Coolout Unit Installation Procedure

    Authorised refrigerant handling personnel will fill R410A refrigerant. Personnel with electrical authorization will install the power and communication cable, see chapter 5.9. Check the cooling function Figure 5.6 – CoolOut7 connection pipe We recommend installing the CoolOut unit with at least 2 people.
  • Page 19: Refrigerant Piping Between Indoor Unit And Outdoor Unit Coolout7

    5.7 Refrigerant piping between indoor unit and outdoor unit CoolOut7 To connect the CoolSeven unit, use a refrigerant pipe with an outside diameter of: Liquid – 1/2“ diameter, wall thickness min. 1 mm. 12 mm wall thickness min. 1 mm.
  • Page 20: Connecting The Refrigerant Piping And Filling With Refrigerant

    5.8 Connecting the refrigerant piping and filling with refrigerant CoolOut outdoor units are ready to be connected to Conteg indoor units. The connection pipe on the outdoor CoolOut unit is brazed to eliminate refrigerant leaks. The brazed joint is not limited by ambient temperature and the tightness of the joint is guaranteed even for very low outdoor temperatures.
  • Page 21: Disassembly Of Covers Before Brazing

    Disassembly of covers before brazing 5.8.1 • Front cover – 7x screw M5x10, head with 3 mm Allen. Figure 5.7 –CoolOut7 front cover • Rear cover – 2x screw M5x10, head with 3 mm Allen. Figure 5.8 –CoolOut7 rear cover...
  • Page 22: Brazing

    Brazing 5.8.2 After removing the covers, the connection points are accessible. Insert the prepared piping into the connection points on the indoor and outdoor unit. Start soldering on the indoor unit to prevent any flue gases from entering the data room through the piping. Cover the ball valves with a wet cloth, this will cool them during the brazing process.
  • Page 23: Refrigerant Circuit Tightness Checks

    Figure 5.9 – CoolOut7 pipe connection points Refrigerant circuit tightness checks 5.8.3 After all components are completely connected and before filling the circuit with refrigerant, two leak tests must be performed on the system. These are a pressure test and a vacuum test.
  • Page 24 • Pressurise the entire circuit to 15 bar via the pressure reducing valve. • Wait 5 minutes; if the pressure does not drop, continue with further testing; if the pressure drops, find one or more leaks using the bubble method, fix them and repeat the procedure •...
  • Page 25: Service Connection Points For Vacuum And Refrigerant Filling

    Service connection points for vacuum and refrigerant filling 5.8.4 Use both 7/16" #1 and #2 service valves at the same time, see picture below. Figure 5.10 – CoolOut7 service connection points for refrigerant charging and vacuum test...
  • Page 26: Vacuum Test

    Vacuum test 5.8.5 Before the CoolOut condensing unit can be started up, it is necessary to ensure that unwanted moisture is removed from the refrigeration circuit, which could cause compressor failure in the long term. The evaporation process takes time, it is not sufficient to simply achieve a given vacuum pressure, but it is important that it continues for a certain period of time.
  • Page 27: Refrigerant Filling

    The remaining amount of refrigerant can be replenished during operation. During operation, add refrigerant only to valve no.2. Type Refrigerant quantity * CoolOut7 4,2 kg * refrigerant quantity up to 30 m of pipes For each additional metre, 0.035 kg is added Maximum pipe length between indoor and outdoor unit is 75 m.
  • Page 28: Electrical Power Supply And Communication With The Indoor Unit

    Type current frequency type / value / p.of cable (A)) phases 230V 50- CoolOut7 12,8 CYKY 3x4mm 60Hz Removing the covers before connecting the power supply 5.9.1 • Front cover – 7x screw M5x10, head with 3 mm Allen hole.
  • Page 29: Electrical Power Supply - Connection Terminals

    • Electrobox cover - 7x screw M5x10, head with 3 mm Allen hole. Electrical power supply - connection terminals 5.9.2 Observe the recommended conductor cross-sections and values of the parent circuit breakers, see table in chapter 5.9. Fix the cable with the cable clamp (included in the electrical box).
  • Page 30: Terminals For Communication Cable

