SC-Series Refrigerant
Leak Detector
Wiring and Controller Setup
General
The SC refrigerant leak sensor is a series of transmitters for measuring concentration of
different gases. The transmitter is available in the Standard Room Type. The sensor
heads are semi-conductive, which provides a long lifetime and stability, but with limited
selectivity.
The transmitter gives a non-linear output signal (4 to 20mA or 0 to 10V DC) proportional
to the gas concentration. For long wiring installations, it is recommended to use the
current output signal to minimize the risk of interference. Output signal mode is set by
jumper (JP1).
*
Technical Data
Table 1: Sensor Technical Specs
Sensor Type
Response Time (T90)
Operating Temperature
Operating Humidity
Dimensions
Housing
Output Signal
Calibration
Lifetime Sensor
Power Supply
Cable gland
*
Specifications subject to change
026-4426 R2
©2024 Copeland LP.
Semiconductor
< 10 seconds
-40°F to 122°F (-40°C to 50°C)
10 to 90% Rh (non condensing)
130x82x56 mm
Polycarbonate / ABS
4 to 20mA (max 500 ohm) or 0 to 10V DC
Zero/span ≥ once per year
> 5 years (replacement recommended every 5
12 to 30V DC (Recommended 24VDC @ 15W,120V, DIN Rail mount P/N 250-2541)
1 x M16
INSTRUCTION GUIDE
th
year or when unit cannot be calibrated)

Advertisement

loading
Need help?

Need help?

Do you have a question about the SC Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Copeland SC Series

  • Page 1 > 5 years (replacement recommended every 5 year or when unit cannot be calibrated) Power Supply 12 to 30V DC (Recommended 24VDC @ 15W,120V, DIN Rail mount P/N 250-2541) Cable gland 1 x M16 Specifications subject to change 026-4426 R2 ©2024 Copeland LP.
  • Page 2 Enclosure Dimensions Mounting 026-4426 R2 ©2024 Copeland LP.
  • Page 3 Before moving the JPI jumper: 1. Disconnect power NOTE 2. Move jumper 3. Cycle power to save the new setting Leak Sensor Setup (4-20 mA to 1-5 VDC) Connected to MultiFlex Boards Need 250-ohm Resistor Required 026-4426 R2 ©2024 Copeland LP.
  • Page 4 Voltage - 1000 PPM End Point 809-1201 R404a 0-2000 2.5 V = 1000 PPM 809-1202 R407a 0-2000 3.0 V = 1000 PPM 809-1203 R448a .5-6.5 0-2000 3.5 V = 1000 PPM P/N 809-1201 Output vs PPM R404A 026-4426 R2 ©2024 Copeland LP.
  • Page 5 P/N 809-1202 Output vs PPM R407A P/N 809-1203 Output vs PPM R448A 026-4426 R2 ©2024 Copeland LP.
  • Page 6 In your E3 or Site Supervisor, add a 16AI Board and go to the application page to set up the leak sensor settings. Set up the leak sensor settings as they appear on this screen: 026-4426 R2 ©2024 Copeland LP.
  • Page 7 UltraSite Setup To set up the leak detector using UltraSite, open and Or right-click on E2 and select Offline Programming: login: Right-click on the site and choose Connect: Right-click on E2 and select Add New Application: 026-4426 R2 ©2024 Copeland LP.
  • Page 8 Assign the point to the MultiFlex Board (this is the point Close: you connect the sensor to). Highlight the point and click OK: 11. The point is now visible in the tree: 026-4426 R2 ©2024 Copeland LP.
  • Page 9 2.5 V = 1000 PPM 809-1202 R407a 0-2000 3.0 V = 1000 PPM 809-1203 R448a .5-6.5 0-2000 3.5 V = 1000 PPM E2 Setup    Log into the E2 and press (Input Status screen). 026-4426 R2 ©2024 Copeland LP.
  • Page 10 Copeland reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.

This manual is also suitable for:

809-1201809-1202809-1203