    5.9.3 Terminals for communication cable...
  • Page 31: Communication Cable - Connection To Coolseven / Coolteg Indoor Unit

    5.9.4 Communication cable - connection to CoolSeven / CoolTeg indoor unit Recommendation - use flexible, shielded cable min. 6 x 1,0 mm2. The maximum distance of the communication cable is 500 m. Description of the terminals clamp no. cable shielding communication with the outdoor unit 2, 3 temperature sensor behind the evaporator...
  • Page 32: Optional Accessories For Monitoring

    Optional accessories for monitoring Communication card pCOWeb Available functions A pCOWeb connected to an Ethernet network provides the following features: • WEB server: used to check or change the operating status of the cooling unit controller using a remote computer running, for example, Mozilla Firefox, Google Chrome or Microsoft Edge.
  • Page 33: Modbus Rs485 Communication Card (Optically Isolated)

    ModBus RS485 communication card (optically isolated) The ModBus RS485 communication card is used to connect information from the controller to the customer's BMS. Using the ModBus RTU communication protocol.
  • Page 34: List Of Variables On Communication

    List of variables on communication Analog variables 6.3.1 Description Direction Address Suction pressure -99.9 99.9 °C Suction temperature -99.9 99.9 Discharge pressure -99.9 99.9 °C Discharge temperature -999.9 999.9 °C Hotgas temperature -999.0 999.9 °C Outside temperature -99.9 99.9 °C Compressor temperature -999.9 999.9...
  • Page 35: Integer Variables

    Integer variables 6.3.2 Description Direction Address Alarms -32768 32767 Unit status Condenser status Position valve steps steps 9999 EVD Evolution OnBoard regulation status Indoor unit addres Condenser fans off delay Valve B position Valve B position steps 9999 New day New month New year New hour...
  • Page 36 Oil protection active PSD fan start Request to copy NEW_DAY into DAY Request to copy NEW_MONTH into MONTH Request to copy NEW_YEAR into YEAR Request to copy NEW_HOUR into HOUR Request to copy NEW_MINUTE into MINUTE...
  • Page 37: Maintenance

    For information on service partners, please contact cooling@conteg.cz Cleaning the heat exchanger Cleaning of the heat exchanger blade surface can only be done by trained service personnel.
  • Page 38: Alarm List

    Alarm list The following table lists all alarms that can occur in the system. Alarm text Code Cause Stops Probe Bnn ALAnn Failure of one of the sensors. The Nothing. An incorrect sensor is marked with the appropriate sensor reading can terminal.
  • Page 39: Disconnection And Disposal Of The Unit

    Disconnection and disposal of the unit This refrigeration unit may only be uninstalled by competent and properly trained persons with the appropriate permit (refrigerant disposal). Before any manipulation of the unit, first disconnect the power supply and secure it against reconnection.
  • Page 40: Technical Data

    Technical data 10.1 CoolOut7 Unit type AC-ODX-07-0 AC-ODX-07-S Connected indoor unit CoolSeven / CoolTeg CoolSeven / CoolTeg BASIC INFORMATION Cooling system Direct expansion Direct expansion Nominal cooling capacity (1) Operating ambient temperatures °C -40 * až +47 -20 až +55...
  • Page 41: Default Parameter Settings

    10.2 Default parameter settings Description Data type DefaultValue U.M. DefMinLim DefMaxLim Band condenser control Analog 30.0 999.9 Band hot gas bypass control Analog 10.0 GradC 999.9 Circuit alarms delay Integer 120 s Low pressure alarm delay after start Integer 90 s Compressor time between starts Integer 360 s...
  • Page 42 Description Data type DefaultValue U.M. DefMinLim DefMaxLim Condenser fans ramp start power Analog 100.0 % Condenser fans off delay power Analog 100.0 % Suction pressure zone 1a Analog 12.5 BAR 50.0 Suction pressure zone 1a delay Integer 30 s Discharge pressure zone 1a Analog 16.8 BAR 50.0...
  • Page 43 Notes...

Table of Contents